The text of a manual · part 2 of 3
FLEX I/O Digital DC Output Modules Installation Instructions, pages 11 to 20
Pages 11 to 20 of 28
The original document is the PDF (571 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 1794-OB16 and Allen-Bradley 1794-OB16P
Page 11
FLEX I/O Digital DC Output Modules
11
1794-TB2, 1794-TB3, and 1794-TB3S Terminal Base Wiring for 1794-OB8, 1794-OB8EP, 1794-OB16, and 1794-OB16P Outputs 0
1
2
3
4
5
6
7
8
9
21
22
23
24
25
26
10
11
12
13
14
15
A 17
16
18
19
20
27
28
29
30
31
32
33
B -V Common 35
34
-V Common
Commons 36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
C Voltage In +V
Terminals 35 thru 50 not available on 1794-TB2
Voltage Out +V
Voltage (1794-TB3 shown)
Connect -V (Supply Common) to terminal B-16 Connect +V (Supply +Voltage) to terminal C-34
(Use B-33 and C-51 for daisy-chaining to next terminal base unit.) Total current draw through the terminal base is limited to 10A. Separate power connections to each terminal base may be necessary.
1794-TBN Terminal Base Wiring for 1794-OB8EP Even Numbered I/O Terminals 0 thru 14 COM 16
COM 4
2
0
6
8
10
14
12
33
B 34
1
3
5
7
9
11
13
15
51
C +V
+V Odd Numbered I/O Terminals 1 thru 15
Connect -V (Supply Common) to terminal B-16 Connect +V (Supply +Voltage) to terminal C-34 (Use B-33 and C-51 for daisy-chaining to next terminal base unit.) Total current draw through the terminal base is limited to 10A. Separate power connections to each terminal base may be necessary.
Publication 1794-IN094C-EN-P - July 2015
Page 12
12 FLEX I/O Digital DC Output Modules
Connecting Wiring for the 1794-OB32P 1. Connect individual output wiring (OUT0 to OUT15) to numbered terminals on the 0-15 row (A) as indicated in the Wiring Connections for 1794-OB32P table. 2. Connect the associated power to the +V1 terminal (35, 37, 39, or 41) on the 34-51 row (C) as indicated in the Wiring Connections for 1794-OB32P table. 3. Connect the associated output common (-V1) for OUT0 to OUT15 to COM1 (terminal 36, 38, 40, or 42) on the 34 to 51 row (C). 4. Connect individual output wiring (OUT16 to OUT31) to numbered terminals on the 16-33 row (B) as indicated in the Wiring Connections for 1794-OB32P table. 5. Connect the associated power to the +V2 terminal (43, 45, 47, or 49) on the 34-51 row (C) as indicated in the Wiring Connections for 1794-OB32P table 6. Connect the associated output common (-V2) for OUT16 to OUT31 to COM2 (terminals 44, 46, 48, or 50) on the 34 to 51 row (C). 7. If continuing power to the next terminal base, connect a jumper from terminal 35, 37, 39, or 41 (+V1) and 43, 45, 37, or 49 (+V2) on this base unit to the power terminal on the next base unit. 8. If continuing output common return to the next base unit, connect a jumper from terminal 36, 38, 40 or 42 (COM1) and 44, 46, 48 or 50 (COM2) on this base unit to common on the next base unit (refer to the installation instructions for the next type of terminal base unit). Note: Total current draw through the terminal base is limited to 10 A. Separate power connections may be necessary.
Publication 1794-IN094C-EN-P - July 2015
Page 13
FLEX I/O Digital DC Output Modules
13
Wiring Connections for 1794-OB32P (used with 1794-TB32 or 1794-TB32S Terminal Base Unit) Output
Output Terminal
Common
Power
Output 0
A-0
Output 1
A-1
Connect common to terminals 36, 38, 40, and 42
Connect power to terminals 35, 37, 39, and 41
Output 2
A-2
Output 3
A-3
Output 4
A-4
Output 5
A-5
Output 6
A-6
Output 7
A-7
Output 8
A-8
Output 9
A-9
Output 10
A-10
Output 11
A-11
Output 12
A-12
Output 13
A-13
Output 14
A-14
Output 15
A-15
Publication 1794-IN094C-EN-P - July 2015
Page 14
14 FLEX I/O Digital DC Output Modules Wiring Connections for 1794-OB32P (used with 1794-TB32 or 1794-TB32S Terminal Base Unit) Output
Output Terminal
Common
Power
Output 16
B-17
Output 17
B-18
Connect common to terminals 44, 46, 48, and 50
Connect power to terminals 43, 45, 47, and 49
Output 18
B-19
Output 19
B-20
Output 20
B-21
Output 21
B-22
Output 22
B-23
Output 23
B-24
Output 24
B-25
Output 25
B-26
Output 26
B-27
Output 27
B-28
Output 28
B-29
Output 29
B-30
Output 30
B-31
Output 31
B-32
For Outputs 0...15, use +V1 and COM1 +V1 DC power
Power terminals 35, 37, 39, and 41
Com1 DC Return
Common terminals 36, 38, 40, and 42
For Outputs 16...31, use +V2 and COM2 +V2 DC power
Power terminals 43, 45, 47, and 49
Com2 DC Return
Common terminals 44, 46, 48, and 50
Publication 1794-IN094C-EN-P - July 2015
Page 15
FLEX I/O Digital DC Output Modules
15
1794-TB32 and 1794-TB32S Terminal Base Wiring for 1794-OB32PI 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
A Outputs 16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
B NC
NC
Outputs 34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
NC
+V1 COM1 +V1 COM1 +V1 COM1 +V1 COM1 +V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC
C +V1 = Terminals 35, 37, 39 and 41 +V2 = Terminals 43, 45, 47 and 49 COM1 = Terminals 36, 38, 40 and 42 COM2 = Terminals 44, 46, 48 and 50 NC = No connections (terminals 16, 33, 34 and 51)
(1794-TB32 shown)
Configuring your 1794-OB8EP Output Module You configure your output module by setting bits in the configuration word (see below). Image Table Memory Map for the 1794-OB8EP Module Dec
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Oct
17
16
15
14
13
12
11
10
7
6
5
4
3
2
1
0
Read
F7
F6
F5
F4
F3
F2
F1
F0
Reserved (see note)
Write
Not used
FR
O7
O4
O3
O2
O1
O0
Where
O = Output – O0 corresponds to output 0, O1 corresponds to output 1, and so on. F = Overload fault bit – 1 = fault present; 0 = no fault FR = Fault reset bit – 1 = reset output; 0 = no change
O6
O5
Note: The unused lower byte in read word 1 floats during operation. Do not use this byte for fault status. See Programming below.
Publication 1794-IN094C-EN-P - July 2015
Page 16
16 FLEX I/O Digital DC Output Modules
Programming the 1794-OB8EP If your program automatically checks for fault bits, bits 8 thru 15 of read word 1 must be masked. This is a sample program for a module at rack address 1, group 0. Add similar rungs to your program. MVM This rung masked bits 8 thru 15.
MASKED MOVE Source Mask Destination
CMP Compare Expression N9: < > 0
I:010 FF00 N9:0 O:000 ( Out )
This rung turns on output if a fault occurs.
Resetting a Fault on the 1794-OB8EP Faults can be reset 3 ways: press the fault reset button on the front of the module; or toggle the output reset bit (write word 1, bit 08); or cycle backplane power. Using the Reset Button on the 1794-OB8EP When you press the reset button, the fault indicator for the faulted output turns off for about 1.2s. After the delay, the faulted output attempts to turn on. If the external condition causing the fault is corrected, the output will remain on, the fault indicator is off, and the status indicator is on.
Publication 1794-IN094C-EN-P - July 2015
Page 17
FLEX I/O Digital DC Output Modules
17
Configuring your 1794-OB8, 1794-OB16, 1794-OB16P, and 1794-OB32 Output Modules You configure your output module by setting bits in the configuration word (word 3). Image Table Memory Map for the 1794-OB8, 1794-OB16, 1794OB16P, and 1794-OB32P Modules Dec
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Oct
17
16
15
14
13
12
11
10
7
6
5
4
3
2
1
0
Read
Not used
Write
O15
O14
O13
O12
O11
O10
O9
O8
O7
O6
O5
O4
O3
O2
O1
O0
Write O31 1794-OB32P only
O30
O29
O28
O27
O26
O25
O24
O23
O22
O21
O20
O19
O18
O17
O16
Where
O = Output – O0 corresponds to output 0, O1 corresponds to output 1, and so on.
1794-OB8 uses outputs 0...7; 1794-OB16 and 1794-OB16P use outputs 0...15; 1794-OB32P uses outputs 0...31.
Publication 1794-IN094C-EN-P - July 2015
Page 18
18 FLEX I/O Digital DC Output Modules
Specifications Specifications – 1794-OB8 Attribute
Value
Number of outputs
8, current, sourcing
Recommended terminal base unit
1794-TB2, 1794-TB3, 1794-TB3S,1794-TB3K, 1794-TB3SK
On-state voltage, output min
10V DC
On-state voltage, output nom
24V DC
On-state voltage, output max
31.2V DC
Output current rating
4 A (8 outputs @ 0.5 A)
On-state current, output, min
1.0 mA per channel
On-state current, output, max
500 mA per channel
On-state voltage drop, max
0.5V DC
Surge current
2 A for 50 ms, repeatable every 2 seconds
Off-state leakage current, max
0.5 mA
Isolation voltage
50V (continuous), Basic Insulation Type Tested at 850V DC for 1 s, between user and system No isolation between individual channels
Output signal delay(1) Off to On On to Off
0.5 ms 1.0 ms
FlexBus current
60 mA @ 5V DC
Power dissipation, max
3.3 W @ 31.2V DC
Thermal dissipation, max
11.2 BTU/hr @ 31.2V DC
Fusing
Module outputs are not fused. Fusing is recommended. If fusing is desired, you must provide external fusing. Use SAN-O MQ4-800mA fuses.
(1)
Delay time is the time from the receipt of an output on or off command to the output actually turning on or off.
Specifications – 1794-OB8EP Attribute
Value
Number of outputs
8, current, sourcing
Recommended terminal base unit
1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TB3K, 1794-TB3SK, 1794-TBNK
On-state voltage, output min
19.2V DC
Publication 1794-IN094C-EN-P - July 2015
Page 19
FLEX I/O Digital DC Output Modules
19
Specifications – 1794-OB8EP Attribute
Value
On-state voltage, output nom
24V DC
On-state voltage, output max
31.2V DC
Output current rating
2.0 A max per output 10.0 A max per module (8 outputs @ 1.25 A, 5 outputs @ 2.0 A, or similar combinations totaling 10.0 A or less)
On-state current, output, min
1.0 mA per channel
On-state current, output, max
2.0 A per channel
On-state voltage drop, max
0.2V DC
Surge current
4 A for 50 ms, repeatable every 3 seconds
Off-state leakage current, max
0.5 mA
Isolation voltage
50V (continuous), Basic Insulation Type Tested at 850V DC for 1 s, between field side and system No isolation between individual channels
Output signal delay(1) Off to On On to Off
0.1 ms 0.1 ms
FlexBus current
73 mA @ 5V DC
Power dissipation, max
5.5 W @ 31.2V DC
Thermal dissipation, max
18.8 BTU/hr @ 31.2V DC
Fusing
Outputs are electronically fused
(1)
Delay time is the time from the receipt of an output on or off command to the output actually turning on or off.
Surge Current for 1794-OB8EP
Surge Current - A
Output minimum Surge Current
20 15 10 5 0 0
10
20
30
40
50
Time - ms Publication 1794-IN094C-EN-P - July 2015
Page 20
20 FLEX I/O Digital DC Output Modules
Specifications – 1794-OB16 and 1794-OB16P Attribute
1794-OB16
Number of outputs
16, current, sourcing
1794-OB16P
Recommended terminal base unit
1794-TB2,1794-TB3,1794-TB3S, 1794-TB3K, 1794-TB3SK
On-state voltage, output min
10V DC
On-state voltage, output nom
24V DC
On-state voltage, output max
31.2V DC (see Derating Curve for 1794-OB16P)
Output current rating
8.0 A (16 outputs @ 0.5 A)
On-state current, output, min
1.0 mA per channel
On-state current, output, max
500 mA per channel
On-state voltage drop, max
0.5V DC
Surge current
2 A for 50 ms, repeatable every 1.5 A for 50 ms, repeatable 2 seconds every 2 seconds
Off-state leakage current, max
0.5 mA
Isolation voltage
50V (continuous), Basic Insulation Type Tested at 850V DC for 1 s between user and system No isolation between individual channels
50V (continuous), Basic Insulation Type Type tested at 2121V DC for 60 s, between field side and system No isolation between individual channels
Output signal delay(1) Off to On On to Off
0.5 ms 1.0 ms
FlexBus current
80 mA @ 5V DC
60 mA @ 5V DC
Power dissipation, max
5.3 W @ 31.2V DC
5.0 W @ 31.2V DC
Thermal dissipation, max
18.1 BTU/hr @ 31.2V DC
17.0 BTU/hr @ 31.2V DC
Fusing
Module outputs are not fused. Fusing is recommended. If fusing is desired, you must provide external fusing. Use SAN-O MQ4-800mA fuses.
Outputs are electronically protected.
(1)
Delay time is the time from the receipt of an output on or off command to the output actually turning on or off.
Publication 1794-IN094C-EN-P - July 2015