Manual · Allen-Bradley
FLEX I/O Diagnostic Modules, Catalog Numbers 1794-IB16D, 1794-OB16D, User Manual
Manual132 pagesPDF 2.4 MB
User manual for the Allen-Bradley FLEX I/O 1794-IB16D diagnostic input and 1794-OB16D diagnostic output modules.
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Rockwell Automation user manual for the Allen-Bradley FLEX I/O diagnostic digital modules, the 1794-IB16D input and 1794-OB16D output modules. It explains installation, wiring of sensors and loads, diagnostic fault detection, protection functions and module limits, then shows how to configure the modules on Remote I/O, DeviceNet, ControlNet and EtherNet/IP networks. Appendices explain the indicators and give simplified schematics for all 1794 digital modules, including the 1794-OB16 24V DC 16 output module.
Its parts
- Preface
- 1794 FLEX I/O Diagnostic Digital Modules Overview
- About the FLEX I/O Diagnostic Input Module
- About the FLEX I/O Diagnostic Output Module
- Configuring Modules for Communication on a Remote I/O Network
- Configure FLEX I/O Digital Modules on a DeviceNet Network
- Configure Your Adapter and Digital Modules on a ControlNet Network
- Configure your Digital Module on an EtherNet/IP Network
From the manual
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley user manual (publication 1794-UM061A-EN-P, July 2006) for the FLEX I/O diagnostic modules 1794-IB16D (16 sinking 24V dc inputs) and 1794-OB16D (16 sourcing 24V dc outputs). The manual is about these diagnostic versions, not the standard 1794-OB16. It explains fault detection, wiring on terminal bases, setup on Remote I/O, DeviceNet, ControlNet and EtherNet/IP networks, and the indicators.
- 1794-OB16D
- 1794-OB16D: 16 sourcing 24V dc outputs with open-wire, short-circuit and reverse polarity diagnostics p. 29
- Output voltage
- 1794-OB16D: 10-31.2V dc operating range p. 17
- Output current
- 1794-OB16D: 0.5 A maximum per output (8 A per module), 2.0 mA minimum; 2 A surge for 50 ms, every 2 s p. 17
- Terminal bases
- 1794-OB16D: 1794-TB2, 1794-TB3 or 1794-TB3S; 1794-IB16D: 1794-TB32 or 1794-TB32S p. 19, 30
- Fault thresholds
- 1794-OB16D: open wire when off-state current drops below 0.1 mA; short when on-state voltage drops below 2V; reverse supply at -10V or more p. 32, 33
- Output commons
- 1794-OB16D: all 16 outputs share one common return, not isolated from one another p. 30
- 1794-IB16D
- 1794-IB16D: 16 sinking 24V dc inputs, 10-31.2V dc, up to 50 mA sensor power, open wire detection down to 50 μA p. 17, 106
- Networks
- Remote I/O, DeviceNet, ControlNet and EtherNet/IP p. 16
- Remote I/O adapters
- 1794-OB16D: 1794-ASB series D or higher, 1794-ASB2 series C or higher; 1794-IB16D: 1794-ASB series E, 1794-ASB2 series D or higher p. 16
- Data table
- 1794-OB16D: outputs written in word 2; word 1 bits 00 module error, 01 reverse polarity, 02 short, 03 open wire p. 34
- Indicators
- Channel indicator off, yellow when on, red for open or short; module fault indicator red on any fault p. 34, 105
- Supply wiring
- 1794-OB16D: supply common on terminals B-16 to B-33, +V on C-34 to C-51; B-33 and C-51 daisy-chain to the next base p. 20
- Fault states
- Outputs can go all on, all off or hold last state on network failure or Program mode p. 33
- Isolation
- Optocouplers isolate system-side logic from the user supply and output channels p. 32
What this manual walks you through
- Wiring output loads and user power on a 1794-TB2, TB3 or TB3S base p. 20, 30
- Wiring 2-wire and 3-wire sensors to the 1794-IB16D p. 19
- How the output module detects open, short and reverse-polarity faults p. 29, 31, 32
- Setting output fault and idle states p. 33
- Reading the output data and diagnostic status words p. 34
- Interpreting the channel and module fault indicators p. 105, 109, 110
- Detecting a lost user power supply with a spare input p. 33
Good to know
- Each unused output needs a dummy resistor to common, or the module signals a fault and diagnostics on the other channels become useless. p. 34
- A shorted output turns off, then turns back on by itself once the short is removed, which can restart a load. p. 32
- The output module does not check whether the user power supply is present. p. 33
- An open cannot be detected with the output on, nor a short with the output off. p. 109
- FLEX I/O grounds through the DIN rail; use zinc plated yellow-chromate steel rail. p. 8
Questions this manual answers
What is the current rating of the 1794-OB16D?
0.5 A per output continuous, 8 A per module, with a 2 A surge for 50 ms repeatable every 2 s. p. 17
What faults does the 1794-OB16D detect?
Open wiring or loads, shorted outputs, and reversed user supply polarity. p. 29
What do I do with unused 1794-OB16D outputs?
Wire a dummy resistor between each unused output and common; without it the module signals a fault. p. 34
Which terminal bases fit the 1794-OB16D?
The 1794-TB2, 1794-TB3 or 1794-TB3S terminal base units. p. 30
What does a red channel light on the 1794-OB16D mean?
That output channel has an open or a short. p. 34
Contents
Chapters and sections
Each line opens the PDF at its page.
- 1794-UM061A-EN-P FLEX I/O Diagnostic Modules User Manual1
- Important User Information2
- Preface7
- Chapter 1 - 1794 FLEX I/O Diagnostic Digital Modules Overview15
- Chapter 2 - About the FLEX I/O Diagnostic Input Module21
- Chapter 3 - About the FLEX I/O Diagnostic Output Module29
- Chapter 4 - Configuring Modules for Communication on a Remote I/O Network35
- Chapter 5 - Configure FLEX I/O Digital Modules on a DeviceNet Network49
- Chapter 6 - Configure Your Adapter and Digital Modules on a ControlNet Network59
- Chapter 7 - Configure your Digital Module on an EtherNet/IP Network83
- Appendix A - Interpret the Indicators105
- Appendix B - Simplified Schematics of FLEX I/O Digital Modules111
- Back Cover132
The whole text · 14 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.