Page 31
About the FLEX I/O Diagnostic Output Module
29
You must connect dummy resistors to unused sensor power ports to mask the diagnostic function. If these external resistors are not used, the module’s sensing circuitry will not detect the intended voltage or current and signal a module fault. The channel fault indicator and the module’s fault indicator will light, and the module’s open and error bits are set, thus rendering fault detection of the remaining channels useless. The recommended value of this dummy resistor is 10 KΩ (+10%), 1/8 W (or larger). The resistor is wired between unused output channels and common. The figure depicts wiring of a dummy resistor.
+
User Power
The module monitors current and voltage at each output channel terminal, and monitors the user supply for reverse supply voltage. The figure below shows the location of these fault monitors within the 1794-OB16D diagnostic output module.
Reverse
Reverse Voltage Monitor Output Indicator
Output
Current Limiting Thermal Prot. Output FET
Open Wire Detect Current
Flexbus Interface
Diagnostic Fault Detection
Open
Open Wire Monitor Fault Indicator V+ Short
Output
Shorted Output Monitor 40117C
Publication 1794-UM061A-EN-P - July 2006
Page 32
30
About the FLEX I/O Diagnostic Output Module
The output open-wire current monitor detects a fault condition if the output OFF-state current drops below 0.1 mA. Output channel shorts are protected by a current limit and over-temperature thermal sensor built into the output device. For overcurrents, the output device’s internal current limit is tripped and the output voltage begins to collapse. For a sustained overcurrent or direct output short the output device’s thermal limit is tripped and the output is automatically turned off. This shorted condition is monitored by the on-state output channel short monitor. It detects a short if the output voltage drops below 2V. If the on-state output channel short is removed, the output will automatically recover and voltage will appear at the output, thus driving the attached load on. ATTENTION
A shorted output channel turns off and deenergizes a connected load. Following removal of the short the output channel becomes active and will reenergize a connected load. Be careful for unexpected machine operation following removal of an active output channel short.
Optocouplers isolate FLEX I/O system-side logic voltages from the user power supply and output channels. This provides protection against field-side voltages and transients.
Module Protection Functions
The module protection functions consist of output device short protection, external power supply reverse voltage protection, and power supply loss detection
Output Device Short Protection Diagnostic digital outputs have internal electronics to prevent too much current from flowing through the module. This feature protects the module, attached wiring, and load from damage. Current limit and over-temperature thermal sensor built into the output device protect against output shorts. For an overcurrent, the output device’s internal current limit trips and output voltage collapses. The output device’s thermal limit is tripped and the output is automatically turned off if an output short circuit is detected. This shorted condition is monitored by the on-state output channel short monitor. It will detect a short if the output voltage drops below 2V. Under shorted conditions, the shorted channels indicator turns red, the module fault indicator turns red and the short fault bit and module error bit are set. If the on-state output channel short is removed, the output automatically recovers and voltage appears at the output, thus driving the attached load on.
Publication 1794-UM061A-EN-P - July 2006
Page 33
About the FLEX I/O Diagnostic Output Module
31
External Power Supply Reverse Voltage If the external user power supply polarity is incorrect, the module is protected and reports a reverse user voltage fault. The reverse voltage condition must be at least -10V to detect a fault. The modules fault indicator turns red and the reverse fault bit is set. The module error bit is also set. When the correct user power supply polarity is applied, the module Fault indicator is off and the reverse fault bit is not set.
User Power Supply Loss Detection The module does not check for presence of the external user power supply. You can detect user power loss by wiring any spare 24V dc input on a 1794-IB16D input module or 1794-IB16 input module to the power leads of the power supply for the 1794-OB16D.
(1794-IB16D shown)
Output Fault & Idle States With Network Communication Failure Configure module outputs for fault states, (either all on, all off or Hold Last State), in the event of a network communication failure (fault state) or switchover to Program mode (idle state). For example, if your module is configured so that the state of the outputs turn off during Program (idle) mode, any on-state outputs will turn off when in idle mode (processor keyswitch placed in Program mode). Refer to documentation for your FLEX I/O adapter and associated processor or controller for further information.
Indicator Status Information The 1794-OB16D diagnostic output module has status indicators that allow you to check the module health and operational status.
Publication 1794-UM061A-EN-P - July 2006
Page 34
32
About the FLEX I/O Diagnostic Output Module
• Channel I/O Status- This indicator displays the on/off state of each output channel, as well as channel wiring fault conditions: – Off indicates the output channel is off with no faults. – Yellow indicates the output channel is on with no faults. – Red indicates either an output channel open or short condition. • Module Fault Status- This indictor turns red for individual output channel opens, shorts or module reverse power conditions. With no fault, the module fault indicator turns off.
Module Limitations
Unused Output Channels You must connect dummy resistors to unused output channels to mask the diagnostic function. If these external resistors are not used, the module’s sensing circuitry will not detect the intended voltage or current and signal a module fault. The channel fault indicator and the module’s fault indicator will light. The module’s open and error bits are set, thus rendering fault detection of the remaining channels useless. The recommended value of this dummy resistor is 10 Kohms (+10%), 1/8 W (or larger). The resistor is wired between unused output channels and common.
Configure Your Output Diagnostic Module
The configuration data table is shown below. 1794-OB16D Configuration Data Table
Dec.
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Oct.
17
16
15
14
13
12
11
10
07
06
05
04
03
02
01
00
Read 1
Not used
Write 2
O15
Where
O = Output Diagnostic status; Bit 00 = module error; Bit 01 = external power reverse polarity error; Bit 02 = output short error; Bit 03 = output open wire error
O14
Read Diagnostics Status
O13
O12
O11
O10
O9
O8
O7
O6
O5
O4
O3
02
O1
O0
The outputs are written in Word 2. Decimal bit 00 is the first output and decimal bit 15 is the last output. Diagnostic status is read from Word 1: Bit 00: Module Error Bit Bit 01: External Power Reverse Polarity Error Bit Bit 02: Output Short Error Bit Bit 03: Output Open Wire Error Bit Publication 1794-UM061A-EN-P - July 2006
Page 35
Chapter
4
Configuring Modules for Communication on a Remote I/O Network
Chapter Objectives
This chapter provides you with the RSLogix 5000 software steps you need to configure a 1756-DHRIO module, remote adapter module and block transfer and digital modules for use with a ControlLogix controller on a Remote I/O (RIO) network. For this Information:
See page:
Add a DHRIO module to the project
34
Add a 1794-ASB adapter module to the project
37
Configuring Block Transfer Modules
40
Create a Block Transfer (Read or Write) Message Instruction
42
Remote I/O Network
ControlLogix Chassis with 1756-DHRIO module 1771-ASB Adapter PLC-5 Controller in Adapter Mode
1747-ASB Adapter 1794-ASB Adapter
33
Publication 1794-UM061A-EN-P - July 2006
Page 36
34
Configuring Modules for Communication on a Remote I/O Network
Add a 1756-DHRIO Module
The 1756-DHRIO module provides two configurable channels that can either send and receive messages over DH+ or scan remote I/O devices. When a channel is configured for remote I/O, the 1756-DHRIO module is designed to function as a remote I/O scanner for a ControlLogix controller. I/O data is exchanged between the 1756-DHRIO module and: • remote adapters on the remote I/O link • the ControlLogix controller • remote block transfer modules Use the following steps to add a 1756-DHRIO module to your RSLogix5000 project. 1. Start the RSLogix 5000 software. 2. Begin a new project or open an existing project offline. 3. Add the 1756-DHRIO Module to the project.
A. Right-click on I/O Configuration folder in the controller organizer and select New Module from the pull-down menu.
B. Click on the + to the nonisolated left of the Communications group to display the communication modules available.
C. Select the series of 1756-DHRIO module you are using in your configuration.
D. Click OK.
Publication 1794-UM061A-EN-P - July 2006
Page 37
Configuring Modules for Communication on a Remote I/O Network
35
4. Configure the 1756-DHRIO module parameters. A. Define the following parameters: • Name • Slot • Type • Baud Rate • Revision • Electronic Keying • Open Module Properties Refer to the 1756-DHRIO Module Properties Dialog Box table for information on how to fill-in the dialog box. Click OK. 1756-DHRIO Module Properties Dialog Box In This Field:
Do the Following:
Name
Type a name for the module (i.e.,DHRIO_module_in_slot_1).
Slot
Type or select the slot number where the module is installed.
Type
Select RIO for the Channel that is connected to the remote I/O network. If only one channel is configured as a remote I/O scanner, we recommend that you use Channel B. If you configure Channel A as a remote I/O scanner, you cannot use the programming terminal din connector on the front of the 1756-DHRIO module.
Channel A Channel B Baud Rate
Specify a baud rate for the Remote I/O channel. This value defines the communication rate at which the 1756-DHRIO module scans the remote I/O modules.
Revision
Select the major and minor revision level for your module.
Electronic Keying
Specify a keying option. When you configure a module, you specify the slot number for the module. However, it is possible to place a different module in that slot, either on purpose or accidently. Electronic keying lets you protect your system against accidental placement of the wrong module in a slot. The keying option you choose determines how closely a module in a slot must match the configuration for that slot. If:
Then Select:
all of the following must match: • type
Exact Match
• catalog number • vendor • major and minor revision number
Open Module Properties all information except the minor revision number must match
Compatible Module no information must match
Disable Keying
Ensure that this box is checked to access all of the available configuration screens for the module. If this box is not checked, clicking OK assigns the default parameters for the remaining configuration fields.
Publication 1794-UM061A-EN-P - July 2006
Page 38
36
Configuring Modules for Communication on a Remote I/O Network
5. Specify parameters on 1756-DHRIO Connection tab screen. A. Define the following parameters: • Requested Packet Interval • Inhibit Module • Major Fault on Controller if Connection Fails While in Run Mode Refer to the Connection Tab Screen table for information on how to fill-in the dialog box. B. Click OK.
The 1756-DHRIO module is now listed in the controller organizer
. Connection Tab Screen In This Field: Requested Packet Interval (RPI)
Inhibit Module
Do the Following: Define the requested rate of packet arrival. This value defines the rate for status information about the DHRIO module to be sent to the controller. We recommend that this value be equal to the overall scan time of your program. The parenthetical values to the right of this field display the module-dependant minimum and maximum values. Check/clear this box if you want to disable/enable connection to the DHRIO module when the controller goes online. If this box is checked, and you go online, the controller organizer displays an inhibit icon next to the module. Although the 1756-DHRIO module connection is inhibited, the DHRIO scanner (Channel A or B) changes to program mode and continues to scan the remote I/O adapters on the remote I/O network. When inhibited, the 1756-DHRIO module accepts configuration from any ControlLogix controller in the control system. ATTENTION
Major Fault on Controller if Connection Fails While in Run Mode
Inhibiting the DHRIO module causes the connection to the module to be disabled and can result in the loss of data.
Determine what action you want the controller to take if communication is lost to the DHRIO module. Place a checkmark in this box if you want a major fault to occur on the controller if the connection between the controller and the DHRIO module is lost. Leaving this box unchecked means that failure to connect to the DHRIO module will not cause a major controller fault.
Publication 1794-UM061A-EN-P - July 2006
Page 39
Configuring Modules for Communication on a Remote I/O Network
Add a 1794 Remote Adapter Module
37
The following steps show you how to add a 1794-ASB module to your project and set the configuration parameters. 1. Add the 1794-ASB adapter module to the controller organizer.:
A. From controller organizer, select the channel you are using for your configuration then, right-click to display the pull-down menu. In this example, only channel B is connected to remote I/O. You can connect both channels to remote I/O simultaneously if necessary. If only one channel is connected to remote I/O, we recommend that you use channel B. If you connect channel A to remote I/O, you cannot use the programming terminal din connector on the front of the 1756-DHRIO module. B. Choose New Module. C. Click on the Communications group to expand the tree and then, choose the 1794-ASB Adapter module from the list. D. Click OK. 2. Define configuration parameters for the 1794-ASB module. A. Define the following parameters: • Name • Rack # • Starting Group • Size • Open Module Properties Refer to the 1794-ASB Adapter Module Properties Dialog Box table for additional information. B. Click OK.
Publication 1794-UM061A-EN-P - July 2006
Page 40
38
Configuring Modules for Communication on a Remote I/O Network
1794-ASB Adapter Module Properties Dialog Box In This Field:
Do the Following:
Name
Type a name for the adapter module. We recommend that you use a name that identifies the I/O type for the adapter module you are configuring.
Rack # (Octal)
Select the Remote I/O network rack ID for the rack.
Starting Group
Select the starting group of this rack based on the switch setting of the 1794-ASB adapter module.
Size
Select the rack size for the adapter based on the switch setting of the 1794-ASB adapter module.
Open Module Properties
Ensure that this box is checked to access all of the available configuration screens for the adapter module. If this box is not checked, clicking OK assigns the default parameters for the remaining configuration fields.
3. Specify parameters on 1794-ASB adapter module Connection tab screen. A. Define the following parameters: • Requested Packet Interval • Inhibit Module • Major Fault on Controller if Connection Fails While in Run Mode Refer to the 1794-ASB Connection Tab Configuration Parameters table for additional information. B. Click OK.