FLEX I/O Diagnostic Modules, Catalog Numbers 1794-IB16D, 1794-OB16D, User Manual, pages 91 to 100

Pages 91 to 100 of 132

The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Allen-Bradley 1794-OB16

Page 91

Configure your Digital Module on an EtherNet/IP Network

89

Add a Module

1. Right-click the level (branch) to which you want to add the module and choose New Module.

2. Choose the module.

3.Configure the module. To

Do this

Use the default configuration

Specify the general information about the module (name, comm format, etc.) and click Finish.

Customize the configuration

Specify the general information about the module (name, comm format, etc.). Then use the tabs to step through subsequent screens.

The Comm Format selection you make when you add a communication module and its I/O modules is based on whether you want rack-optimized or direct connections to each distributed I/O module. In general: If the Ddstributed I/O is

Select this format for the remote adapter

Select this format for the distributed I/O module

Digital

Rack Optimization

Rack Optimization

Analog

None

An appropriate direct-connection format.

Download the Program to the Controller

Follow this procedure to download the program you just saved to the ControlLogix controller. 1. From the main menu, choose Communication>Who-Active. 2. Select the processor slot in the chassis. 3. From the Who-Active dialog, choose Set Project Path.

Publication 1794-UM061A-EN-P - July 2006

Page 92

90

Configure your Digital Module on an EtherNet/IP Network

4. From the Who Active dialog, choose Download to see the Download dialog.

5. From the Download dialog, choose Download.

6. Click OK. 7. Your system is now up and running.

Publication 1794-UM061A-EN-P - July 2006

Page 93

Configure your Digital Module on an EtherNet/IP Network

Access Distributed I/O

91

I/O information is presented as a structure of multiple fields, which depend on the specific features of the I/O module. The name of the structure is based on the location of the I/O module in the system. Each I/O tag is automatically created when you configure the I/O module through the programming software. Each tag name follows this format: Location:SlotNumber:Type.MemberName.SubMemberName.Bit where:

This address variable:

Is:

Location

Identifies network location LOCAL = local DIN rail or chassis ADAPTER_NAME = identifies remote adapter or bridge

SlotNumber

Slot number of I/O module in its chassis

Type

Type of data I = input O = output C = configuration S = status

MemberName

Specific data from the I/O module; depends on the type of data the module can store For example, Data and Fault are possible fields of data for an I/O module. Data is the common name for values the are sent to or received from I/O points.

SubMemberName

Specific data related to a MemberName.

Bit (optional)

Specific point on the I/O module; depends on the size of the I/O module (0-31 for a 32-point module)

EXAMPLE

Example 1

Example 2

Publication 1794-UM061A-EN-P - July 2006

Page 94

92

Configure your Digital Module on an EtherNet/IP Network

Example 1

Example 2

When you choose rack optimization for an I/O module, its tags are created as aliases for the tags of the adapter module. In your logic, you see the tag of the device as aliases for a tag of the adapter module. (The tag name of the adapter is in angle brackets). tag name of the I/O device conveyor:2:I.0 <conveyor:I.Data[2].0>

Publication 1794-UM061A-EN-P - July 2006 tag name of the adapter

Page 95

Configure your Digital Module on an EtherNet/IP Network

93

Data type with tag names are produced by the program.

General Information About IP Addresses

The following information outlines steps you must take if initially setting up your EtherNet/IP network.

Determining Required Network Parameters To operate on an EtherNet/IP network, you must define these parameters. EtherNet/IP Parameter:

Description:

IP address

The IP address uniquely identifies the module. The IP address is in the form xxx.xxx.xxx.xxx where each xxx is a number between 0-255. These are reserved values you cannot use: • 127.0.0.1 • 0.0.0.0 • 255.255.255.255 subnet mask

Subnet addressing is an extension of the IP address scheme that allows a site to use a single network ID for multiple physical networks. Routing outside of the site continues by dividing the IP address into a net ID and a host ID via the class. Inside a site, the subnet mask is used to redivide the IP address into a custom network ID portion and host ID portion. This field is set to 0.0.0.0 by default. If you change the subnet mask of an already-configured module, you must cycle power to the module for the change to take effect.

gateway

A gateway connects individual physical networks into a system of networks. When a node needs to communicate with a node on another network, a gateway transfers the data between the two networks. This field is set to 0.0.0.0 by default.

Publication 1794-UM061A-EN-P - July 2006

Page 96

94

Configure your Digital Module on an EtherNet/IP Network

If you use DNS addressing, or reference the module via host name in MSG instructions, define these parameters: EtherNet/IP Parameter:

Description:

host name

A host name is part of a text address that identifies the host for a module. The full text address of a module is host_name.domain_name.

domain name

A domain name is part of a text address that identifies the domain in which the module resides. The full text address of a module is host_name.domain_name. The domain name has a 48-character limit. If you specify a DNS server, you must enter a domain name. Also, if you send email from the module, some mail relay servers require a domain name be provided during the initial handshake of the SMTP session.

primary DNS server address secondary DNS server address

This identifies the DNS server(s), if used in the network. You must have a DNS server configured if you specified a domain name or a host name in the module’s configuration. The DNS server converts the domain name or host name to an IP address that can be used by the network. The 1756-ENBT requires a DNS server address. For more information on DNS addressing, see publication ENET-UM001, EtherNet/IP Modules in Logix5000 Control Systems.

Check with your Ethernet network administrator to determine if you need to specify all of the above parameters. To configure these network parameters, the recommended method is to use the Rockwell Automation BOOTP/DHCP utility. If this utility is not available, there are other methods you can use.

Assigning Network Parameters via the BOOTP/DHCP Utility

By default, the EtherNet/IP module is BOOTP enabled. The BOOTP/DHCP utility is a stand alone program that is located in the: • BOOTP-DHCP Server folder in the Rockwell Software program folder on the Start menu (the utility is automatically installed when you install RSLinx software) • Tools directory on the RSLogix 5000 installation CD. IMPORTANT

Before you start the BOOTP/DHCP utility, make sure you have the hardware (MAC) address of the module. The hardware address is on a sticker located on the side of the EtherNet/IP module. The hardware address in a format similar to: 00-0b-db-14-55-35.

This utility recognizes BOOTP-enabled devices and provides an interface to configure a static IP address for each device.

Publication 1794-UM061A-EN-P - July 2006

Page 97

Configure your Digital Module on an EtherNet/IP Network

95

To use the BOOTP/DHCP utility: 1. Start the BOOTP/DHCP software. 2. Select Tool → Network Settings.

If appropriate for your network, enter the subnet mask, gateway address, primary/secondary server addresses, and roman name. Click OK. In the Request History panel you see the hardware addresses of modules issuing BOOTP requests. 3. Double-click on the hardware (MAC) address of the module you want to configure. The hardware address is on a sticker located on the side of the EtherNet/IP module. The hardware address will be in a format similar to: 00-0b-db-14-55-35.

Publication 1794-UM061A-EN-P - July 2006

Page 98

96

Configure your Digital Module on an EtherNet/IP Network

The New Entry window appears with the module’s Ethernet Address (MAC).

4. Enter the IP address or the host name. You can also enter a description of the module. Click OK 5. To permanently assign this configuration to the module, highlight the module and click on the Disable BOOTP/DHCP button. When power is recycled, the module uses the configuration you assigned and not issue a BOOTP request. If you do not select the Disable BOOTP/DHCP button, on a power cycle, the host controller clears the current IP configuration and will again begin sending BOOTP requests.

Publication 1794-UM061A-EN-P - July 2006

Page 99

Configure your Digital Module on an EtherNet/IP Network

Using Other Methods to Assign Network Parameters

Other methods to assign network parameters include:

If you are working in these conditions

Use this method for assigning network parameters

See publication

• a BOOTP server is not available

RSLinx software

ENET-UM001

97

• the EtherNet/IP module is connected to another NetLinx network • the RSLogix 5000 project is online with the controller that communicates to or through the EtherNet/IP module

RSLogix 5000 software

• DHCP is enabled (not BOOTP) for the EtherNet/IP module

DHCP software

Other considerations that might affect your choice of method include: • whether the network is isolated from or integrated into the plant/enterprise network • size of the network For large networks, even isolated networks, it might be more convenient and safer to use a BOOTP/DHCP server rather than RSLogix 5000 or RSLinx software. It might also offer fewer opportunities for assigning duplicate IP addresses. • company policies and procedures dealing with plant floor network installation and maintenance • level of involvement by IT personnel in plant floor network installation and maintenance • type of training offered to control engineers and maintenance personnel If you use the Rockwell Automation BOOTP or DHCP server in an uplinked subnet where an enterprise DHCP server exists, a module may get an address from the enterprise server before the Rockwell Automation utility even sees the module. You might have to disconnect from the uplink to set the address and have the module remember its static address before reconnecting to the uplink. This is not a problem if you have node names configured in the module and leave DHCP enabled.

Publication 1794-UM061A-EN-P - July 2006

Page 100

98

Configure your Digital Module on an EtherNet/IP Network

Using RSLinx software to set the IP address To use RSLinx to configure the EtherNet/IP module: 1. Make sure the module is installed and powered up. 2. Start RSLinx. The RSWho window opens. Navigate in RSWho to the Ethernet network. 3. Right-click on the EtherNet/IP module (not the controller, if there is one) and select Module Configuration.

4. Select the Port Configuration tab, choose Status Network Configuration type, and enter the IP address and the other network parameters, if needed. 5. Also, select the Static radio button to permanently assign this configuration to the port. If you select Dynamic, on a power cycle, the controller clears the current IP configuration and will again begin sending BOOTP requests.

Publication 1794-UM061A-EN-P - July 2006