For the Allen-Bradley 1794-OB16 and Allen-Bradley 1794-OB16P

Page 11

FLEX I/O Digital DC Output Modules

11

1794-TB2, 1794-TB3, and 1794-TB3S Terminal Base Wiring for 1794-OB8, 1794-OB8EP, 1794-OB16, and 1794-OB16P Outputs 0

1

2

3

4

5

6

7

8

9

21

22

23

24

25

26

10

11

12

13

14

15

A 17

16

18

19

20

27

28

29

30

31

32

33

B -V Common 35

34

-V Common

Commons 36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

C Voltage In +V

Terminals 35 thru 50 not available on 1794-TB2

Voltage Out +V

Voltage (1794-TB3 shown)

Connect -V (Supply Common) to terminal B-16 Connect +V (Supply +Voltage) to terminal C-34

(Use B-33 and C-51 for daisy-chaining to next terminal base unit.) Total current draw through the terminal base is limited to 10A. Separate power connections to each terminal base may be necessary.

1794-TBN Terminal Base Wiring for 1794-OB8EP Even Numbered I/O Terminals 0 thru 14 COM 16

COM 4

2

0

6

8

10

14

12

33

B 34

1

3

5

7

9

11

13

15

51

C +V

+V Odd Numbered I/O Terminals 1 thru 15

Connect -V (Supply Common) to terminal B-16 Connect +V (Supply +Voltage) to terminal C-34 (Use B-33 and C-51 for daisy-chaining to next terminal base unit.) Total current draw through the terminal base is limited to 10A. Separate power connections to each terminal base may be necessary.

Publication 1794-IN094C-EN-P - July 2015

Page 12

12 FLEX I/O Digital DC Output Modules

Connecting Wiring for the 1794-OB32P 1. Connect individual output wiring (OUT0 to OUT15) to numbered terminals on the 0-15 row (A) as indicated in the Wiring Connections for 1794-OB32P table. 2. Connect the associated power to the +V1 terminal (35, 37, 39, or 41) on the 34-51 row (C) as indicated in the Wiring Connections for 1794-OB32P table. 3. Connect the associated output common (-V1) for OUT0 to OUT15 to COM1 (terminal 36, 38, 40, or 42) on the 34 to 51 row (C). 4. Connect individual output wiring (OUT16 to OUT31) to numbered terminals on the 16-33 row (B) as indicated in the Wiring Connections for 1794-OB32P table. 5. Connect the associated power to the +V2 terminal (43, 45, 47, or 49) on the 34-51 row (C) as indicated in the Wiring Connections for 1794-OB32P table 6. Connect the associated output common (-V2) for OUT16 to OUT31 to COM2 (terminals 44, 46, 48, or 50) on the 34 to 51 row (C). 7. If continuing power to the next terminal base, connect a jumper from terminal 35, 37, 39, or 41 (+V1) and 43, 45, 37, or 49 (+V2) on this base unit to the power terminal on the next base unit. 8. If continuing output common return to the next base unit, connect a jumper from terminal 36, 38, 40 or 42 (COM1) and 44, 46, 48 or 50 (COM2) on this base unit to common on the next base unit (refer to the installation instructions for the next type of terminal base unit). Note: Total current draw through the terminal base is limited to 10 A. Separate power connections may be necessary.

Publication 1794-IN094C-EN-P - July 2015

Page 13

FLEX I/O Digital DC Output Modules

13

Wiring Connections for 1794-OB32P (used with 1794-TB32 or 1794-TB32S Terminal Base Unit) Output

Output Terminal

Common

Power

Output 0

A-0

Output 1

A-1

Connect common to terminals 36, 38, 40, and 42

Connect power to terminals 35, 37, 39, and 41

Output 2

A-2

Output 3

A-3

Output 4

A-4

Output 5

A-5

Output 6

A-6

Output 7

A-7

Output 8

A-8

Output 9

A-9

Output 10

A-10

Output 11

A-11

Output 12

A-12

Output 13

A-13

Output 14

A-14

Output 15

A-15

Publication 1794-IN094C-EN-P - July 2015

Page 14

14 FLEX I/O Digital DC Output Modules Wiring Connections for 1794-OB32P (used with 1794-TB32 or 1794-TB32S Terminal Base Unit) Output

Output Terminal

Common

Power

Output 16

B-17

Output 17

B-18

Connect common to terminals 44, 46, 48, and 50

Connect power to terminals 43, 45, 47, and 49

Output 18

B-19

Output 19

B-20

Output 20

B-21

Output 21

B-22

Output 22

B-23

Output 23

B-24

Output 24

B-25

Output 25

B-26

Output 26

B-27

Output 27

B-28

Output 28

B-29

Output 29

B-30

Output 30

B-31

Output 31

B-32

For Outputs 0...15, use +V1 and COM1 +V1 DC power

Power terminals 35, 37, 39, and 41

Com1 DC Return

Common terminals 36, 38, 40, and 42

For Outputs 16...31, use +V2 and COM2 +V2 DC power

Power terminals 43, 45, 47, and 49

Com2 DC Return

Common terminals 44, 46, 48, and 50

Publication 1794-IN094C-EN-P - July 2015

Page 15

FLEX I/O Digital DC Output Modules

15

1794-TB32 and 1794-TB32S Terminal Base Wiring for 1794-OB32PI 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

A Outputs 16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

B NC

NC

Outputs 34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

NC

+V1 COM1 +V1 COM1 +V1 COM1 +V1 COM1 +V2 COM2 +V2 COM2 +V2 COM2 +V2 COM2 NC

C +V1 = Terminals 35, 37, 39 and 41 +V2 = Terminals 43, 45, 47 and 49 COM1 = Terminals 36, 38, 40 and 42 COM2 = Terminals 44, 46, 48 and 50 NC = No connections (terminals 16, 33, 34 and 51)

(1794-TB32 shown)

Configuring your 1794-OB8EP Output Module You configure your output module by setting bits in the configuration word (see below). Image Table Memory Map for the 1794-OB8EP Module Dec

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read

F7

F6

F5

F4

F3

F2

F1

F0

Reserved (see note)

Write

Not used

FR

O7

O4

O3

O2

O1

O0

Where

O = Output – O0 corresponds to output 0, O1 corresponds to output 1, and so on. F = Overload fault bit – 1 = fault present; 0 = no fault FR = Fault reset bit – 1 = reset output; 0 = no change

O6

O5

Note: The unused lower byte in read word 1 floats during operation. Do not use this byte for fault status. See Programming below.

Publication 1794-IN094C-EN-P - July 2015

Page 16

16 FLEX I/O Digital DC Output Modules

Programming the 1794-OB8EP If your program automatically checks for fault bits, bits 8 thru 15 of read word 1 must be masked. This is a sample program for a module at rack address 1, group 0. Add similar rungs to your program. MVM This rung masked bits 8 thru 15.

MASKED MOVE Source Mask Destination

CMP Compare Expression N9: < > 0

I:010 FF00 N9:0 O:000 ( Out )

This rung turns on output if a fault occurs.

Resetting a Fault on the 1794-OB8EP Faults can be reset 3 ways: press the fault reset button on the front of the module; or toggle the output reset bit (write word 1, bit 08); or cycle backplane power. Using the Reset Button on the 1794-OB8EP When you press the reset button, the fault indicator for the faulted output turns off for about 1.2s. After the delay, the faulted output attempts to turn on. If the external condition causing the fault is corrected, the output will remain on, the fault indicator is off, and the status indicator is on.

Publication 1794-IN094C-EN-P - July 2015

Page 17

FLEX I/O Digital DC Output Modules

17

Configuring your 1794-OB8, 1794-OB16, 1794-OB16P, and 1794-OB32 Output Modules You configure your output module by setting bits in the configuration word (word 3). Image Table Memory Map for the 1794-OB8, 1794-OB16, 1794OB16P, and 1794-OB32P Modules Dec

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Read

Not used

Write

O15

O14

O13

O12

O11

O10

O9

O8

O7

O6

O5

O4

O3

O2

O1

O0

Write O31 1794-OB32P only

O30

O29

O28

O27

O26

O25

O24

O23

O22

O21

O20

O19

O18

O17

O16

Where

O = Output – O0 corresponds to output 0, O1 corresponds to output 1, and so on.

1794-OB8 uses outputs 0...7; 1794-OB16 and 1794-OB16P use outputs 0...15; 1794-OB32P uses outputs 0...31.

Publication 1794-IN094C-EN-P - July 2015

Page 18

18 FLEX I/O Digital DC Output Modules

Specifications Specifications – 1794-OB8 Attribute

Value

Number of outputs

8, current, sourcing

Recommended terminal base unit

1794-TB2, 1794-TB3, 1794-TB3S,1794-TB3K, 1794-TB3SK

On-state voltage, output min

10V DC

On-state voltage, output nom

24V DC

On-state voltage, output max

31.2V DC

Output current rating

4 A (8 outputs @ 0.5 A)

On-state current, output, min

1.0 mA per channel

On-state current, output, max

500 mA per channel

On-state voltage drop, max

0.5V DC

Surge current

2 A for 50 ms, repeatable every 2 seconds

Off-state leakage current, max

0.5 mA

Isolation voltage

50V (continuous), Basic Insulation Type Tested at 850V DC for 1 s, between user and system No isolation between individual channels

Output signal delay(1) Off to On On to Off

0.5 ms 1.0 ms

FlexBus current

60 mA @ 5V DC

Power dissipation, max

3.3 W @ 31.2V DC

Thermal dissipation, max

11.2 BTU/hr @ 31.2V DC

Fusing

Module outputs are not fused. Fusing is recommended. If fusing is desired, you must provide external fusing. Use SAN-O MQ4-800mA fuses.

(1)

Delay time is the time from the receipt of an output on or off command to the output actually turning on or off.

Specifications – 1794-OB8EP Attribute

Value

Number of outputs

8, current, sourcing

Recommended terminal base unit

1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TB3K, 1794-TB3SK, 1794-TBNK

On-state voltage, output min

19.2V DC

Publication 1794-IN094C-EN-P - July 2015

Page 19

FLEX I/O Digital DC Output Modules

19

Specifications – 1794-OB8EP Attribute

Value

On-state voltage, output nom

24V DC

On-state voltage, output max

31.2V DC

Output current rating

2.0 A max per output 10.0 A max per module (8 outputs @ 1.25 A, 5 outputs @ 2.0 A, or similar combinations totaling 10.0 A or less)

On-state current, output, min

1.0 mA per channel

On-state current, output, max

2.0 A per channel

On-state voltage drop, max

0.2V DC

Surge current

4 A for 50 ms, repeatable every 3 seconds

Off-state leakage current, max

0.5 mA

Isolation voltage

50V (continuous), Basic Insulation Type Tested at 850V DC for 1 s, between field side and system No isolation between individual channels

Output signal delay(1) Off to On On to Off

0.1 ms 0.1 ms

FlexBus current

73 mA @ 5V DC

Power dissipation, max

5.5 W @ 31.2V DC

Thermal dissipation, max

18.8 BTU/hr @ 31.2V DC

Fusing

Outputs are electronically fused

(1)

Delay time is the time from the receipt of an output on or off command to the output actually turning on or off.

Surge Current for 1794-OB8EP

Surge Current - A

Output minimum Surge Current

20 15 10 5 0 0

10

20

30

40

50

Time - ms Publication 1794-IN094C-EN-P - July 2015

Page 20

20 FLEX I/O Digital DC Output Modules

Specifications – 1794-OB16 and 1794-OB16P Attribute

1794-OB16

Number of outputs

16, current, sourcing

1794-OB16P

Recommended terminal base unit

1794-TB2,1794-TB3,1794-TB3S, 1794-TB3K, 1794-TB3SK

On-state voltage, output min

10V DC

On-state voltage, output nom

24V DC

On-state voltage, output max

31.2V DC (see Derating Curve for 1794-OB16P)

Output current rating

8.0 A (16 outputs @ 0.5 A)

On-state current, output, min

1.0 mA per channel

On-state current, output, max

500 mA per channel

On-state voltage drop, max

0.5V DC

Surge current

2 A for 50 ms, repeatable every 1.5 A for 50 ms, repeatable 2 seconds every 2 seconds

Off-state leakage current, max

0.5 mA

Isolation voltage

50V (continuous), Basic Insulation Type Tested at 850V DC for 1 s between user and system No isolation between individual channels

50V (continuous), Basic Insulation Type Type tested at 2121V DC for 60 s, between field side and system No isolation between individual channels

Output signal delay(1) Off to On On to Off

0.5 ms 1.0 ms

FlexBus current

80 mA @ 5V DC

60 mA @ 5V DC

Power dissipation, max

5.3 W @ 31.2V DC

5.0 W @ 31.2V DC

Thermal dissipation, max

18.1 BTU/hr @ 31.2V DC

17.0 BTU/hr @ 31.2V DC

Fusing

Module outputs are not fused. Fusing is recommended. If fusing is desired, you must provide external fusing. Use SAN-O MQ4-800mA fuses.

Outputs are electronically protected.

(1)

Delay time is the time from the receipt of an output on or off command to the output actually turning on or off.

Publication 1794-IN094C-EN-P - July 2015