FLEX I/O Diagnostic Modules, Catalog Numbers 1794-IB16D, 1794-OB16D, User Manual, pages 51 to 60

Pages 51 to 60 of 132

The original document is the PDF (2.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Allen-Bradley 1794-OB16

Page 51

Configure FLEX I/O Digital Modules on a DeviceNet Network

49

Set the status size for a scanner If you want this information:

Set the Status Which gives you: Size to (DINTs): Member:

Data Type

10

ScanCounter

DINT

DeviceFailureRegister

SINT[8]

AutoverifyFailureRegister

SINT[8]

DeviceIdleRegister

SINT[8]

ActiveNodeRegister

SINT[8]

StatusDisplay

SINT[4]

ScannerAddress

SINT status code of scanner

ScannerStatus

SINT address with an error:

ScrollingDeviceAddress

SINT

ScrollingDeviceStatus

SINT count of I/O scans indication that a device has failed: • There is 1 bit for each address on the DeviceNet network (0 -63). • The position of a bit = address of a device. • If a bit = 1, then the device at that address has failed. indication that the data size of a device does not match the amount of memory allocated for the device in the scanner: • There is 1 bit for each address on the DeviceNet network (0 -63). • The position of a bit = address of a device. • If a bit = 1, then their is a mismatch with that address. indication that a device is idle: • There is 1 bit for each address on the DeviceNet network (0 -63). • The position of a bit = address of a device. • If a bit = 1, then the device at that address is idle. indication that a device is online: • There is 1 bit for each address on the DeviceNet network (0 -63). • The position of a bit = address of a device. • If a bit = 1, then the device at that address is online. ASCII representation of scanner status/display address of the scanner

11

• scrolls through the addresses with errors • ScrollingDeviceStatus member shows the status code status code of an address with an error: • scrolls through addresses with errors • ScrollingDeviceAddress member shows the address possible future expansion of the structure – 5 DINTs

16 status code of lower 32 devices – 1 byte per device

24

DeviceStatus

SINT[32] status code of all devices – 1 byte per device

32

DeviceStatus

SINT[64]

Publication 1794-UM061A-EN-P - July 2006

Page 52

50

Configure FLEX I/O Digital Modules on a DeviceNet Network

Add the Scanner to the I/O Configuration Folder CompactLogix scanner

ControlLogix, FlexLogix, and SoftLogix5800 scanners

1. Right-click and choose New Module.

EtherNet/IP to DeviceNet linking device

ControlNet to DeviceNet linking device

2. Choose the type of scanner.

3. Select the major revision of the scanner.

Publication 1794-UM061A-EN-P - July 2006

Page 53

Configure FLEX I/O Digital Modules on a DeviceNet Network

51

Define the Properties of the Scanner

1. Specify the general properties (name, slot, sizes, etc.).

2. Choose Next.

3. Choose Next. 4. Choose Browse and find the RSNetWorx configuration file for the network (.dnt file). The default path for the file is …\Program Files\Rockwell Software\RSNetWorxII\Networks.

5. Choose Finish.

Publication 1794-UM061A-EN-P - July 2006

Page 54

52

Configure FLEX I/O Digital Modules on a DeviceNet Network

Determine the Address of DeviceNet Data

When you add the scanner to the I/O configuration of the controller, RSLogix 5000 software automatically creates a set of tags for the input, output, and status data of the network:

input data from the scanner output data for the scanner status data from the scanner

The tags for your DeviceNet data follow this format: The scanner memory uses this format: slot type

.Data

[element]

Which is this tag in the controller .bit location

:type

.Data

[element]

.bit = Optional

Where:

Is:

slot slot number of the scanner location

If you have this scanner:

Then location is:

local ControlLogix 1756-DNB

Local:slot_number_of_scanner remote ControlLogix 1756-DNB name_of_remote_bridge:slot_number_of_scanner

CompactLogix 1769-SDN

Local:slot_number_of_scanner

SoftLogix5800 1784-PCIDS

Local:slot_number_of_scanner

DriveLogix/FlexLogix 1788-DNBO name of the scanner in the I/O configuration of the controller

Linking Device 1788-EN2DN or 1788-CN2DN name of the linking device in the I/O configuration of the controller

If the data is:

Then type is:

input from a device

I output to a device

O status of the network

S type element specific DINT (DWord, 32-bit integer) within the array bit specific bit within an integer

Publication 1794-UM061A-EN-P - July 2006

Page 55

Configure FLEX I/O Digital Modules on a DeviceNet Network

53

To determine the tag name (address) for DeviceNet data: 1. On the report for the network, find the memory address for the input or output data of the device.

2. Find the corresponding tag in the controller-scoped tags of the controller using RSLogix 5000. 3. Find the required data within the controller tag. Use the data map for the device as a reference.

Local:2:I.Data[0] 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 data map for Bulletin 160 AC drive

Publication 1794-UM061A-EN-P - July 2006

Page 56

54

Configure FLEX I/O Digital Modules on a DeviceNet Network

Tally Memory Requirements

The 1794-ADN FLEX I/O adapter packs the data of its I/O modules into a contiguous block of input or output bytes. By default, the modules share DINT elements in the scanner. For example, to determine the amount of scanner memory required for your adapter and its I/O modules 1. Add the input bytes of each module + 2 bytes for the adapter. 2. Add the output bytes of each module (0 for the adapter).

Sub Tally Input Size of Device (bytes)

Output Size of Device (bytes)

FLEX I/O adapter - 1794-ADN

2

0 digital output module - 1794-OB16D

2

2 digital input module - 1794-IB16D

2

0

Total

6

2

Device

Main Tally

3. Add the totals to the main tally.

Input Size of Device (bytes)

Input Memory in Scanner (DINTs)

Output Size of Device (bytes)

Output Memory in Scanner (DINTs)

Start/stop Buttons

1

1

1

1

Motor Starter

4

1

4

1

FLEX I/O Adapter w/modules

6

2

2

1

Device

Address

Total

As an option, give each module its own memory location (DINTs) within the scanner. This may make your programming easier. Assign one address for the 1794-ADN and all the modules that you connect to it. DeviceNet network 4 A D N

Publication 1794-UM061A-EN-P - July 2006

I/ I/ I/ O O O

Page 57

Configure FLEX I/O Digital Modules on a DeviceNet Network

If You Configure the Adapter Offline offline Offline configuration Configuration

55

If you configure the FLEX I/O adapter offline, check the I/O sizes of each module. For FLEX I/O, RSNetWorx software uses offline I/O sizes that are different from the default values of the modules.

Online online Configuration configuration

Publication 1794-UM061A-EN-P - July 2006

Page 58

56

Configure FLEX I/O Digital Modules on a DeviceNet Network

Set the Address of the Adapter

To set the address of the FLEX I/O DeviceNet adapter 1794-ADN:

1. To change the address, press the button above or below a number. 2. Connect the adapter to the network. 3. Turn on power to the adapter. 4. Check the Mode/Net STATUS light. If:

Then the:

Green (Flashing or Solid)

address is OK

Solid Red address and/or baud rate conflict with another device

Off device is waiting to set its baud rate When autobaud is on, the device waits until it hears another device on the network. It then sets its baud rate to that of the other device.

For more information on using DeviceNet in Logix5000 control systems, see publication DNET-UM004.

Publication 1794-UM061A-EN-P - July 2006

Page 59

Chapter

6

Configure Your Adapter and Digital Modules on a ControlNet Network

Introduction

This chapter guides you through the steps required to configure your 1794 FLEX I/O ControlNet adapter and associated modules on a ControlNet network using RSNetworx for ControlNet and RSLogix 5000 software. For this information:

See page:

Set Up the Hardware

58

Setting a Requested Packet Interval (RPI)

6-58

Select a Communication Format

6-59

Add Local and Remote ControlNet Modules

65

Add Distributed I/O

66

Download the Program to the Controller

68

Configure the 1794-ACN15 Adapter

69

Schedule I/O Module Connections

70

Access Module Data via the 1794-ACN15 Adapter

75

Change Configuration Data

77

This chapter describes how a controller controls distributed I/O over ControlNet. The controller requires a communication module to connect to the network. Distributed I/O modules require an adapter to connect to the network. In this example, we show you how to control FLEX I/O over ControlNet using RSNetworx for ControlNet and RSLogix 5000. To control distributed I/O over ControlNet, you must: • Add local and remote ControlNet communication modules to your RSLogix 5000 project. • Add distributed I/O to your RSLogix 5000 project. • Schedule the ControlNet network via RSNetWorx for ControlNet. • Use the I/O information in RSLogix 5000 You can also validate connections to distributed I/O when controlling it over ControlNet. This task is particularly useful when one or more of the connections are not working but is not required, especially when all connections appear to work normally.

57

Publication 1794-UM061A-EN-P - July 2006

Page 60

58

Configure Your Adapter and Digital Modules on a ControlNet Network

Set Up the Hardware

In this example, the Logix5000 controller uses a ControlNet communication module in the local chassis to connect to the ControlNet network. The distributed (remote) I/O has a ControlNet adapter to connect it to the ControlNet network. Data Distributed I/O ControlNet adapter with I/O modules

Local Chassis Logix5000 controller with ControlNet communication module

Programming Terminal

43611

Make sure: • all wiring and cabling is properly connected • the communication driver [such as, AB-PCIC(S)-1] is configured for the programming workstation

Setting a Requested Packet Interval (RPI)

When you configure an I/O module, you define the RPI for the module. The RPI specifies the period at which data updates over a connection. For example, an input module sends data to a controller at the RPI that you assign to the module. Configure the RPI in milliseconds. RPIs are only used for modules that produce or consume data. For example a local ControlNet communication module does not require an RPI because it is not a data-producing member of the system; it is used only as a bridge. In Logix5000 controllers, I/O values update at a period that you configure via the I/O configuration folder of the project. The values update asynchronously to the execution of logic. At the specified interval, the controller updates a value independently from the execution of logic. Set the RPI only as fast as needed by the application. The RPI determines the number of packets per second on a connection. Each I/O module has a limit of how many packets it can handle per second. If you exceed this limit, the module cannot open any more connections.

Publication 1794-UM061A-EN-P - July 2006