The text of a manual · part 11 of 14
FLEX I/O Diagnostic Modules, Catalog Numbers 1794-IB16D, 1794-OB16D, User Manual, pages 101 to 110
Pages 101 to 110 of 132
The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Allen-Bradley 1794-OB16
Page 101
Configure your Digital Module on an EtherNet/IP Network
99
Using RSLogix 5000 software to set the IP address To use RSLogix 5000 software to configure the EtherNet/IP module: 1. Make sure the module in installed and powered up. 2. Connect to the controller via a serial, or other network, connection. 3. Start RSLogix 5000 software. In the Controller Organizer, select properties for the EtherNet/IP module.
4. Select the Port Configuration tab and specify the IP address and the other network parameters, if needed. Click Apply and then click OK.
Publication 1794-UM061A-EN-P - July 2006
Page 102
100
Configure your Digital Module on an EtherNet/IP Network
This sets the IP address in the hardware. This IP address should be the same IP address you assigned under the General tab. On this screen, you can also specify port speed (10 Mbps or 100 Mbps) and duplex mode (autonegotiate, half duplex, or full duplex). All modules on the same subnet must be configured for the same port speed and duplex mode.
Using DHCP software to set the IP address DHCP (Dynamic Host Configuration Protocol) software automatically assigns IP addresses to client stations logging onto a TCP/IP network. DHCP is based on BOOTP and maintains some backward compatibility. The main difference is that BOOTP allows for manual configuration (static), while DHCP allows for both static and dynamic allocation of network addresses and configurations to newly attached modules. Be cautious when using DHCP software to configure your module. A BOOTP client, such as the EtherNet/IP modules, can boot from a DHCP server only if the DHCP server is specifically written to also handle BOOTP queries. This is specific to the DHCP software package you use. Check with your system administrator to see if your DHCP package supports BOOTP commands and manual IP allocation. ATTENTION
The EtherNet/IP module must be assigned a fixed network address. The IP address of this module must not be dynamically provided. Failure to observe this precaution may result in unintended machine motion or loss of process control.
Duplicate IP Address Detection
These EtherNet/IP modules (and their future revisions) support duplicate IP address detection: • 1756-ENBT, firmware revision 3.2 and greater • 1788-ENBT, firmware revision 2.1 and greater • 1756-EWEB, firmware revision 2.2 and greater (For more information about this module, see the EtherNet/IP Web Server Module User Manual, publication ENET-UM527.) When you change the IP address or connect one of these modules to an EtherNet/IP network, the module checks to make sure that the IP address assigned to this module is not the same as that for any other device already on the network. If the module determines that there is a conflict (some other
Publication 1794-UM061A-EN-P - July 2006
Page 103
Configure your Digital Module on an EtherNet/IP Network
101 device on the network already has the IP address), the EtherNet/IP port of the module goes into conflict mode, where the module’s: • OK indicator blinks red. • network (NET) indicator is solid red. • front display indicates the conflict (1756-ENBT only). The display scrolls: ”OK <IP_address_of_this_module> Duplicate IP <Mac_address_of_duplicate_node_detected>” For example: OK 10.88.60.196 Duplicate IP - 00:00:BC:02:34:B4 To correct this conflict, use the instructions in this chapter to change the IP address of the module. Then cycle power to the module or reset the module (such as disconnecting the EtherNet/IP cable and reconnecting the cable). There is also the possibility that two modules can detect a conflict simultaneously. If this occurs, remove the module that has the incorrect IP address or correct its conflict. To get the second module out of conflict mode, cycle power to the module or disconnect its EtherNet/IP cable and reconnect the cable.
Duplicate detection scenarios • The behavior of devices that are in conflict over an IP address varies depending on whether connections have been established to either of the modules and whether both modules support duplicate IP address detection: • If both modules support duplicate IP address detection, the module that powers up first and uses the IP address, keeps the IP address. The other module will detect a conflict, give up the IP address, and enter conflict mode. • If both modules support duplicate IP address detection and both modules power up at roughly the same time, both modules give up the IP address and enter conflict mode. • If one module supports duplicate IP address detection and a second module does not, the second module generally keeps it IP address, regardless of which module obtains the IP address first. The module that supports duplicate IP address detection will detect the conflict and give up the IP address.
Publication 1794-UM061A-EN-P - July 2006
Page 104
102
Configure your Digital Module on an EtherNet/IP Network
IP Address Swapping
These EtherNet/IP modules (and their future revisions) support IP address swapping in ControlLogix redundancy systems: • 1756-ENBT, firmware revision 3.1 and greater • 1756-EWEB, firmware revision 2.2 and greater During a switchover in ControlLogix redundancy systems, these modules swap their IP addresses with their partner modules in the other redundant chassis. For more information about IP address swapping, see the ControlLogix Redundancy User Manual, publication 1756-UM523.
Publication 1794-UM061A-EN-P - July 2006
Page 105
Appendix
A
Interpret the Indicators
Introduction
About the Indicators
This chapter provides the following: For Information About
See Page
About the Indicators
103
1794-IB16D Diagnostic Functional Details
104
1794-OB16D Diagnostic Functional Details
107
The diagnostic modules have indicators that let you check the module health and operational status. The following status can be checked with the indicators. • Channel I/O Status - This indicator displays the ON/OFF state of the input channel, as well as channel wiring fault conditions: – Off indicates the channel is off with no faults. – Yellow indicates the channel is on with no faults. – Red indicates either a channel open or short condition. • Module Fault Status- This indictor turns red for any individual input/output channel open, short or module reverse power conditions. With no fault, the module fault status indicator turns off. Allen-Bradley
1794-IB16D
24 VDC SINK INPUT WITH DIAGNOSTIC
2
FLT 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
1
15
3
2
Allen-Bradley
1794-OB16D
24 VDC SOURCE OUTPUT WITH DIAGNOSTIC
2
FLT 0
1
2
1
3
4
5
6
7
8
9
10
11
12
13
14
15
2
3
Where: 1 = Channel bicolor Status indicator 2 = Insertable label for writing individual input/output designations 3 = Module bicolor Fault Indicator
103
Publication 1794-UM061A-EN-P - July 2006
Page 106
104
Interpret the Indicators
1794-IB16D Diagnostic Functional Details
The 1794-IB16D input module provides 16 points of 24V dc sinking input with open wire and short circuit diagnostic features. Each input signal has an a associated sensor power connection. The module monitors current and voltage at each input channel sensor power terminal. Two module indicators and four diagnostic bits report fault conditions: • the module Fault indicator and the individual faulted channel indicator also turn red under open and short conditions. • the module Fault indicator turns red for reverse user power conditions. • the open bit is set for open sensor and wiring conditions. • the short bit is set for shorted sensor and wiring conditions. • the reverse power bit is set for reverse polarity user power conditions. • the module fault bit is set for any open, short or reverse power conditions detected.
Diagnostic Capabilities The module’s diagnostic capability depends on the connected sensor type.
For 2-wire sensors and contact input devices (for example, switches): • an open fault will be detected when an open occurs on either the sensor-power wire, the input signal wire, or the input sensor field device. • a shorted circuit from a sensor-power wire to common fault (-V) is detected as a short fault (no voltage at the sensor-power port). • a shorted circuit from the sensor-power wire to the input-signal wire cannot be detected. It appears as an on/active input device. • a shorted circuit from the input-signal wire to common (-V), with the input sensor field device in the off-state (field device contacts open), cannot be detected. It appears as an off/inactive input sensor device. • a shorted circuit from the input-signal wire to common (-V), with the input sensor field device in the on-state (field device contacts closed), is detected as a short fault if the sensor field device can pass the sensor power short circuit current. • a shorted 2-wire input sensor field device (contact field device) cannot be detected. It appears as an on/active input field device. • a shorted circuit from a sensor-power wire, an input sensor wire, or the input-sensor field device to the DIN rail or chassis ground cannot be detected. A dummy resistor must be placed across the contacts of contact input devices (for example, switches). Use 20 KΩ resistors. Fault
Device State Field Device
Input Status
Publication 1794-UM061A-EN-P - July 2006
Fault Indicators Module Fault
Channel Fault
Error Bit Status
Conditions
Page 107
Interpret the Indicators
Open
OFF or ON
OFF
Red
Red
Short
OFF OFF OFF ON OFF or ON
OFF ON OFF OFF OFF
Red OFF OFF Red Red
Red Yellow OFF Red OFF
Reverse User Power 1 If sensor can pass Sensor Power short circuit current
Open wire & Module Short & Module None None Short & Module Reverse & Module
105
No current in Sensor Power terminalMissing sensor, cut Sensor Power or Input Signal wire Shorted Sensor Power/ Common Shorted Sensor Power/ Input Signal Shorted Input Signal/ Common Shorted Input Signal/ Common1 User power supply wiring is reversed
For 3-wire sensors: • an open fault will be detected when an open occurs on either the sensor-power wire, the sensor (-V) wire, or the high-current portion of the input sensor field device. • an open on the input-signal wire or low-current portion of the input sensor field device will not be detected, and will be seen as an off/inactive input sensor field device. • a shorted circuit from the sensor-power wire to sensor common (-V) is detected as short fault (no voltage at the sensor-power port). • a shorted circuit from the sensor-power wire to the input-signal wire cannot be detected. It will appear as an on/active input device. • a shorted circuit from the input-signal wire to sensor common (-V), with the input sensor field device in the off-state, cannot be detected. It will appear as an off/inactive input sensor device. • a shorted circuit from the input-signal wire to sensor common (-V), with the input sensor field device in the on-state, is detected as a short fault if the sensor field device can pass the sensor power short circuit current. • a shorted 3-wire input sensor device may or may not be detected, depending on which portion of the input sensor device is shorted. • a shorted circuit to the DIN rail or chassis ground cannot be detected. Fault
Open
Short
Reverse User Power
Device/Input State Field Input Device Status OFF OFF
Indicators Module Fault Red
Channel Fault Red
Error Bit Status
Conditions
OFF Red Yellow OFF Red
Open wire & Module None Short & Module None None Short & Module
No current in Sensor Power terminalMissing sensor, cut Sensor Power or Common wire Cut Input Signal wire Shorted Sensor Power/ Common Shorted Sensor Power/ Input Signal Shorted Input Signal/ Common
OFF or ON OFF OFF OFF ON
OFF OFF ON OFF OFF
OFF Red OFF OFF Red
OFF or ON
OFF
Red
OFF
Reverse & Module
Shorted Input Signal/ Common1 User power supply wiring is reversed
1 If sensor can pass Sensor Power short circuit current
Diagnostic Functions for the 1794-IB16D Each unused sensor port requires a dummy resistor to mask the channel diagnostic function. Publication 1794-UM061A-EN-P - July 2006
Page 108
106
Interpret the Indicators
Diagnostic Functions for the 1794-IB16D Ext. Power
Wiring
OFF
Open
Input Status
Channel LED Status
Open Wire Error Bit
Short Error Bit
Rev. Error Bit
Module Error Bit/LED
Off Off 0 0 0 0/OFF On Off 0 0 0 0/OFF Short Off Off 0 0 0 0/OFF On Off 0 0 0 0/OFF Normal Off Off 0 0 0 0/OFF On Off 0 0 0 0/OFF ON Open Off RED 1 0 0 1/RED RED/YEL 1 0 0 1/RED On Short Off RED 0 1 0 1/RED RED/YEL 0 1 0 1/RED On Normal Off Off 0 0 0 0/OFF On YEL 0 0 0 0/OFF 1 1/RED REV Open Off Off 0 0 1 1/RED On Off 0 0 Short Off Off 0 0 1 1/RED 1 1/RED On Off 0 0 1 1/RED Normal Off Off 0 0 On Off 0 0 1 1/RED The module monitors each sensor-power port for current and voltage. It turns on the channel red LED and sets (1) the error bit when 1) the module detects a short circuit (no voltage at the sensor-port), and 2) the module detects an open wire ( no current at the sensor-port).
Publication 1794-UM061A-EN-P - July 2006
Page 109
Interpret the Indicators
1794-OB16D Diagnostic Functional Details
107
Two module indicators and four diagnostic bits report fault conditions: • the module fault indicator illuminates red and the individual faulted channel indicator also illuminates red under output ON state open and output OFF state short conditions. • the module fault indicator illuminates red for reverse user power conditions. • the open bit is set for open load and wiring conditions in the output OFF state. • the short bit is set for shorted load and wiring conditions in the output ON state. • the reverse power bit is set for reverse polarity user power conditions. • the module fault bit is set for any open, short or reverse power conditions detected. The module’s diagnostic capability depends on whether the output is energized (ON) or de-energized (OFF).
Fault Open
Short Reverse User Power
Device/Output Status Field Device Status
Output Status
Fault Indicators Module Fault
OFF
OFF
Red
Channel Fault Red
OFF OFF OFF OFF
ON ON OFF OFF or ON
OFF Red OFF Red
Yellow Red OFF OFF
Error Bit Status
Conditions
Open wire & Module
No current in output terminalmissing dummy resistor or field device, cut output channel or Common wire Can’t detect an open in the ON-state Short - output to Common Can’t detect a short in the OFF-state User power supply wiring is reversed
None Short & Module None Reverse & Module
Publication 1794-UM061A-EN-P - July 2006
Page 110
108
Interpret the Indicators
Diagnostic Functions for the 1794-OB16D
ATTENTION
Each unused output port requires a dummy resistor (20 KΩ +10%, 1/8 W) to mask the channel diagnostic function.
Diagnostic Functions for the 1794-OB16D Ext. Power
Wiring
OFF
Open
Output Status
Channel LED Status
Open Wire Error Bit
Short Error Bit
Rev. Error Bit
Module Error Bit/LED
Off Off 0 0 0 0/OFF On Off 0 0 0 0/OFF Short Off Off 0 0 0 0/OFF On Off 0 0 0 0/OFF Normal Off Off 0 0 0 0/OFF On Off 0 0 0 0/OFF ON Open Off RED 1 0 0 1/RED YEL 0 0 0 0/OFF On Short Off Off 0 0 0 0/OFF On RED 0 1 0 1/RED Normal Off Off 0 0 0 0/OFF On YEL 0 0 0 0/OFF 1 1/RED REV Open Off Off 0 0 1 1/RED On Off 0 0 Short Off Off 0 0 1 1/RED 1 1/RED On Off 0 0 1 1/RED Normal Off Off 0 0 On Off 0 0 1 1/RED The module monitors each output channel. It turns on the channel red indicator and sets (1) the error bit when 1) the module detects a short circuit (the output signal is active at a channel and the corresponding output voltage is low), and 2) the module detects an open wire (the output signal is inactive at a channel and the corresponding output voltage is high).
Publication 1794-UM061A-EN-P - July 2006