For the Allen-Bradley 1794-IB16 and Allen-Bradley 1794-IH16

Page 10

Select FLEX I/O Modules

17

Digital I/O Module Summary Catalog Number

Inputs

Outputs

Terminal Base Unit

Electrical Range

Module Type

1794-IB8

8, 24V DC

Nonisolated inputs

1794-IB16

16, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK

DC Modules

1794-IB16D

1794-TB32, 1794-TB32S

Group isolated inputs Diagnostics

1794-IB16XT

1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK

Nonisolated inputs Extended temperatures

1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK

Nonisolated I/O

16

1794-TB32, 1794-TB32S

Nonisolated I/O Protected outputs, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK

1794-IB10XOB6

10

6

1794-IB10XOB6XT 1794-IB16XOB16P

16

1794-IC16 1794-IG16

Nonisolated I/O Extended temperatures

48V DC 5V DC

1794-IH16

125V DC

1794-IV16

24V DC

1794-IB32

32

1794-TB32, 1794-TB32S

1794-IV32 1794-OB8

Nonisolated inputs with groups, 8

1794-OB8EP

1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK, 16

1794-OB16D 1794-OB16P

1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK

1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TB3K, 1794-TB3SK, 1794-TBNK

1794-OB16PXT

1794-OB32P

24V DC

1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TB3K, 1794-TB3SK, 1794-TBNK

1794-OB8EPXT

1794-OB16

Nonisolated inputs

Nonisolated outputs Nonisolated, protected outputs Nonisolated, protected outputs Extended temperatures

24V DC

Nonisolated outputs Group isolated inputs Diagnostics Nonisolated, protected outputs Conformal coated Nonisolated, protected outputs Extended temperatures

32

1794-TB32, 1794-TB32S

Nonisolated, protected outputs with groups

Publication 1794-SG002D-EN-P - May 2012

Page 11

18

Select FLEX I/O Modules

Digital I/O Module Summary Catalog Number

Inputs

Outputs

Terminal Base Unit

Electrical Range

Module Type

1794-OC16, 16

1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK

48V DC

Nonisolated outputs

1794-OG16

5V DC

1794-OV16

24V DC

1794-OV16P

Nonisolated, protected outputs

1794-OV32

32

1794-TB32, 1794-TB32S

8

1794-TB2, 1794-TB3, 1794-TB3S, 1794-TBN, 1794-TBNF, 1794-TB3K, 1794-TB3SK, 1794-TBNK, 1794-TBNFK

Nonisolated inputs in groups

Relay Modules 1794-OW8, 1794-OW8XT

24V DC

Isolated outputs Electromagnetic relays Isolated outputs Electromagnetic relays Extended temperatures

(1) Auxiliary terminal strips are required when using the 1794-TBN.

Select Input Filter Times for Digital Modules

Input filter times can be set to the following values (EtherNet/IP, ControlNet, and DeviceNet only). Input Filter Times – AC Modules Filter Times for Inputs

Maximum Times (ms) OFF to ON 1794-IA8, 1794-IA8I

1794-IA16, 1794-IM8

1794-IA8, 1794-IA8I

1794-IA16, 1794-IM8

Filter time 0 (default)

8.4(1)

7.5

26.4(2)

26.5

1

8.6

8

26.6

27

2

9

9

27

28

3

10

10

28

29

4

12

12

30

31

5

16

16

34

35

6

24

24.5

42

44

7

40

42

58

60.5

(1) OFF to ON filter is 8 ms. (2) ON to OFF filter is 26 ms.

Publication 1794-SG002D-EN-P - May 2012

ON to OFF

Page 12

Select FLEX I/O Modules

23

1794-OM8 Derating Curve

Vin

On-State Voltage (V AC)

Ambient Temperature °C

The area within the curve represents the safe operating range for the module under various conditions of user supplied 220V AC supply voltages and ambient temperatures. = Normal mounting safe operating range included = Other mounting positions (including inverted horizontal, vertical) safe operating range

FLEX I/O Digital DC Input Modules Digital DC Input Comparison Specification

1794-IB8, 1794-IB16, 1794-IB16XT

1794-IV16

1794-IB32

1794-IV32

1794-IC16

1794-IG16

1794-IH16

Voltage, on-state input, min

10V DC, sinking 10V DC, sourcing

19.2V DC, sinking

19.2V DC, sourcing

30V DC, sinking

-0.2V DC, TTL

90V DC, sinking

Voltage, on-state input, nom 24V DC

48V DC

0V DC

125V DC

Voltage, on-state input, max

60V DC

0.8V DC

146V DC

10V DC

2.0...5.5V DC

20V DC

31.2V DC

Voltage, off-state input, max 5V DC Terminal base unit

1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK

1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK

1794-TB32, 1794-TB32S

Current, on-state input, min

2.0 mA

Current, on-state input, nom

8 mA @ 24V DC

4.1 mA @ 24V DC

4.1 mA

Current, on-state input, max

1794-IB16:12 mA 1794-IB8, 1794-IV16: 11 mA 1794-IB16XT: 5.0 mA

6 mA

6 mA

1794-TB3, 1794-TB3S, 1794-TB3K, 1794-TB3SK, 1.0 mA

5 mA @ 48V DC, 2 mA @ 125V DC

11 mA, 3 mA

4.1 mA

0.8 mA

Current, off-state input, max 1.5 mA Input impedance, max

4.6 kΩ

4.7 kΩ

6 kΩ

11 kΩ, 60 kΩ

Power dissipation, max

3.5 W @ 31.2V DC(1)

5.7 W @ 31.2V DC

6.0 W @ 31.2V DC

6.4 W @ 60V DC

1.4 W @ 5.5V DC

6 W @ 146V DC

Thermal dissipation, max

11.9 BTU/hr @ 31.2V DC(2)

19.4 BTU/hr @ 31.2V DC

20.5 BTU/hr @ 31.2V DC

21.9 BTU/hr @ 60V DC

4.78 BTU/hr @ 5.5V DC

20.47 BTU/hr @ 146V DC

Publication 1794-SG002D-EN-P - May 2012

Page 13

24

Select FLEX I/O Modules

Digital DC Input Comparison Specification

1794-IB8, 1794-IB16, 1794-IB16XT

1794-IV16

1794-IB32

1794-IV32

Dimensions (HxWxD), approx

46 x 94 x 53 mm (1.8 x 3.7 x 2.1 in.) 94 x 94 x 69 mm (3.7 x 3.7 x 2.7 in.) installed

Isolation voltage

50V (continuous), Basic Insulation Type, between field side and system No isolation between individual channels 1794-IB8, 1794-IB16XT: Type tested at 850V DC for 60 s 1794-IV16: Type tested at 700V DC for 60 s 1794-IB32: Routine tested at 2121V DC for 2 s 1794-IV32: Type tested at 707V DC for 60 s All other modules: Type tested at 707V DC for 60 s

1794-IC16

1794-IG16

1794-IH16

Tested at 1900V DC for 1 s, I/O to system No isolation between individual channels

50V (continuous), Basic Insulation Type, between field side and system No isolation between individual channels Type tested at 707V DC for 60 s

250V (continuous), Basic Insulation Type, between field side and system Type tested at 1706V DC for 60 s, between field side and system No isolation between individual channels

(1) Power dissipation – 1794-IB16: 6.1 W @ 31.2V DC; 1794-IB16XT: 2 W @ 31.2V DC (2) Thermal dissipation – 1794-IB16: 20.8 BTU/hr at 31.2V DC; 1794-IB16XT: 9.2 BTU/hr @ 31.2V DC

IMPORTANT

• Do not put the 1794-IB8 module next to an output module in 8-point compact addressing with the 1794-ASB2/C or 1794-ASB/D. • Modules have a yellow status indicator for each channel. These indicators are driven from the customer field-side input device.

1794-IB16 Derating Curve

Vin

On-State Voltage (V DC)

Ambient Temperature °C

The area within the curve represents the safe operating range for the module under various conditions of user supplied 24V DC supply voltages and ambient temperatures. = Normal mounting safe operating range included = Other mounting positions (including inverted horizontal, vertical) safe operating range

Publication 1794-SG002D-EN-P - May 2012

Page 14

Section

1.4

Select a FLEX I/O Terminal Base Unit

Step 3 – Select:

the appropriate terminal base unit for your module and system Each FLEX I/O module requires a terminal base unit that snaps onto the DIN rail to the right of the I/O adapter. The terminal bases provide terminal connection points for the I/O wiring and plug together to form the backplane. They are available with screw, clamp, or spring terminations. Common Terminal Base Characteristics Current Capacity, max

Wire Size

Dimensions (HxWxD)

10

0.34…2.1 mm2 (22…14 AWG) solid or stranded copper wire rated at 75 °C (167 °F) or greater, 1.2 mm (3/64 in.) insulation max

94 x 94 x 69 mm 3.7 x 3.7 x 2.7 in. 1794-TB37DS and 1794-TB62DS* (1) 127 x 94 x 69 mm 5.0 x 3.7 x 2.7 in

(1) Measured with expansion module installed.

The following table is a comparison of general specifications for each FLEX I/O terminal base unit. For compatibility with FLEX I/O modules, see Table Digital I/O Module Summary on page 16. General Specification Comparison Catalog(1)

Termination Connections Type

Used in Applications

Current Wiring Capacity, Category max

Purpose

1794-TB2

Cage clamp

Up to 132V AC/156V DC

10

2

A generic 2-wire version of the 1794-TB3.

Module dependent

Primarily intended for use with input modules when using 3-wire input proximity switches – can also be used with output modules.

1794-TB3, 1794-TB3K(2)

16 I/O; 18 common; 18 +V

1794-TB3S, 1794-TB3SK

Spring clamp

1794-TB32

Cage clamp

1794-TB32S

Spring clamp

1794-TB3G, 1794-TB3GK(2)

Grounded screw clamp

1794-TB3GS, Grounded 1794-TB3GSK(2) spring clamp

65

16 I/O; 18 common; 2 +V

A spring clamp version of the 1794-TB3 – provides faster, simpler wire installation. 32 I/O; 8 common; 8 +V

Up to 31.2V DC

A 32-point version of the 1794-TB3 to be used with 32-point digital modules and the 1794-IB16D module. A spring clamp version of the 1794-TB32.

36 I/O; 2 common; 2 +V; 10 chassis ground

A screw clamp terminal base unit with individual grounding used with certain analog modules. 2

A spring clamp version of the 1794-TB3G.

Publication 1794-SG002D-EN-P - May 2012

Page 15

66

Select a FLEX I/O Terminal Base Unit

General Specification Comparison Catalog(1)

Termination Connections Type

Used in Applications

Current Wiring Capacity, Category max

Purpose

1794-TB3T

Cage clamp, temperature

16 I/O; 10 common; 4 +V; 8 chassis ground; 2 sets of CJC for temperature modules

Up to 132V AC/156V DC

10

Module dependent

A cage clamp terminal base to be used with the 1794-IT8 or 1794-IRT8 module (when used in thermocouple mode) – also provides chassis ground connections for the 1794-IR8 and analog modules.

1794-TB3TS, 1794-TB3TSK(2)

Spring clamp, temperature

16 I/O; 10 common; 4 +V; 8 chassis ground; 2 sets of CJC for temperature modules

Up to 132V AC/156V DC

10

2

A spring clamp version of the 1794-TB3T.

1794-TBKD

Cage clamp, knife disconnect

16 I/O; 18 common; 2 +V, Module dependent

A cage clamp terminal base with 16 knife disconnects.

1794-TBKDS

A spring clamp version of the 1794-TBKD.

1794-TBN, 1794-TBNK(2)

Screw clamp, 16 I/O; 2 common; 2 +V NEMA-style

1794-TBNF

Screw clamp, fused NEMA-style

1794-TB37DS

D-shell

1794-TB62DS

264V AC/DC

A NEMA-style screw clamp terminal base for larger gauge wires with a cover for I/O wiring. Provides eight 5 x 20 mm fused, screw terminals with a cover for I/O wiring – shipped with fuses for the 1794-OA8 module; can be used to fuse the 1794-OM8 and 1794-OW8 modules with a replacement fuse.(3)

37 Pin; digital and analog, Module dependent

A 37-pin D-shell termination for both digital and analog modules.

62 Point;

A 62-pin D-shell termination for both digital and analog modules.

1794-TB62DSG

Grounded D-shell

62 Point; chassis ground

A grounded version of the 1794-TB62DS – for use with analog modules.

1794-TB62DST

D-shell

16 I/O; 18 common; 2 +V; 2 sets of CJC for temperature modules

A 62-pin D-shell termination to be used with the 1794-IT8 or 1794-IRT8 module (when used in thermocouple mode) – also provides chassis ground connections for analog modules.

(1) Isolation voltage, channel to channel, is determined by the insert module. Use this conductor category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1. (2) The letter K in the last position of the catalog number, before the series designation, indicates a conformal coated versions of standard modules and can be used with extended temperature modules (modules ending in -XT). (3) Contains eight 5 x 20 mm fuses (one for each even-numbered terminal – 0…14 on row B). Shipped with 1.6 A, 250V AC Slow Blow fuse suitable for the 1794-OA8 AC output module. Refer to individual installation instructions for fusing recommendations for other modules. Littlefuse PN23901.6 A-B PN94171304, SAN-O PNSD6-1.6A.

Publication 1794-SG002D-EN-P - May 2012

Page 16

Section

1.5

Select a FLEX I/O Power Supply

Step 4 – Select:

if power consumption exceeds the maximum for a single power supply, install additional power supplies FLEX I/O modules are interfaced to the I/O link through a FLEX I/O adapter module with a built-in 24V DC input power supply. The FLEX I/O modules receive power from the adapter/power supply through the backplane. The 120V AC to 24V DC power supply (1794-PS13 or 1794-PS3) is also available for powering the adapter/power supply.

General Specification Comparison Catalog

Power Supply Input Voltage, nom

Power Supply Apparent Input Input Power Power, max

Transformer Load, Output Current, Output Dimensions max max Voltage, nom (HxWxD), approx

1794-PS3

120V/220V AC

86 W

205 VA

250 VA

3.0 A

36 W

53 VA

90 VA

1.3 A

1794-PS13

24V DC

87 x 94 x 69 mm (3.4 x 3.7 x 2.7 in.) 87 x 69 x 69 mm (3.4 x 2.7 x 2.7 in.)

Power Supply Definitions Module Supply Voltage, This is typically either 120V AC or 24V DC nominal voltage that is supplied from an external power source wired to the module terminal base unit. All Flex I/O adapters provide internal power to the maximum possible number of 8 Flex I/O modules. Power supply modules are required to provide 24V to the adapters. The 1794-PS13 power supply is capable of supplying a maximum of 1.3 A at 24V DC. The output surge current is sufficient to drive four adapters with a surge of 23 A for 2 ms each operating at 24V DC. The 1794-PS3 power supply is capable of supplying a maximum of 3 A(1) at 24V DC. The output surge current is sufficient to drive six adapters with a surge of 23 A for 2 ms each operating at 24V DC. Non-Allen-Bradley DC power supplies can also be used, but should operate within the specifications for the devices they are powering. Size the power supply by calculating the total current consumed by summing the currents for each of the modules used for the power supply operating voltage applied. (1) This refers to horizontal mounting: 2.8 A maximum for all other mountings. Refer to the derating curve in the installation instructions for that module.

67

Publication 1794-SG002D-EN-P - May 2012

Page 17

68

Select a FLEX I/O Power Supply

The 1606 switched mode power supplies are capable of supplying a maximum of up to 40 A at 24V DC and can be used as an alternative when more power is needed. Digital Input Modules require supplied 24V DC (19.2…31.2V DC) and consume the currents listed in the module specifications. Digital Output Modules require supplied 24V DC (19.2…31.2V DC) and consume the currents listed in the module specifications plus the total current consumed by their loads. The load current is limited by the maximum load current and surge listed. Combination Digital Modules have a combination of inputs and outputs. The current load should be determined as described for the combined input and output specifications listed. Analog Input Modules require supplied 24V DC (19.2…31.2V DC) and consume the currents listed in the module specifications. In addition, adequate power must be supplied to the 1794-IE8 and 1794-IF4I transmitters to deliver input terminal voltage or drive 20 mA into the input impedance listed. This power source may be the same as the module power and can be included in the power supply calculated. Analog Output Modules require supplied 24V DC (19.2…31.2V DC) and consume the currents listed plus the total current consumed by their loads. The load current is limited by maximum current or resistive load permitted per channel. Combination Analog Modules have a combination of analog inputs and outputs. The current load should be determined as described previously for the combined modules and output specifications listed. The output load current is limited by the maximum current or resistive load permitted per channel. In addition, adequate power must be supplied to the 1794-IE8 and 1794-IF4I transmitters to deliver input terminal voltage or drive 20 mA into the input impedance listed. This power source may be the same as the module power and can be included in the power supply calculation. Counter Modules require module power, transmitter input power, and in some cases output load power. If output load power is required, use a separate power supply for output load power for noise immunity.

Power Requirements and Transformer Sizing • Use the real power value in watts for determining the amount of heat dissipation you will have inside the enclosure. • Use the apparent power value in VA for estimated power distribution sizing. • Use the transformer load value in VA of each power supply plus all other loads on a transformer to determine the required transformer size. Publication 1794-SG002D-EN-P - May 2012

Page 18

Select a FLEX I/O Power Supply

69

1794-PS3 AC/DC output current load real power (Watts apparent power (Watts)

transformer load (VS)

1794-PS13 AC/DC output current load (Amps) real power (Watts apparent power (Watts)

transformer load (VS) = real power (Watts) X 25

Publication 1794-SG002D-EN-P - May 2012