FLEX I/O Diagnostic Modules, Catalog Numbers 1794-IB16D, 1794-OB16D, User Manual, pages 11 to 20
Pages 11 to 20 of 132
The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Allen-Bradley 1794-OB16
Page 11
Preface
Catalog Number
Voltage
Description
9
Publications Installation Instructions
User Manual
1794-IE12
24V dc
12 Input Analog Module
1794-IN106
1794-OE12
24V dc
12 Output Analog Module
1794-IE8XOE4
24V dc
8 Input/4 Output Analog Module
1794-IE8H
24V dc
8 HART Input Module
1794-IN108
1794-OE8H
24V dc
8 HART Output Module
1794-IN109
1794–IR8
24V dc
8 RTD Input Analog Module
1794-IN021
1794–IT8
24V dc
8 Thermocouple Input Module
1794–IRT8
24V dc
8 Thermocouple/RTD Input Module
1794-IN050
1794–6.5.12
1794–IJ2
24V dc
2 Channel Frequency Input Module
1794-IN049
1794–6.5.11
1794–ID2
24V dc
2 Channel Frequency Input Module
1794-IN063
1794–6.5.15
1794–IP4
24V dc
2 Channel Pulse Counter Module
1794-IN064
1794–6.5.16
1794–VHSC
24V dc
Very High Speed Counter Module
1794IN067
1794–6.5.10
1794–IC16
48V dc
16 Sink Input Module
1794-IN105
1794–OC16
48V dc
16 Source Output Module
1794–IA8
120V ac
8 Input Module
1794–IA8I
120V ac
Isolated 8 Input Module
1794–IA16
120V ac
16 Input Module
1794–OA8
120V ac
8 Output Module
1794–OA8I
120V ac
Isolated 8 Output Module
1794–OA16
120V ac
16 Output Module
1794–IM8
220V ac
8 Input Module
1794–OM8
220V ac
8 Output Module
1794-UM063 1794–6.5.4 1794–6.5.7
1794-IN102
1794-IN103
1794-IN104
Publication 1794-UM065B-EN-E - July 2006
Page 12
10
Preface
Catalog Number
Voltage
Description
Publications Installation Instructions
1794–TB2
Cage Clamp Terminal Base
1794-IN092
1794–TB3
Cage Clamp Terminal Base
1794–TB3S
Spring Clamp Terminal Base Unit
1794–TB3T
Temperature Terminal Base Unit
1794–TB3TS
Spring Clamp Temperature Base Unit
1794–TB3G
Terminal Base Unit
1794–TB3GS
Spring Clamp Terminal Base Unit
1794–TB32
Cage Clamp Terminal Base Unit
1794–TB32S
Spring Clamp Terminal Base Unit
1794–TBN
Terminal Base Unit
1794–TBNF,
Fused Terminal Base Unit
, 1794-TB3GK
Conformally Coated Terminal Base Unit
1794-TB3K
Conformally Coated Terminal Base Unit
1794-TBNFK
Conformally Coated Fused Terminal Base Unit
1794-TB37DS, -TB62DS, TB37EXD4VM8, -TB37EXD4CM8, -TB62EXD4X15
D-Shell Terminal Base Units and Distribution Boards
1794-IN107
1794–CE1, –CE3
Extender Cables
1794–5.12
1794–NM1
Mounting Kit
1794–5.13 1794-IN069
1794–PS13
24V dc
Power Supply
1794–PS3
24V dc
Power Supply
1797–IBN16
See note
16 NAMUR Digital Input Module
1797-5.7
1797–OB4D
See note
4 NI, Ex Source Digital Output Module
1797-5.6
1797–IE8, -IE8H
See note
8 Input Module
1797-5.5
1797–IE8NF
See note
8 Selectable Filter Analog Input Module 1797-5.31
1797–OE8, -OE8H
See note
Analog 8 Output Module
1797-5.3
1797–IRT8
See note
8 Thermocouple/RTD Input Module
1797-5.4
1797–IJ2
See note
2 Channel Frequency Input Module
1797-5.9
Cage Clamp Terminal Base Spring Clamp Terminal Base
1797-5.1 1797-5.2
FLEX Ex
1797–TB3 1797–TB3S
Publication 1794-UM065B-EN-E - July 2006
User Manual
Page 13
Preface
Catalog Number
Voltage
Description
11
Publications Installation Instructions
1797–BIC
See note
I.S. Bus Isolator
1797-5.13
1797–CEC
See note
FLEX Ex Bus Connector
1797-5.13
User Manual
Note: Intrinsically Safe Voltage
For more information on DeviceNet modules in Logix5000 systems, see publication DNET-UM004, DeviceNet Modules in Logix5000 Systems. For more information on ControlNet modules in Logix5000 systems, see publication CNET-UM001, ControlNet Modules in Logix5000 Systems. For more information on EtherNet/IP modules in Logix5000 systems, see publication ENET-UM001, EtherNet/IP Modules in Logix5000 Systems.
Publication 1794-UM065B-EN-E - July 2006
Page 14
12
Preface
Notes:
Publication 1794-UM065B-EN-E - July 2006
Page 15
Chapter
1
1794 FLEX I/O Diagnostic Digital Modules Overview
Introduction
General Description
In this chapter, you will learn about the diagnostic input module, cat. no. 1794-IB16D, and the diagnostic output module, cat. no. 1794-OB16D. Topic
See Page
General Description
13
Install Your Digital Input or Output Module
16
This chapter contains an overview of the FLEX I/O diagnostic digital modules, the 1794-IB16D input module and 1794-OB16D output module. You can use the FLEX I/O diagnostic modules to help diagnose problems with input and output field devices, I/O wiring and the user power supply. Additionally, these modules can reduce installation start-up time and help minimize time to find and fix failures. This chapter explains how to use the FLEX I/O diagnostic modules to help detect the following types of faults: • Open input or output field devices • Open input or output wiring • Shorted output field devices • Shorted input or output wiring • Reversed polarity of user supply wiring • Open user supply wiring or failed user supply (using one diagnostic input channel)
13
Publication 1794-UM061A-EN-P - July 2006
Page 16
14
1794 FLEX I/O Diagnostic Digital Modules Overview
Network Compatibility You can use the diagnostic modules with ControlNet, DeviceNet, EtherNet/IP, or remote I/O networks. Usage Limitations Network
1794-IB16D
1794-OB16D
Remote I/O
Compatible with 1794-ASB series E (or higher) and 1794-ASB2 series D (or higher) remote I/O adapters.
Compatible with 1794-ASB series D (or higher) and 1794-ASB2 series C (or higher) remote I/O adapters.
DeviceNet
No limitations or constraints.
ControlNet
Direct connection only.
Direct or rack connections.
EtherNet/IP
Direct connection only.
Direct or rack connections.
1794-IB16D Diagnostic Input Module Compatibility The 1794-IB16D diagnostic input module interfaces to sensing devices and detects whether they are on or off. The diagnostic input module converts dc signals from user devices to the appropriate logic level for use in the FLEX I/O system. Typical input devices include these types of switches. • Proximity switches • Limit switches • Photoelectric switches • Selector switches • Float switches • Pushbutton switches When designing a system using a FLEX I/O diagnostic input module, you must consider: • the voltage necessary for your application. • current leakage through the input devices. • the amount of current consumed by the input devices. • whether the application requires sinking or sourcing devices.
Publication 1794-UM061A-EN-P - July 2006
Page 17
1794 FLEX I/O Diagnostic Digital Modules Overview
15
Capabilities of the 1794-IB16D include: • 61131-2 Type 3 compatible sinking inputs. • interface with PNP sourcing sensors. • 10-31.2V dc operating range. • provides up to 50 mA to power an attached sensor. • detects for an open wire condition down to 50 μA. You need a dummy resistor to mask the channel diagnostic function for each unused sensor port. Used sensor ports must have a 50 μA minimum current draw with the input field device in both the on- and off-state.
1794-OB16D Diagnostic Output Module Compatibility You can use FLEX I/O diagnostic output modules to drive a variety of output devices. Typical output devices include the following. • Relays • Solenoids • Contactors • Indicators • Small motor starters When you design a system using FLEX I/O diagnostic output modules, you must consider: • The output must supply the necessary surge and continuous current for the output device being used. • When sizing output loads, check the documentation supplied with the output device for the surge and continuous current needed to operate the device. Capabilities of the 1794-OB16D diagnostic output module include: • sourcing style outputs for loads connected to common. • 10-31.2V dc operating range. • provides continuous current of 0.5 A maximum (8 A per module), 2.0 mA minimum per output. • capable of 2 A surge for 50 ms, repeatable every 2 s. • protection from short circuit and overload. You need a dummy resistor to mask the channel diagnostic function for each unused output channel.
Publication 1794-UM061A-EN-P - July 2006
Page 18
16
1794 FLEX I/O Diagnostic Digital Modules Overview
Install Your Digital Input or Output Module
To install a digital diagnostic module, follow these steps: ✓
Installation Step
❑ 1.
Mount the terminal base unit See installation instructions 1794-IN096.
❑ 2.
Install the module in the terminal base unit See installation instructions 1794-IN096.
❑ 3.
Connect the wiring to the terminal base unit See installation instructions 1794-IN096.
Publication 1794-UM061A-EN-P - July 2006
Page 19
1794 FLEX I/O Diagnostic Digital Modules Overview
17
1794-TB32 and 1794-TB32S Terminal Base Wiring for the 1794-IB16D 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
A 0
1
17
16
2
18
3
19
4
20
5
6
7
8
9
10
11
Inputs Channels 0-15 21
22
23
24
25
26
27
12
28
13
29
14
30
15
31
32
33
B NC
0
34
1
35
2
36
3
4
5
6
7
8
9
10
11
12
13
Sensor Power Terminals for Channels 0-15 37
38
39
40
41
42
43
44
45
46
47
48
14
NC
15
49
50
51
C NC +V1 COM1 +V1 COM1 +V1 COM1 +V1 COM1 +V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC
Sensor Common and User Power Common: Terminals C-36, C-38, C-40, C-42, C-44, C-46, C-48 and C-50. +V1 Terminals C-35, C-37, C-39, and C-41 are not used User power (+) Voltage: Terminals C-43, C-45, C-47 and C-49. COM1 and COM2 are connected together in the module.
Wiring for 1794-IB16D (use with 1794-TB32 or 1794-TB32S Terminal Base Units) Input IN 00 IN 01 IN 02 IN 03 IN 04 IN 05 IN 06 IN 07 IN 08 IN 09 IN 10 IN 11 IN 12 IN 13 IN 14 IN 15 +V2 dc power COM dc Return
Supply Input Sensor Power Common1 Terminal Terminal +V2 connected A-0 B-17 -V common to terminals 43, connected to A-1 B-18 45, 47, and 49 terminals 36, 38, A-2 B-19 40, 42, 44, 46, 48, (+V1 terminals A-3 B-20 35, 37, 39, and and 50 A-4 B-21 41 are not used). A-5 B-22 A-6 B-23 A-7 B-24 A-8 B-25 A-9 B-26 A-10 B-27 A-11 B-28 A-12 B-29 A-13 B-30 A-14 B-31 A-15 B-32 Power terminals 43, 45, 47, and 49 (power terminals are internally connected together in the module) Common terminals 36, 38, 40, 42, 44, 46, 48, and 50 (common terminals COM 1 and COM 2 are internally connected together in the module)
(1)3-wire devices only. 2-wire devices use input and sensor power terminals; 3-wire devices use input, sensor power and common terminals.
Publication 1794-UM061A-EN-P - July 2006
Page 20
18
1794 FLEX I/O Diagnostic Digital Modules Overview
1794-TB2, -TB3, and -TB3S Terminal Base Wiring for the 1794-OB16D Outputs 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
A 17
16
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
B -V Common 34
Commons 35
36
37
38
39
40
41
42
-V Common 43
44
45
46
47
48
49
50
51
C Voltage In +V
Terminals 35 through 50 not available on 1794-TB2
Voltage Out +V
Voltage -V (Supply Common) = Terminals B-16 through B-33. +V (Supply +Voltage In) = Terminals C-34 through C-51. (Use B-33 and C-51 for daisy-chaining to next terminal base unit.)
(1794-TB3 shown)
Wiring Connections for the 1794-OB16D (use with 1794-TB2, 1794-TB3 or 1794-TB3S Terminal Base Units).
Outputs Output 00 Output 01 Output 02 Output 03 Output 04 Output 05 Output 06 Output 07 Output 08 Output 09 Output 10 Output 11 Output 12 Output 13 Output 14 Output 15 +V dc
Common
Output Terminal Common Terminal A-0 B-17 A-1 B-18 A-2 B-19 A-3 B-20 A-4 B-21 A-5 B-22 A-6 B-23 A-7 B-24 A-8 B-25 A-9 B-26 A-10 B-27 A-11 B-28 A-12 B-29 A-13 B-30 A-14 B-31 A-15 B-32 C-34 and C-51 (1794-TB2) (Power Terminals are internally connected in the terminal base unit. C-34…C-51 (1794-TB3, 1794-TB3S) (Power terminals are internally connected in the terminal base unit. B-16…B-33 (Common terminals are internally connected in the terminal base unit.