Page 71

Configure Your Adapter and Digital Modules on a ControlNet Network

69

Notice that the 1756-CNB Bridge is now on line, but the rest of the I/O configuration (adapter and I/O modules) connections are not scheduled (notice the yellow triangles).

Configure the 1794-ACN15 Adapter

You have now built the I/O tree in RSLogix 5000, and the RSLogix 5000 software used the chassis size from the 1794-ACN15 General Tab. Now you need to download this new chassis size value into the 1794-ACN15 adapter hardware. This procedure will synchronize the chassis size value from the RSLogix 5000 software into the 1794-ACN15 adapter. 1. Highlight the 1794-ACN15 adapter, and right-click to choose Properties.

Verify the node address and the chassis size.

Publication 1794-UM061A-EN-P - July 2006

Page 72

70

Configure Your Adapter and Digital Modules on a ControlNet Network

2. Click the Connection tab.

Notice that the connection request error is still present because we haven’t scheduled any of the I/O module connections yet. You’ll do that through RSNetWorx for ControlNet.

Schedule I/O Module Connections

Use these procedures to schedule I/O module connections. 1. Start RSNetWorx for ControlNet. 2. From the File menu, choose New.

3. Click OK. 4. Choose Network>Online.

Publication 1794-UM061A-EN-P - July 2006

Page 73

Configure Your Adapter and Digital Modules on a ControlNet Network

71

5. Browse to ControlNet Selection dialog.

6. Click OK. When you are online, you’ll see the following dialog.

7. Choose Edits Enabled in the top left of the dialog.

File and Save.

Publication 1794-UM061A-EN-P - July 2006

Page 74

72

Configure Your Adapter and Digital Modules on a ControlNet Network

You see the Online/Offline mismatch window.

8. Click OK. 9. Give the RSNetworx file a unique name, if desired.

10. If the file already exists, you are prompted before overwriting it.

11. Click OK. 12. The network is verified, and configured,

Publication 1794-UM061A-EN-P - July 2006

Page 75

Configure Your Adapter and Digital Modules on a ControlNet Network

73

13. The network and connections are now scheduled.

14. From the main menu, choose Network>Properties. The _default dialog appears.

Specify the following information on network parameters: 15. Specify a value for Network Update Time - the repetitive time interval in which data can be sent on the link. 16. Specify a value for Max Scheduled Address - the highest number node that has scheduled connections to it. 17. Specify a value for Max Unscheduled Address - the node with the highest MAC ID that can use unscheduled time on the link. These values are set to 99 by default. Change these values to what is installed in your system. This saves you time because the controller will not have to search for all of the node addresses.

Publication 1794-UM061A-EN-P - July 2006

Page 76

74

Configure Your Adapter and Digital Modules on a ControlNet Network

18. Specify a value for Media Redundancy on channel A, B or A and B. 19. Click OK to see the Save As dialog.

20. Click Save to see the Save As dialog. 21. From the Save As dialog, enter a name and location for the file, and click Save. You see the Save Configuration dialog.

22. Click OK. 23. Minimize the RSNetworx for Controlnet window, and open your RSLogix 5000 window. 24. Notice the I/O OK is solid green in your RSLogix 5000 project.

Publication 1794-UM061A-EN-P - July 2006

Page 77

Configure Your Adapter and Digital Modules on a ControlNet Network

75

25. Notice that all of the yellow warning triangles are gone in the I/O Configuration once connections are scheduled..

26. Notice that the Status in the 1794-ACN15 Module Properties dialog is Running with no faults.

clear of faults

Access Module Data via the 1794-ACN15 Adapter

Use the following information to use the 1794 FLEX I/O ControlNet adapter module data in the ladder logic program. • ACN15 = the name you gave to your ControlNet adapter • # = slot number of FLEX I/O module (0 to 7) • C = configuration, I = input, O = output When there is no slot number, that is the rack optimized data. Here are some typical sample comfiguration data examples.

Publication 1794-UM061A-EN-P - July 2006

Page 78

76

Configure Your Adapter and Digital Modules on a ControlNet Network

ACN15:3:C (1794-IB16D module) configuration data

ACN15:2:I (1794-IB16D module) input data

ACN15:4:O (1794-OB16D module) configuration data

ACN15:4:I (1794-OB16D module) input data

ACN15:4:O (1794-OB16D module) output data

TIP

It is also possible to send configurations via CIP messages.

Use the controller tags in your ladder program to read input data or write output data.

Publication 1794-UM061A-EN-P - July 2006

Page 79

Configure Your Adapter and Digital Modules on a ControlNet Network

77

Slot Status Bits The Slot Status bits display the connection status for each of the FLEX I/O modules that use a rack optimized connection. • Adapter:I:slot status bits:3 and :4 correspond to the rack optimized connection in the 1794-ACN15 slots 3 and 4. • Each of the other bits correspond to a FLEX I/O module that may be installed in the I/O backplane.

In this example, the 1794-ACN15 adapter is using 3 direct connections; slot 0 is a 1794-IE12 module, slot 1 is a 1794-OE12 module, and slot 2 is a 1794-IB8XOB4 module. Slot 3 is a 1794-IB16D, and slot 4 is a 1794-OB16D module, both connected using rack optimized connections. All modules are installed and operating correctly with (0 = no error). A 1 would indicate “no connection error,” (typically, module removed or missing).

Change Configuration Data

One way to change the configuration data for a 1794 FLEX I/O module: 1. Enter the new configuration data (#:C) into the controller tags. 2. Select Module or Adapter in the I/O configuration tree. 3. Right-click Properties. IMPORTANT

When your first add an I/O module to the I/O configuration, the default parameters are assigned. To change these default values, you must modify the controller reference tags associated with the I/O module. To download the new configuration, you must re-initiate the connection to the I/O module. This download is best achieved by inhibiting and uninhibiting the module.

Publication 1794-UM061A-EN-P - July 2006

Page 80

78

Configure Your Adapter and Digital Modules on a ControlNet Network

4. Select Properties.

5. Click on the Connection tab. 6. Check the Inhibit Module checkbox.

When you inhibit an adapter, all modules are inhibited. When you inhibit a module, only the module is inhibited, not the whole rack. 7. Click Apply.

Publication 1794-UM061A-EN-P - July 2006