Page 21
2 About the FLEX I/O Diagnostic Input Module
Introduction
About the 1794-IB16D Diagnostic Input Module
In this chapter, you will learn about the diagnostic input module, cat. no. 1794-IB16D. For Information About
See Page
About the 1794-IB16D Diagnostic Input Module
19
Diagnostic Fault Detection
21
Indicator Status Information
2
Module Limitations
24
Configure Your Diagnostic Input Module
26
The 1794-IB16D diagnostic input module provides 16 points of 24V dc sinking inputs with open-wire, short-circuit, and user supply reverse polarity diagnostic features. Each input signal has an associated sensor power connection. The module monitors current and voltage at each input channel sensor power terminal. The module detects: • an open fault if the sensor-power current drops. • a short fault if the sensor-power voltage goes low. • a reverse-polarity fault if reverse voltage is applied to the user terminals.
19
Publication 1794-UM061A-EN-P - July 2006
Page 22
20
About the FLEX I/O Diagnostic Input Module
Wiring Input Sensors You must use a 1794-TB32 or 1794-TB32S terminal base unit with the 1794-IB16D diagnostic input module. See installation instructions ldkg df;l 1794-IN096 for complete information. 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
A Input Channels 0-15 16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
NC
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
NC
34
35
36
50
51
NC
+V1 COM1 +V1 COM1 +V1 COM1 +V1 COM1 +V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC
B Sensor Power Terminals for Channels 0-15 37
38
39
40
41
42
43
44
45
46
47
48
49
C Sensor Common and User Power Common: Terminals C-36, C-38, C-40, C-42, C-44, C-46, C-48 and C-50. +V1 Terminals C-35, C-37, C-39 and C-41 are not used User power (+) Voltage: Terminals C-43, C-45, C-47 and C-49 COM1 and COM2 are connected together in the module.
Two-wire input devices connect to the input and sensor power terminals; 3-wire devices use input, sensor power and common terminals. You can wire 2-wire and 3-wire sensors to the FLEX I/O 1794-TB32 or 1794-TB32S terminal base units.
Unused sensor-power ports or open-contact input devices must use a dummy resistor to mask the diagnostic function. If these external resistors are not used, the module’s fault indicator will light, along with the module’s error bits, thus rendering fault detection of the remaining channels useless. The recommended value of this dummy resistor is 20 kΩ (+10%), 1/8 Watt (or larger). Connect the resistor between sensor power and input signal or between sensor power and common.
Publication 1794-UM061A-EN-P - July 2006
Page 23
About the FLEX I/O Diagnostic Input Module
21
.
.
The module monitors current and voltage at each input channel sensor power terminal, and monitors the user supply for reverse user supply voltage. The figure below shows the location of these fault monitors in the 1794-IB16D diagnostic input module.
+
User Power
Reverse Voltage Monitor
PTC
Reverse
Shorted Input Monitor
Short V+ Fault Indicator
Sensor Power
Open Wire Monitor
Open
Flexbus Interface
Diagnostic Fault Detection
Input
Input
Input Circuit Indicator
Publication 1794-UM061A-EN-P - July 2006
Page 24
22
About the FLEX I/O Diagnostic Input Module
Sensor Power Open and Short Circuit Detection The sensor-power open-wire current monitor detects a fault condition if the sensor-power current drops below 50 μA. Sensor-power shorts are protected by the positive temperature coefficient (PTC) resistor in series with each sensor power output (16 total). For overcurrents or shorts, the PTC resistor heats up, the resistance increases and the sensor power output opens, similar to a fuse opening. This shorted condition is monitored by the sensor power voltage monitor. It detects a short if the sensor power voltage disappears. When the short is removed, the PTC resistor cools down and the previously shorted sensor-power port, sensor power is automatically restored and normal operation continues. The module’s embedded monitors detect open and short conditions.
When a fault is detected: • the corresponding channel’s red indicator lights. • the module’s red fault indicator lights. • the module’s open, short or reverse error bit is set. • the module error bit is set. The input circuit is a conventional sinking style with an input voltage dropping resistor. The yellow input indicator is in series with the input signal (field-side indication). FLEX I/O system-side logic voltages are isolated from the user power supply and input channels by optocouplers. This provides protection against field side voltages and transients.
Publication 1794-UM061A-EN-P - July 2006
Page 25
About the FLEX I/O Diagnostic Input Module
23
User Power Supply Reverse Voltage Detection If the external user power supply is miswired (incorrect polarity), the module is protected and reports a reverse user voltage fault. The reverse voltage condition must be at least -10V to detect a fault. The module’s Fault indicator turns red and the reverse fault bit is set. The module error bit is also set. When the correct user power supply polarity is applied, the module Fault indicator is off and the reverse fault bit is not set.
User Power Supply Loss Detection The module does not check for presence of the external user power supply. Detection can be accomplished by wiring an input channel to the user supply. Any 24V dc input can be used. You can wire a 1794-IB16D diagnostic input module or 1794-IB16 input module to monitor the user supply as shown below:
(1794-IB16D shown)
Indicator Status Information
The 1794-IB16D diagnostic input module has indicators that let you check the module health and operational status. The following status can be checked with the indicators. • Channel I/O Status - This indicator displays the ON/OFF state of the input channel, as well as channel wiring fault conditions: – Off indicates the input channel is off with no faults. – Yellow indicates the input channel is on with no faults. – Red indicates either a channel sensor power open or short condition. • Module Fault Status- This indictor turns red for any individual input channel open, short or module reverse power conditions. With no fault, the module fault status indicator turns off.
Publication 1794-UM061A-EN-P - July 2006
Page 26
24
About the FLEX I/O Diagnostic Input Module
Module Limitations
Input Voltage Derating You must derate the input voltage applied to each input channel, based on operating ambient temperature, to keep module power dissipation within an acceptable level.
30 25 Input Voltage (V)
31.2 26.4
20 15 10 5 0
10
20
30
40
Ambient Temperature
50 55 (0°C)
Sensor-Power Derating You must derate the allowable current from each channel sensor-power port based on operating ambient temperature to keep module power dissipation to an acceptable level.
Sensor Power Current (mA)
Ambient Temperature (° C)
Publication 1794-UM061A-EN-P - July 2006
Page 27
About the FLEX I/O Diagnostic Input Module
25
Unused Sensor Power Ports You must connect dummy resistors to unused Sensor Power ports to mask the diagnostic function. If external resistors are not used, the module's sensing circuitry will not detect the intended voltage or current and not report that a fault exists. The module’s fault and open-channel indicators light, and the module’s open and module error bits are set, thus rendering fault detection of the remaining channels useless. The recommended value of this dummy resistor is 20 KΩ (+10%), 1/8 W (or larger).
Open Contact Mechanical Switches and Relays The module's sensing circuitry must detect a minimum current level to conclude that an open circuit does not exist. Electronic input field devices typically have sufficient leakage current to satisfy the minimum requirement. However, hard contacts have no leakage current, so you must add dummy resistors in parallel to the hard contacts to supply the minimum current needed for the module to sense that an open circuit does not exist. The recommended resistor value is 20 kΩ (+10%), 1/8 W (or larger). Placement of the dummy resistor at the field device also allows for monitoring of field wiring conditions. Connect the resistor between sensor power and input signal, or between sensor power and common.
Sensor Power Internal Voltage Drop The modules sensor power circuit exhibits an internal voltage drop. This voltage drop can be as large as 2.2V for all operating conditions. You must subtract 2.2V from the value of your external user power supply to determine the voltage applied to power attached sensors. Make sure this voltage meets sensor requirements. Consult the data sheet for your sensor to determine what voltage is necessary.
User Power +
PTC Resistor
Overcurrent causes PTC to open
Off-Wire Current Monitor Fault if: 1 < 50 μA
Sensor Power
24V dc External User Power Supply
Sensor
Vsensor = (Ext Pwr) - 2.2V
Voltage Drop = 2.2V maximum User Power -
Input
Publication 1794-UM061A-EN-P - July 2006
Page 28
26
About the FLEX I/O Diagnostic Input Module
Configure Your Diagnostic Input Module Dec. Oct. Read 1 Read 2 Write 1 Where:
The configuration and input filter selection table are shown below. Data Table & Input Filter Time Selection
15 14 13 12 11 10 09 08 17 16 15 14 13 12 11 10 I 15 I 14 I 13 I 12 I 11 I 10 I 9 I8 Not used Not used Input Filter FT 0-15 I = Input FT = Input filter time Diagnostic status; Bit 00 = module error; Bit 01 = external power reverse polarity error; Bit 02 = sensor power short error; Bit 03 = sensor power open wire error
07 07 I7
06 06 I6
05 05 I5
04 04 I4
03 02 01 00 03 02 01 00 I3 I2 I1 I0 Read Diagnostics Status
Not used
The inputs are read in Word 1. Bit 00 is the first input and decimal bit 15 is the last input. Diagnostic status is read from Word 2: Bit 00: Module Error Bit Bit 01: External Power Reverse Polarity Error Bit Bit 02: Sensor Power Short Error Bit Bit 03: Sensor Power Open Wire Error Bit
Input Filter Times Input filter times are configurable on a module basis. Both off-to-on and on-to-off times are set by write Word 3. The default filter time is 0.25 ms.
Publication 1794-UM061A-EN-P - July 2006
Bits 10 09
08
0 0 0 0 1 1 1 1
0 1 0 1 0 1 0 1
0 0 1 1 0 0 1 1
Description Filter time for inputs 0 thru 15 Filter time 0 (default) Filter time 1 Filter time 2 Filter time 3 Filter time 4 Filter time 5 Filter time 6 Filter time 7
Filter Time Off-to-On/ On-to-Off 0.25 ms 0.5 ms 1 ms 2 ms 4 ms 8 ms 16 ms 32 ms
Page 29
Chapter
3
About the FLEX I/O Diagnostic Output Module
Introduction
About the 1794-OB16D Diagnostic Output Module
In this chapter, you will learn about the diagnostic output module, cat. no. 1794-OB16D. For Information About
See Page
About the 1794-OB16D Diagnostic Output Module
27
Diagnostic Fault Detection
29
Module Protection Functions
30
Module Limitations
32
Configure Your Output Diagnostic Module
32
The 1794-OB16D diagnostic output module provides sixteen 24V dc sourcing outputs with open-wire, short-circuit, and user supply reverse polarity diagnostic features. The module monitors current and voltage at each output channel. The module detects: • an open fault if no current is present at the output terminal. • a short fault if no voltage is present at the output terminal. • a reverse-polarity fault if reverse voltage is applied. When an open or short fault is detected: • the corresponding channels red indicator is illuminated. • the module’s red fault indicator is illuminated. • the module’s open or short error bit is set. • the module error bit is set. When a user supply reverse-polarity fault is detected: • the modules red fault indicator is turned on, • and the reverse error bit is set. • the module error bit is set.
27
Publication 1794-UM061A-EN-P - July 2006
Page 30
28
About the FLEX I/O Diagnostic Output Module
Wiring Output Loads You can use the 1794-OB16D diagnostic module with the 1794-TB2, 1794-TB3, or 1794-TB3S terminal base units. 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
A
17
16
Output Channel 0-15
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
B 0 -V Common 34
35
36
37
38
39
Common 40
41
42
43
44
45
46
47
48
-V Common
49
50
51
C Voltage In +V
Terminals 35 thru 50 not available on 1794-TB2
Voltage (24V dc)
Voltage Out +V
(1794-TB3 shown)
User power can be wired to the (+) voltage and common terminals directly, or power can be daisychained from the FLEX I/O terminal base units on the DIN rail. Output channels are not isolated from one another. All 16 channels share a common return (group isolation from FLEX I/O system-side logic voltages). FLEX TB2/3/3S Terminal Base Output
A0-A15
Output Device Common
24V dc External User Power Supply
Publication 1794-UM061A-EN-P - July 2006
V+ V-
B17-B32
C34 B16