Manual · Allen-Bradley
FLEX I/O Digital DC Output Modules Installation Instructions
Manual28 pagesPDF 571 KB
Installation instructions for Allen-Bradley FLEX I/O digital DC output modules 1794-OB8, -OB8EP, -OB16, -OB16P and -OB32P.
What this file really is
The old site listed this file as “Installation Manual” for the Allen-Bradley 1794-OB16, 1794-OB16P and 1794-OE4. The file is named for the 1794-OE4, but the document covers FLEX I/O digital DC output modules (1794-OB8, -OB8EP, -OB16, -OB16P, -OB32P) and does not mention the 1794-OE4.
Names · 2 models
The models it names
Allen-Bradley 1794-OB16I/O module from$95.009 in stock Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Installation instructions for the Allen-Bradley FLEX I/O digital DC output modules 1794-OB8, 1794-OB8EP, 1794-OB16, 1794-OB16P and 1794-OB32P. It covers environment and enclosure requirements, hazardous location approvals, mounting the module on a 1794 terminal base, wiring connections for each module, configuring and programming the 1794-OB8EP and the other modules, and detailed specifications with a derating curve for the 1794-OB16P.
Its parts
- Important User Information
- Installing Your Digital Output Module
- Configuring your 1794-OB8EP Output Module
- Configuring your 1794-OB8, 1794-OB16, 1794-OB16P, and 1794-OB32 Output Modules
- Specifications
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Allen-Bradley installation instructions (publication 1794-IN094C-EN-P, July 2015) for the FLEX I/O digital DC output modules 1794-OB8, 1794-OB8EP, 1794-OB16, 1794-OB16P and 1794-OB32P. It does not cover the 1794-OE4 the site also files it under. It shows how to mount and wire each module on its terminal base, the image table bits and the full specifications.
- Outputs
- 1794-OB16 and 1794-OB16P: 16 current-sourcing DC outputs, FLEX I/O p. 1, 20
- Output voltage
- 10V DC min., 24V DC nom., 31.2V DC max. p. 20
- Output current
- 500 mA per channel max.; 8.0 A per module (16 outputs @ 0.5 A) p. 20
- Terminal bases
- 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK p. 20
- 24V supply current
- 1794-OB16: 49 mA @ 24V DC; 1794-OB16P: 60 mA @ 24V DC p. 22
- Operating temperature
- 1794-OB16 and 1794-OB16P: -20 to 55 °C (-4 to 131 °F) p. 23
- Indicators
- 1794-OB16 and 1794-OB16P: 16 yellow status indicators p. 22
- Keyswitch position
- 2 p. 7, 22
- Field wiring
- Outputs on row A terminals 0 to 15; commons on row B; +V DC to terminal 34 (row C); -V DC common to terminal 16 (row B) p. 8
- Leakage and drop
- Off-state leakage 0.5 mA max.; on-state voltage drop 0.5V DC max. p. 20
- Isolation
- 50V continuous, Basic Insulation Type; no isolation between channels p. 20
- Dimensions
- 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in.), H x W x D p. 21
- Image table
- 1794-OB16 and 1794-OB16P use write bits O0 to O15, one bit per output p. 17
- Certifications
- The manual states UL Listed Industrial Control Equipment and, for the 1794-OB16 and 1794-OB16P, CSA Certified Process Control Equipment, when the product is marked p. 24
What this manual walks you through
- Mounting the module on a 1794 terminal base p. 7, 8
- Wiring the outputs, commons and DC power p. 8
- Output and common terminal numbers on the 1794-TB2, 1794-TB3 and 1794-TB3S p. 9, 11
- Daisy-chaining power and common to the next terminal base p. 8
- Wiring the 1794-OB8EP and 1794-OB32P p. 10, 12, 13, 14, 15
- Reading the image table memory map p. 17
- Masking fault bits and resetting faults on the 1794-OB8EP p. 16
- Derating the 1794-OB16P by supply voltage and ambient temperature p. 26
- Handling the module without electrostatic damage p. 3
Good to know
- Inserting or removing the module with backplane power on can cause an electrical arc. p. 8
- Total current through the terminal base is limited to 10 A; separate power connections may be needed. p. 11
- FLEX I/O grounds through the DIN rail, so use zinc plated yellow-chromate steel rail. p. 6
- The module is open-type equipment and must be mounted in a suitable enclosure. p. 3
- Keep debris such as metal chips and wire strands from falling into the module while mounting. p. 7
Questions this manual answers
How many outputs does the 1794-OB16 have?
16 current-sourcing outputs, up to 500 mA each and 8.0 A per module. p. 20
Which terminal base does the 1794-OB16P use?
The 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K or 1794-TB3SK. p. 20
What keyswitch position does the 1794-OB16 need?
Rotate the terminal base keyswitch clockwise to position 2. p. 7
Where does the 24V DC supply connect for a 1794-OB16?
+V DC goes to terminal 34 on row C and -V DC common to terminal 16 on row B. p. 8
How much 24V DC current does the 1794-OB16P draw?
60 mA at 24V DC; the 1794-OB16 draws 49 mA. p. 22
Contents
Chapters and sections
Each line opens the PDF at its page.
The whole text · 3 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file