Summary

What is in it

Rockwell Automation user manual for the Allen-Bradley FLEX I/O diagnostic digital modules, the 1794-IB16D input and 1794-OB16D output modules. It explains installation, wiring of sensors and loads, diagnostic fault detection, protection functions and module limits, then shows how to configure the modules on Remote I/O, DeviceNet, ControlNet and EtherNet/IP networks. Appendices explain the indicators and give simplified schematics for all 1794 digital modules, including the 1794-OB16 24V DC 16 output module.

Its parts

  1. Preface
  2. 1794 FLEX I/O Diagnostic Digital Modules Overview
  3. About the FLEX I/O Diagnostic Input Module
  4. About the FLEX I/O Diagnostic Output Module
  5. Configuring Modules for Communication on a Remote I/O Network
  6. Configure FLEX I/O Digital Modules on a DeviceNet Network
  7. Configure Your Adapter and Digital Modules on a ControlNet Network
  8. Configure your Digital Module on an EtherNet/IP Network

From the manual

Key facts from this manual

Each line names its page in the PDF.

Allen-Bradley user manual (publication 1794-UM061A-EN-P, July 2006) for the FLEX I/O diagnostic modules 1794-IB16D (16 sinking 24V dc inputs) and 1794-OB16D (16 sourcing 24V dc outputs). The manual is about these diagnostic versions, not the standard 1794-OB16. It explains fault detection, wiring on terminal bases, setup on Remote I/O, DeviceNet, ControlNet and EtherNet/IP networks, and the indicators.

Read for this summary: pages 1 to 2, 7 to 9, 15 to 20, 29 to 34 and 105 to 110 of 132.

1794-OB16D
1794-OB16D: 16 sourcing 24V dc outputs with open-wire, short-circuit and reverse polarity diagnostics p. 29
Output voltage
1794-OB16D: 10-31.2V dc operating range p. 17
Output current
1794-OB16D: 0.5 A maximum per output (8 A per module), 2.0 mA minimum; 2 A surge for 50 ms, every 2 s p. 17
Terminal bases
1794-OB16D: 1794-TB2, 1794-TB3 or 1794-TB3S; 1794-IB16D: 1794-TB32 or 1794-TB32S p. 19, 30
Fault thresholds
1794-OB16D: open wire when off-state current drops below 0.1 mA; short when on-state voltage drops below 2V; reverse supply at -10V or more p. 32, 33
Output commons
1794-OB16D: all 16 outputs share one common return, not isolated from one another p. 30
1794-IB16D
1794-IB16D: 16 sinking 24V dc inputs, 10-31.2V dc, up to 50 mA sensor power, open wire detection down to 50 μA p. 17, 106
Networks
Remote I/O, DeviceNet, ControlNet and EtherNet/IP p. 16
Remote I/O adapters
1794-OB16D: 1794-ASB series D or higher, 1794-ASB2 series C or higher; 1794-IB16D: 1794-ASB series E, 1794-ASB2 series D or higher p. 16
Data table
1794-OB16D: outputs written in word 2; word 1 bits 00 module error, 01 reverse polarity, 02 short, 03 open wire p. 34
Indicators
Channel indicator off, yellow when on, red for open or short; module fault indicator red on any fault p. 34, 105
Supply wiring
1794-OB16D: supply common on terminals B-16 to B-33, +V on C-34 to C-51; B-33 and C-51 daisy-chain to the next base p. 20
Fault states
Outputs can go all on, all off or hold last state on network failure or Program mode p. 33
Isolation
Optocouplers isolate system-side logic from the user supply and output channels p. 32

What this manual walks you through

  • Wiring output loads and user power on a 1794-TB2, TB3 or TB3S base p. 20, 30
  • Wiring 2-wire and 3-wire sensors to the 1794-IB16D p. 19
  • How the output module detects open, short and reverse-polarity faults p. 29, 31, 32
  • Setting output fault and idle states p. 33
  • Reading the output data and diagnostic status words p. 34
  • Interpreting the channel and module fault indicators p. 105, 109, 110
  • Detecting a lost user power supply with a spare input p. 33

Good to know

  • Each unused output needs a dummy resistor to common, or the module signals a fault and diagnostics on the other channels become useless. p. 34
  • A shorted output turns off, then turns back on by itself once the short is removed, which can restart a load. p. 32
  • The output module does not check whether the user power supply is present. p. 33
  • An open cannot be detected with the output on, nor a short with the output off. p. 109
  • FLEX I/O grounds through the DIN rail; use zinc plated yellow-chromate steel rail. p. 8

Questions this manual answers

What is the current rating of the 1794-OB16D?

0.5 A per output continuous, 8 A per module, with a 2 A surge for 50 ms repeatable every 2 s. p. 17

What faults does the 1794-OB16D detect?

Open wiring or loads, shorted outputs, and reversed user supply polarity. p. 29

What do I do with unused 1794-OB16D outputs?

Wire a dummy resistor between each unused output and common; without it the module signals a fault. p. 34

Which terminal bases fit the 1794-OB16D?

The 1794-TB2, 1794-TB3 or 1794-TB3S terminal base units. p. 30

What does a red channel light on the 1794-OB16D mean?

That output channel has an open or a short. p. 34

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. 1794-UM061A-EN-P FLEX I/O Diagnostic Modules User Manual1
    1. Important User Information2
    2. Preface7
    3. Chapter 1 - 1794 FLEX I/O Diagnostic Digital Modules Overview15
    4. Chapter 2 - About the FLEX I/O Diagnostic Input Module21
    5. Chapter 3 - About the FLEX I/O Diagnostic Output Module29
    6. Chapter 4 - Configuring Modules for Communication on a Remote I/O Network35
    7. Chapter 5 - Configure FLEX I/O Digital Modules on a DeviceNet Network49
    8. Chapter 6 - Configure Your Adapter and Digital Modules on a ControlNet Network59
    9. Chapter 7 - Configure your Digital Module on an EtherNet/IP Network83
    10. Appendix A - Interpret the Indicators105
    11. Appendix B - Simplified Schematics of FLEX I/O Digital Modules111
  2. Back Cover132

From the PDF’s own bookmarks.

The whole text · 14 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70
  8. Pages 71 to 8071-80
  9. Pages 81 to 9081-90
  10. Pages 91 to 10091-100
  11. Pages 101 to 110101-110
  12. Pages 111 to 120111-120
  13. Pages 121 to 130121-130
  14. Pages 131 to 132131-132

The file

Revision and size

Part no.1794-UM065B-EN-E
RevisionJuly 2006
PublisherRockwell Automation (Allen-Bradley)
Pages132
PDF2.4 MB
TextText from the PDF itself; page 1 is a scan, read by OCR, which may hold reading errors.
1794-UM065B-EN-E

The first pages · 3 of 132

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 132
Page 2
Page 2of 132
Page 3
Page 3of 132