Page 21

FLEX I/O Digital DC Output Modules

21

Specifications – 1794-OB32P Attribute

Value

Number of outputs

32, current, sourcing

Recommended terminal base unit

1794-TB32, 1794-TB32S

On-state voltage, output min

10V DC

On-state voltage, output nom

24V DC

On-state voltage, output max

31.2V DC

Output current rating

14.0 A max per module (6 A total for channels 0...15; 8 A total for channels 16...31)

On-state current, min

1.0 mA per channel

On-state current, max

500 mA per channel

On-state voltage drop, max

0.5V DC

Surge current

2 A for 50 ms, repeatable every 2 seconds

Off-state leakage current, max

0.5 mA

Isolation voltage

50V (continuous), Basic Insulation Type Type tested at 850V DC for 60 s, between field side and system No isolation between individual channels

Output signal delay(1) Off to On On to Off

0.5 ms 1.0 ms

FlexBus current

80 mA @ 5V DC

Power dissipation, max

5.3 W @ 31.2V DC

Thermal dissipation, max

18.1 BTU/hr @ 31.2V DC

Fusing

Outputs are electronically protected

(1)

Delay time is the time from the receipt of an output on or off command to the output actually turning on or off.

General Specifications Attribute

Value

Off-state voltage, max

31.2V DC

Terminal base screw torque

Determined by installed terminal base

Dimensions, approx. (H x W x D)

94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in.)

Publication 1794-IN094C-EN-P - July 2015

Page 22

22 FLEX I/O Digital DC Output Modules General Specifications Attribute

Value

Indicators (field side indication)

(1794-OB8) 8 yellow status indicators (1794-OB8EP) 8 yellow status indicators 8 red fault indicators (1794-OB16, 1794-OB16P) 16 yellow status indicators (1794-OB32P) 32 yellow status indicators

External DC power supply voltage, nom 24V DC External DC power voltage range

(1794-OB8, 1794-OB16, 1794-OB16P, 1794-OB32P) 10...31.2V DC (includes 5% AC ripple) (1794-OB8EP) 19.2...31.2V DC (includes 5% AC ripple)

External DC power supply current

(1794-OB8) 25 mA @ 24V DC (10...35 mA) (1794-OB8EP) 80 mA @ 24V DC (1794-OB16) 49 mA @ 24V DC (20...65 mA) (1794-OB16P) 60 mA @ 24V DC (25...75 mA) (see Derating Curve) (1794-OB32P) 219 mA @ 24V DC (104 mA @ 10V DC; 278 mA @ 31.2V DC)

North American temp code

(1794-OB8, 1794-OB8EP, 1794-OB16) T4A (1794-OB16P, 1794-OB32P) T3C

IEC temp code

(1794-OB8, 1794-OB8EP, 1794-OB16) T4 (1794-OB16P) T3

Keyswitch position

2

Enclosure type rating

None (open-style)

Wire size

Determined by installed terminal base

Wiring category(1)

2 - on signal ports

(1)

Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

Publication 1794-IN094C-EN-P - July 2015

Page 23

FLEX I/O Digital DC Output Modules

23

Environmental Specifications Attribute

Value

Operating temperature

IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): (1794-OB8, 1794-OB8EP, 1794-OB16, 1794-OB16P) -20…55 °C (-4…131 °F) (1794-OB32P) 0…55 °C (32…131 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock): -40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 5…95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating): 5 g @ 10...500 Hz

Shock, operating

IEC60068-2-27 (Test Ea, Unpackaged shock): 30 g

Shock, nonoperating

IEC60068-2-27 (Test Ea, Unpackaged shock): 50 g

Emissions

CISPR 11: Group 1, Class A (with appropriate enclosure)

ESD immunity

IEC 61000-4-2: 6 kV contact discharges 8 kV air discharges

Radiated RF immunity

(1794-OB8, 1794-OB16) IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz (1794-OB8EP, 1794-OB16P) IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz 10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz 3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz (1794-OB32P) IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from 30...1000 MHz

Publication 1794-IN094C-EN-P - July 2015

Page 24

24 FLEX I/O Digital DC Output Modules Environmental Specifications Attribute

Value

EFT/B immunity

(1794-OB8, 1794-OB16, 1794-OB32P) IEC 61000-4-4: ±2 kV @ 5 kHz on power ports ±2 kV @ 5 kHz on signal ports (1794-OB8EP, 1794-OB16P) IEC 61000-4-4: ±3 kV @ 5 kHz on power ports ±3 kV @ 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5: ±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Conducted RF immunity

IEC 61000-4-6: 10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Certifications Certifications (when product is marked)(1)

Value c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.

CSA

(1794-OB8, 1794-OB8EP, 1794-OB16, 1794-OB16P only) CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.

CE

European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

Publication 1794-IN094C-EN-P - July 2015

Page 25

FLEX I/O Digital DC Output Modules

25

Certifications Certifications (when product is marked)(1)

Value

Ex

(1794-OB8, 1794-OB16 only) European Union 94/9/EC ATEX Directive, compliant with: EN 60079-0:2009; General Requirements EN 60079-15:2010; Potentially Explosive Atmospheres, Protection "n" LCIE 01ATEX6020X II 3 G Ex nA IIC T4 Gc EC 60079-0, 6th Edition IEC 60079-15, 4th Edition (1794-OB8EP, 1794-OB16 only) European Union 94/9/EC ATEX Directive, compliant with: EN60079-0:2012+A11:2013 EN 60079-15:2010; Potentially Explosive Atmospheres, Protection "n" DEMKO 14ATEX1342501X II 3 G Ex nA IIC T4 Gc – 1794-OB8EP III 3 G Ex nA IIC T3 Gc – 1794-OB16P EC 60079-0, 6th Edition IEC 60079-15, 4th Edition

TÜV

(1794-OB8EP, 1794-OB16, 1794-OB16P only) TÜV Certified for Functional Safety: up to and including SIL 2

KC

Korean Registration of Broadcasting and Communications Equipment, compliant with: Article 58-2 of Radio Waves Act, Clause 3

EAC

Russian Customs Union TR CU 020/2011 EMC Technical Regulation

RCM

Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions

(1)

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.

Publication 1794-IN094C-EN-P - July 2015

Page 26

26 FLEX I/O Digital DC Output Modules

Derating Curve for 1794-OB16P 31.2 30 28.5 27.5 25 V in On-State Voltage (V DC) 20

15

10

0

10

30 32

20

37 40

50

55

60

AmbientTemperature oC

The area within the curve represents the safe operating range for the module under various conditions of user supplied 24V DC supply voltages and ambienttemperatures. = Normal mounting safe operating range, (includes

).

= Other mounting positions (including inverted horizontal) safe operating Normal Mounting – Horizontal

Other Mounting (including Vertical, and Inverted Horizontal Mounting)

Publication 1794-IN094C-EN-P - July 2015

Page 27

FLEX I/O Digital DC Output Modules

27

Notes:

Publication 1794-IN094C-EN-P - July 2015

Page 28

Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.

Installation Assistance If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running. United States or Canada

1.440.646.3434

Outside United States or Canada

Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.

New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States

Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.

Outside United States

Please contact your local Rockwell Automation representative for the return procedure.

Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Allen-Bradley, Rockwell Automation, FLEX I/O, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Publication 1794-IN094C-EN-P - July 2015 Supersedes Publication 1794-IN094B-EN-P - April 2004

Copyright © 2015 Rockwell Automation, Inc. All rights reserved.