Page 61

Configure Your Adapter and Digital Modules on a ControlNet Network

Select a Communication Format

59

When you configure a remote ControlNet communications module or an I/O module, you select a communication format. The communication format you choose determines the data structure for the tags that are associated with the module. Many I/O modules support different formats. Each format uses a different data structure. The communication format that you choose also determines: • Direct or rack-optimized connection • Ownership of outputs For a remote ControlNet communications module, you must select one of the formats listed below. Use this communication format In these scenarios: with a remote ControlNet communication module: None

• All of the remote I/O communicating with a controller via the remote ControlNet communication module use a Direct Connection communication format. • The connection is used for scheduled peer interlocking. • When I/O will be predominately direct connections. • When multiple controllers control the outputs in the chassis

Rack optimized

• Some or all of the remote I/O communicating with a controller via the remote ControlNet communication module use a Rack Optimized communication format. • To minimize ControlNet bandwidth when using large volume of digital I/O. • If only one controller will control the I/O.

Rack optimized - Listen only

• Some or all of the remote I/O communicating with a controller via the remote ControlNet communication module use a Rack Optimized communication format. • The connection is going to read inputs but is not going to be controlling outputs.

Publication 1794-UM061A-EN-P - July 2006

Page 62

60

Configure Your Adapter and Digital Modules on a ControlNet Network

For I/O modules, the available communication formats depend on the module type. In general: If you have this type of I/O module:

And want:

Select a communication format that specifies:

digital module a rack-optimized connection

Rack Optimization a direct connection or to use specialty features of the module, such as diagnostics, timestamps, or electronic fuses

The data your controller needs from the I/O module. For example, if your application uses a 1756-IA16I module in a remote chassis that must provide timestamped input data, you should select the CST Timestamped Input Data communication format.

or analog module to only listen to data from the module.

A Listen Only communication format that matches the data the I/O module is broadcasting to other controllers.

a direct connection or to use specialty features of the module, such as diagnostics, timestamps, or electronic fuses

The data your controller needs from the I/O module. For example, if your application uses a 1756-OF6CI module in a remote chassis that must provide floating point output data, you should select the Float Data communication format.

or to only listen to data from the module.

A Listen Only communication format that matches the data the I/O module is broadcasting to other controllers.

See online help in RSLogix 5000 programming software for specific communication formats per I/O module.

Publication 1794-UM061A-EN-P - July 2006

Page 63

Configure Your Adapter and Digital Modules on a ControlNet Network

61

Direct or rack-optimized connection Logix5000 controllers use connections to transmit I/O data. These connections can be direct connections or rack-optimized connections. direct connection A direct connection is a real-time, data transfer link between the controller and an I/O module - analog or digital. In some cases (for example, with some modules) this connection enables your controller to collect more data from an I/O module. For example, with a direct connection, the controller can collect diagnostic status data from a 1756-IA8D module that would not be collected in a rack-optimized connection. The controller maintains and monitors the connection with the I/O module. Any break in the connection, such as a module fault or the removal of a module while under power, sets fault bits in the data area associated with the module.

rack-optimized connection

Digital I/O Modules only - A rack-optimized connection consolidates connection usage between the controller and all the digital I/O modules in the chassis (or DIN rail). Rather than having individual, direct connections for each I/O module, there is one connection for the entire chasis (or DIN rail). Any time a remote chassis houses I/O modules that use rack-optimized connections, the remote ControlNet communication module connecting these modules to their owner-controller must also use a rack-optimized connection. However, you can mix direct and rack-optimized connections to the same remote chassis. For example, if your remote chassis houses 6 digital I/O modules and your application requires that you use direct connections for the 3 that require them and rack-optimized connection for the others, you can select direct connections for the 3 that require them and rack-optimized connections for the other 3. In this case, even though you must use a rack-optimized connection for the remote ControlNet communication module the owner-controller still makes direct connections with the 3 I/O modules that are configured as such. You can only make up to 5 rack-optimized connections to a single remote ControlNet communication module.

Publication 1794-UM061A-EN-P - July 2006

Page 64

62

Configure Your Adapter and Digital Modules on a ControlNet Network

Direct connections for I/O modules In this example, assume that each distributed I/O module is configured for a direct connection to the controller.

controller with ControlNet communication module or built-in communication port ControlNet network

I/O I/O ControlNet adapter with digital I/O modules

I/O I/O

I/O I/O

ControlNet adapter with analog I/O modules

ControlNet adapter with digital I/O modules

The table below calculates the connections in this example. System Connections:

Amount:

Controller to local ControlNet communication module

0

Controller to ControlNet adapter(1)

0 direct connection for digital I/O modules

4 direct connection for analog I/O modules

2 total connections used: 6 (1)

In this example, the remote ControlNet adapter uses the None communications format.

TIP

If you have a high number of modules, direct connections to each module may not be feasible because the module supports a finite number of connections and packets per second, and direct connections may require more resources than the module has available. In this case, use rack-optimized connections to conserve connection use and network traffic.

Publication 1794-UM061A-EN-P - July 2006

Page 65

Configure Your Adapter and Digital Modules on a ControlNet Network

63

Rack-optimized connections for I/O modules In this example, assume that each digital I/O module is configured for a rack-optimized connection to the controller. Analog modules must be configured for direct connections.

controller with ControlNet communication module or built-in communication port ControlNet network

I/O I/O ControlNet adapter with digital I/O modules

I/O I/O

I/O I/O

ControlNet adapter with analog I/O modules

ControlNet adapter with digital I/O modules

The table below calculates the connections in this example. System Connections:

Amount:

Controller to local ControlNet communication module

0

Controller to ControlNet adapters with digital modules

2

(rack-optimized connection to each adapter) Controller to ControlNet adapter with analog modules

0

(direct connection for each analog I/O module)

2 total connections used: 4

The rack-optimized connection conserves connections, but can limit the status and diagnostic information that is available from the digital I/O modules. To increase the number of available connections, use a rack-optimized connection to any remote adapter with multiple digital I/O modules that allow rack-optimized connection, instead of direct connections to those I/O modules.

Publication 1794-UM061A-EN-P - July 2006

Page 66

64

Configure Your Adapter and Digital Modules on a ControlNet Network

Ownership In a Logix5000 system, modules multicast data. This means that multiple modules can receive the same data at the same time from a single module. When you choose a communication format, you have to choose whether to establish an owner or listen-only relationship with the module. owner controller

The controller that creates the primary configuration and communication connection to a module. The owner controller writes configuration data and can establish a connection to the module. The owner controller is the only device that controls the outputs.

An I/O connection where another controller owns/provides the configuration data for the I/O module. A controller using a listen-only connection only monitors the module. It does not write configuration data and con only maintain a connection to the I/O module when the owner controller is actively controlling the I/O module.

Publication 1794-UM061A-EN-P - July 2006

Page 67

Configure Your Adapter and Digital Modules on a ControlNet Network

Add Local and Remote ControlNet Modules

65

Before you can connect to and control distributed I/O, you must add local and remote ControlNet communication modules. The type of distributed I/O determines your choice of a remote ControlNet adapter. Figure shows a brief series of screens used when adding local and remote ControlNet communication modules to an RSLogix 5000 project. For more detailed information on how to add local and remote ControlNet modules to your project, refer to publication CNET-UM001. 1. Add Local ControlNet Communication Module

2. Add Remote ControlNet Communication Module

Publication 1794-UM061A-EN-P - July 2006

Page 68

66

Configure Your Adapter and Digital Modules on a ControlNet Network

Add Distributed I/O

To communicate with the I/O modules in your system, you add bridge, adapter, and I/O modules to the I/O Configuration folder of the controller. Within the I/O Configuration folder, you organize the modules into a hierarchy (tree/branch, parent/child).

For a typical distributed I/O network… controller local communication module remote adapter

I/O module device

…you build the I/O configuration in this order

A. Add the local communication module (bridge). B. Add the remote adapter for the distributed I/O chassis or DIN rail. C. Add the distributed I/O module.

Do these steps to add distributed I/O to your RSLogix 5000 project: 1. Add the local ControlNet communications modules, add the ControlNet adapter for the distributed I/O. 2. Add the distributed I/O module.

Publication 1794-UM061A-EN-P - July 2006

Page 69

Configure Your Adapter and Digital Modules on a ControlNet Network

67

3. Configure the distributed I/O module. Depending on the distributed I/O type, the configuration screens differ. To:

Do this:

Use the module’s default configuration.

Specify the general information about the module (name, comm format, RPI, and others) and click Finish.

Customize the configuration.

Specify the general information about the module (name, comm format, RPI, and others). Then use the Tabs to step through subsequent screens to configure such parameters as filter times and fault actions. If the Open Module Properties is checked, clicking OK will automatically take you to next tab.

After you complete adding all Flex I/O modules to your project file, you must download the project to your Logix5000 controller.

Publication 1794-UM061A-EN-P - July 2006

Page 70

68

Configure Your Adapter and Digital Modules on a ControlNet Network

Download the Program to the Controller

Follow this procedure to download the program you just saved to the ControlLogix controller. 1. From the main menu, choose Communications>Who-Active. 2. Select the processor slot in the chassis. 3. From the Who Active dialog, choose Set Project Path.

4. From the Who Active dialog, choose Download to see the Download dialog.

5. From the Download dialog, choose Download. You see this RSLogix 5000 dialog.

Publication 1794-UM061A-EN-P - July 2006