Page 81
Configure Your Adapter and Digital Modules on a ControlNet Network
79
8. Click OK to confirm disabling the connection. The connection is now inhibited.
9. Uncheck the Inhibit Module checkbox to disable the inhibit module function.
10. Click Apply to download the configuration data.
11. Click Yes.
Publication 1794-UM061A-EN-P - July 2006
Page 82
80
Configure Your Adapter and Digital Modules on a ControlNet Network
12. The connection status is now Running, and the module is using the updated configuration data.
Publication 1794-UM061A-EN-P - July 2006
Page 83
Chapter
7
Configure your Digital Module on an EtherNet/IP Network
How to Use This Chapter
This chapter describes how a controller controls distributed I/O over an EtherNet/IP network. The controller requires a communication module to connect to the network. Distributed I/O modules require an adapter to connect to the network. Topic
See Page
How to Use This Chapter
81
Set Up the Hardware
82
Select a Requested Packet Interval (RPI)
82
Select a Communication Format
83
Add Distributed I/O
88
Download the Program to the Controller
89
Access Distributed I/O
91
Determining Required Network Parameters
93
Assigning Network Parameters via the BOOTP/DHCP Utility
94
Using Other Methods to Assign Network Parameters
97
Duplicate IP Address Detection
100
IP Address Swapping
102
In this example, we show you how to control FLEX I/O over EtherNet using RSNetWorx for EtherNet and RSLogix 5000 software. To control distributed I/O over EtherNet, you must: • Add local and remote EtherNet communication modules to your RSLogix 5000 project. • Add distributed I/O to your RSLogix 5000 project. • Schedule the EtherNet network via RSNetWorxRSNetWorx for EtherNet. • Use the I/O information in RSLogix 5000 You can also validate connections to distributed I/O when controlling it over EtherNet. This task is particularly useful when one or more of the connections
81
Publication 1794-UM061A-EN-P - July 2006
Page 84
82
Configure your Digital Module on an EtherNet/IP Network are not working but is not required, especially when all connections appear to work normally. When you first install a Rockwell Automation EtherNet/IP module (right out of the box), the module is BOOTP/DHCP enabled.
Set Up the Hardware
In this example, the Logix5000 controller has an EtherNet/IP communication module to connect to the EtherNet/IP network. The distributed (remote) I/O has an EtherNet/IP adapter to connect it to the EtherNet/IP network. Data Distributed I/O EtherNet/IP Adapter with I/O Modules
Local Chassis Logix5000 Controller with EtherNet/IP Communication Module Switch
Programming Terminal
The Logix5000 controller can communicate with each I/O module directly (direct connection). Or you can configure a rack-optimized connection to the EtherNet/IP adapter to send data to any digital I/O modules. Make sure: • the IP addresses are set for each EtherNet/IP module • all wiring and cabling is properly connected • the communication driver (such as, AB-ETHIP-1) is configured for the programming workstation For more information on the Ethernet Adapter and Flex I/O in an Ethernet network, refer to publication ENET-UM001.
Select a Requested Packet Interval (RPI)
When you configure an I/O module, you define the requested packet interval (RPI) rate for the module. The RPI specifies the period at which data updates over a connection. For example, an input module sends data to a controller at the RPI that you assign to the module. Configure the RPI in milliseconds.
Publication 1794-UM061A-EN-P - July 2006
Page 85
Configure your Digital Module on an EtherNet/IP Network
83
RPIs are only used for modules that produce data. For example a local EtherNet/IP communication module does not require an RPI because it is not a data-producing member of the system; it is used only as a bridge. In Logix5000 controllers, I/O values update at a period that you configure via the I/O configuration folder of the project. The values update asynchronous to the execution of logic. At the specified interval, the controller updates a value independently from the execution of logic. Set the RPI only as fast as needed by the application. The RPI also determines the number of packets per second that the module will produce on a connection. Each module has a limit of how many packets it can produce per second. If you exceed this limit, the module cannot open any more connections. For information on RPI and how it affects the actual packet interval (API), see the EtherNet/IP Performance Application Solution, ENET-AP001.
Select a Communication Format
When you configure an I/O module, you select a communication format for the module. The communication format you choose determines the data structure for the tags that are associated with the module. Many I/O modules support different formats. Each format uses a different data structure. The communication format that you choose also determines: • Direct or rack-optimized connection • Ownership The available communication formats depend on the type of I/O module. In general:
If you have this type of I/O module
And want
Select a communication format that specifies
Digital Module rack-optimized connection
Rack Optimization Scheduled Data... Input Data Output Data
Digital Module
Analog Module a direct connection
Any connection that is not Rack Optimization to use specialty features of the module, such as diagnostics, timestamps, or electronic fuses
Full Diagnostics... CST Timestamped...
a direct connection
Float Data... Integer Data CST Timestamped...
(only direct connection is supported for analog modules)
See online help in RSLogix 5000 programming software for specific communication formats per I/O module.
Publication 1794-UM061A-EN-P - July 2006
Page 86
84
Configure your Digital Module on an EtherNet/IP Network
Choose Direct or Rack-optimized Connection The Logix5000 controller uses connections to transmit I/O data. These connections can be direct connections or rack-optimized connections. Term
Definition
Direct Connection
A direct connection is a real-time, data transfer link between the controller and an I/O module. The controller maintains and monitors the connection with the I/O module. Any break in the connection, such as a module fault or the removal of a module while under power, sets fault bits in the data area associated with the module.
A direct connection is any connection that does not use the Rack Optimization Comm Format. Rack-optimized Connection
For digital I/O modules, you can select rack-optimized communication. A rack-optimized connection consolidates connection usage between the controller and all the digital I/O modules in the chassis (or DIN rail). Rather than having individual, direct connections for each I/O module, there is one connection for the entire chassis (or DIN rail).
Rack-optimized Connection
Publication 1794-UM061A-EN-P - July 2006
Page 87
Configure your Digital Module on an EtherNet/IP Network
85
Direct Connections For I/O Modules In this example, assume that each distributed I/O module is configured for a direct connection to the controller.
Controller With EtherNet/IP Communication Module
Switch
EtherNet/IP Network
EtherNet/IP Adapters With I/O Modules Digital I/O Modules
Analog I/O Modules
Digital I/O Modules
The following table calculates the connections in this example. System Connections
Amount
Controller to local EtherNet/IP communication module
0
Controller to EtherNet/IP adapter Direct connection for digital I/O module Direct connection for analog I/O module
4 2
Total connections used 6
If you have many modules, direct connections to each module may not be feasible because you could use up the number of connections and packets per second supported by the module. Refer to Rack-optimized Connections For I/O Modules on page 86 to conserve connection use and network traffic.
Publication 1794-UM061A-EN-P - July 2006
Page 88
86
Configure your Digital Module on an EtherNet/IP Network
Rack-optimized Connections For I/O Modules In this example, assume that each digital I/O module is configured for a rack-optimized connection to the controller. Analog modules must be configured for direct connections.
Controller With EtherNet/IP Communication Module
Switch
EtherNet/IP Network
EtherNet/IP Adapters With I/O Modules Digital I/O modules
Analog I/O Modules
Digital I/O Modules
The following table calculates the connections in this example. System Connections
Amount
Controller to local EtherNet/IP communication module
0
Controller to EtherNet/IP adapter with digital modules (rack-optimized connection to each adapter)
2
Controller to EtherNet/IP adapter with analog modules (direct connection for each analog I/O module)
2
Total Connections used 4
The rack-optimized connection conserves connections, but can limit the status and diagnostic information that is available from the I/O modules. To optimize the number of available connections, use a rack-optimized connection between any digital I/O that allow it and the remote adapter that connects the distributed I/O to the controller via the communication module.
Publication 1794-UM061A-EN-P - July 2006
Page 89
Configure your Digital Module on an EtherNet/IP Network
87
Ownership In a Logix5000 system, modules multicast data. This means that multiple modules can receive the same data at the same time from a single module. When you choose a communication format, you have to choose whether to establish an owner or listen-only relationship with the module Owner controller
The controller that creates the primary configuration and communication connection to a module. The owner controller writes configuration data and can establish a connection to the module.
An owner connection is any connection that does not include Listen-Only in its Comm Format. Listen-only connection An I/O connection where another controller owns/provides the configuration data for the I/O module. A controller using a listen-only connection only monitors the module. It does not write configuration data and can only maintain a connection to the I/O module when the owner controller is actively controlling the I/O module.
Listen-only Connection
If the module is also in the I/O configuration of another controller, then select the Listen Only version of the Comm Format (for example, Listen Only Input Data).
Select a Remote Adapter The remote adapter you use depends on the distributed I/O you use. When using FLEX I/O modules, you use the FLEX I/O adapter, cat. no. 1794-AENT, which requires the BOOTP utility.
Publication 1794-UM061A-EN-P - July 2006
Page 90
88
Configure your Digital Module on an EtherNet/IP Network
Add Distributed I/O
To communicate with the I/O modules in your system, you add bridge, adapter, and I/O modules to the I/O Configuration folder of the controller. Within the I/O Configuration folder, you organize the modules into a hierarchy (tree/branch, parent/child).
For a typical distributed I/O network you build the I/O configuration in this order. Controller
Local Communication Module
Remote Adapter
I/O Module
Device
…you build the I/O configuration in this order.
1. Add the local communication module (bridge).
2. Add the remote adapter for the distributed I/O chassis or DIN rail. 3. Add the I/O module.
Publication 1794-UM061A-EN-P - July 2006