Page 9
Resistive Brake Module Installation Instructions
9
Ensure all fasteners are properly bonded to the subpanel. Refer to the System Design for Control of Electrical Noise Reference Manual (publication GMC-RM001x-EN-P) for HF bonding techniques. IMPORTANT
To improve the bond between the RBM and subpanel, construct your subpanel out of zinc plated (paint-free) steel.
3. Tighten all mounting fasteners. The minimum recommended torque for M6 (1/4 in. - 20) bolts is 1 Nm (9 in-lb).
Understanding RBM Connectors
RBMs have connectors and status indicators as listed in the following table: RBM Connectors or Indicators
2090-XB33-xx
2090-XB120-xx
TB1 - Drive Connection
X
X
TB2 - Motor Connection
X
X
TB3 - I/O Connection
X
X
TB4 - 230VAC Aux Power Connection
–
X
Status LED
X
–
24 VDC Status LED
–
X
230 VAC Status LED
–
X
Connectors and indicators locations are shown in Figure 6 on page 10 for the 2090-XB33-xx, and Figure 7 on page 10 for the 2090-XB120-xx.
Block diagrams of electrical functions are provided as Figure 8 on page 11 for the 2090-XB33-xx, and Figure 9 on page 12 for the 2090-XB120-xx.
Connector functions for the 2090-XB33-xx, and the 2090-XB120-xx are described in RBM Wiring Requirements on page 13.
Publication 2090-IN009F-EN-P, November 2004
Page 10
10
Resistive Brake Module Installation Instructions
Front view of 2090-XB33-xx Resistive Brake Module
Drive U-Phase Drive V-Phase Drive W-Phase Ground Motor U-Phase Motor V-Phase Motor W-Phase Ground
TS_21 TS_22 CONSTAT_41 CONSTAT_42 SHIELD COIL_A1 COIL_A2 SHIELD
Figure 6 2090-XB33-xx Resistive Brake Module Connectors and LED Indicator
TB3 - I/O Connection
Status LED TB1 - Drive Connection Power Cable Shield Clamps (2)
TB2 - Motor Connection
TB3 - I/O Connection
Drive U-Phase Drive V-Phase Drive W-Phase Ground Motor U-Phase Motor V-Phase Motor W-Phase Ground
TB4 - 230VAC Aux Power Connection
TS_21 TS_22 CONSTAT_41 CONSTAT_42 SHIELD COIL_A1 COIL_A2 SHIELD
Front view 2090-XB120-xx Resistive Brake Module
230 VAC L1 230 VAC L2
Figure 7 2090-XB120-xx Resistive Brake Module Connectors and LED Indicators
24 VDC Status LED 230 VAC Status LED
TB1 - Drive Connection TB2 - Motor Connection
Publication 2090-IN009F-EN-P, November 2004
Power Cable Shield Clamps (2)
Page 11
Resistive Brake Module Installation Instructions
11
This section provides wiring instructions for the Resistive Brake Module within a general drive system. Refer to Related Documentation on page 24 for installation and integration instructions containing wiring information specific to a drive system. In addition:
Wiring the RBM to a Drive System
ATTENTION
!
To comply with UL 508C, a Resistive Brake Module must be protected upstream by a 2.5 kV overvoltage control device. Kinetix and Ultra servo drives from Rockwell Automation meet this requirement. For additional drive applicability, please consult your Allen-Bradley representative.
Figure 1 on page 5 depicts suggested routing of RBM wiring within the dirty noise zone.
Figure 6 and Figure 7 on page 10 show connector locations and provides pinouts for each RBM connector.
Recommended wire sizes and torque values for I/O signal wires and power wires are provided in RBM Wiring Requirements on page 13 and in Specifications.
Figure 8 2090-XB33-xx Resistive Brake Module Block Diagram TB1 - Drive Connection Ground
4
W Drive V Drive
3
U Drive
1
TB2 - Motor Connection
100S-C23 CR1
2
1
2
3
4
5
6
11
12
21
22
31
32
41
42
A1
A2
4
Ground
3 2
W Motor V Motor
1
U Motor
Printed Circuit Board Status LED
TB3 - I/O D1
1 2 3 4 5 6 7 8
T1 (Fault)
TS_21 TS_22 CONSTAT_41 CONSTAT_42 SHIELD COIL_A1 COIL_A2 SHIELD
T2 (Warning)
Publication 2090-IN009F-EN-P, November 2004
Page 12
12
Resistive Brake Module Installation Instructions
Figure 9 2090-XB120-xx Resistive Brake Module Block Diagram TB1 - Drive Connection Ground W Drive V Drive U Drive
TB2 - Motor Connection
100S-C85 CR1
4 3 2 1
4
1
2
3
4
5
6
11
12
21
22
31
32
41
42
53
54
N/C
3 2 1
24VDC Status LED 230VAC Status LED Printed Circuit Board
N/C A1
A2
DC Interface Module E1 100-JE A1
E2
Ground W Motor V Motor U Motor
TB3 - I/O 1
T1 (Fault)
2 3 4 5 6 7 8
TS_21 TS_22 CONSTAT_41 CONSTAT_42 SHIELD COIL_A1 COIL_A2 SHIELD
TB4 - 230V ac T2 (Warning)
1 2
Publication 2090-IN009F-EN-P, November 2004
L1 L2
Page 13
Resistive Brake Module Installation Instructions
13
RBM Wiring Requirements Connects to: Connector
Drive Connection 1
Motor Connection 1
Terminal -Pin
Signal
Input/ Output
TB1-1
U Drive
–
TB1-2
V Drive
–
TB1-3
W Drive
–
TB1-4
2
–
TB2-1
U Motor
–
TB2-2
V Motor
–
TB2-3
W Motor
–
TB2-4
2
–
TB3-1
TS_21
In
TB3-2
TS_22
Out
TB3-3
CONSTAT_41
In
TB3-4
CONSTAT_42
Out
I/O Signals 5,6
Description and Usage
230/460V power input from drive
230/460V power output to motor
Insulation Strip Length mm (in.)
Torque Value Nm (lb-in.)
2090-XB33-xx 10.0 (0.375)
2090-XB33-xx: 0.5 - 0.6 (4.4 - 5.3)
2090-XB120-xx: 16.0 (0.63)
2090-XB120-xx: 2.5 - 2.9 (22.1 - 25.7)
2090-XB33-xx 10.0 (0.375)
2090-XB33-xx: 0.5 - 0.6 (4.4 - 5.3)
2090-XB120-xx: 16.0 (0.63)
2090-XB120-xx: 2.5 - 2.9 (22.1 - 25.7)
1.5 - 0.08 (16 - 28)
6.0 (0.25)
0.22 - 0.25 (1.9 - 2.2)
4.0 - 0.2 (10 - 24)
7.0 (0.28)
0.5 - 0.6 (4.4 - 5.3)
Minimum gauge for power cable is dependent on the motor/drive combination,
2090-XB33-xx 6 (10) maximum 2090-XB120-xx: 25 (3) maximum
RBM output with integral thermal warning Customer use of this auxiliary contact may include: • PLC or control string input that RBM is nearing its thermal limit RBM output of a normally closed contact (Closed = motor disconnected from drive) Customer use of this auxiliary contact may include: • PLC input connection, indicating RBM contactor status • Safety relay input for safety string • Part of RBM safety string for mechanical redundancy
TB3-5
SHIELD 3
–
I/O Shield internally terminated at chassis ground
TB3-6
COIL_A1
In
TB3-7
COIL_A2
Out
RBM contactor coil with integral thermal fault. Applying 24V Coil Power picks-up the contactor, which connects drive power to motor leads (i.e., motor rotates). Customer use may include: • Control from a safety relay output or signal relay output indicating system is clear for rotation
TB3-8
SHIELD 3
–
I/O Shield internally terminated at chassis ground
L1
–
L2
–
Auxiliary power input from external 230 VAC power source (2090-XB120-xx only)
230V Power 7 TB4-1 (2090-XB120-x TB4-2 x only)
Recommended Wire Size 4 mm2 (AWG)
1 Connectors are keyed to prevent misconnection of power interface cables to and from the RBM. 2 Ground connection for the motor cable passes through the drive and motor connectors. Cable shielding must be grounded to the chassis via the spring-loaded cable clamps. 3 I/O Shield terminations are connected internally to chassis ground. 4 Wire supplied by user should be stranded copper with 75° C (167° F) minimum rating. An earth ground connection is required for safe and proper operation. Local agency rules apply. 5 For additional contactor applications, refer to the Allen-Bradley Safety Product Catalog (Publication S114-CA001A-EN-P). 6 I/O is powered by an external 24V (22.4 - 26.4), 0.5A power supply. 7 Provided by an external 230V (207 - 253), 1A power supply.
Publication 2090-IN009F-EN-P, November 2004
Page 14
14
Resistive Brake Module Installation Instructions
Wiring Instructions 1. Allow five minutes for the power supplies to completely discharge before proceeding.
ATTENTION
!
To avoid hazard of electrical shock, verify that all voltage on the capacitors has been discharged before attempting to service, repair, or remove this unit. This product connects to stored energy devices. You should only attempt the procedures in this document if you are qualified to do so and familiar with solid-state control equipment and the safety procedures in publication NFPA 70E.
2. Separate the I/O signal cable and the power cables as shown in Figure 1 on page 5 and described below: I/O signal connections are at the top of the RBM (TB3). Power cable connections enter (TB1) and exit (TB2) at the bottom of the RBM. Auxiliary power connections (2090-XB120-xx only) are at the top of the RBM (TB4) IMPORTANT
To ensure correct wiring, verify connector orientation on the RBM before wiring each connector. Figure 6 and Figure 7 on page 10 show connector locations and pinouts.
3. Prepare your I/O signal wires by stripping the appropriate length of insulation from the end of the wire. Use caution not to nick, cut, or otherwise damage strands as you remove the insulation. Insert the wires into the TB3 terminal and torque the screws to the specified value. Gently pull on the wire to make sure it does not come out of its terminal. Re-insert and test any loose wires.
Publication 2090-IN009F-EN-P, November 2004
If RBM is:
Strip this length of insulation from the I/O wire:
2090-XB33-xx
6.0 mm (0.25 in.)
2090-XB120-xx
7.0 mm (0.28 in.)
Torque TB3 terminal screw within this range:
0.22 - 0.25 Nm (1.9 - 2.2 in-lbs)
Page 15
Resistive Brake Module Installation Instructions
15
4. Prepare your power cables as shown in Figure 10. by stripping the appropriate length of insulation from the end of the wire. Use caution not to nick, cut, or otherwise damage strands as you remove the insulation. Insert the wires into the proper terminal (TB1 or TB2) and torque the screws. Gently pull on the wire to make sure it does not come out of its terminal. Re-insert and test any loose wires.
If RBM is:
Strip this length of insulation from the power wire:
Torque TB1 or TB2 terminal screw within this range:
2090-XB33-xx
10.0 mm (0.375 in.)
0.5 - 0.6 Nm (4.4 - 5.3 lbs-in.)
2090-XB120-xx
16.0 mm (0.63 in.)
2.5 - 2.9 Nm (22.1 - 25.7 lbs-in.)
Figure 10 Shielded Power Cable Preparation 2090-XB33-xx Strip Length 10 mm (0.375 in.) 2090-XB120-xx Strip Length 16 mm (0.63 in.)
13
Outer Insulation 2
Motor Power Wires 3
Power Cable Exposed Braid 46 mm (1.8 in.)
2090-XB33-xx: 76 mm (3.0 in.) 2090-XB120-xx: 119 mm (4.7 in.) 2090-XB33-xx: 122 mm (4.8 in.) 2090-XB120-xx: 165 mm (6.5 in.)
5. Prepare your 230VAC auxiliary power cables (2090-XB120-xx only) by stripping the appropriate length of insulation from the end of the wire. Use caution not to nick, cut, or otherwise damage strands as you remove the insulation. Insert the wires into the TB4 terminal and torque the screws to the specified value. Pull on each wire to ensure it is secured to the terminal. Re-insert and test any loose wires.
If RBM is:
Strip this length of insulation from the I/O signal wire:
2090-XB33-xx
This terminal is not present
2090-XB120-xx
7.0 mm (0.28 in.)
Torque TB4 terminal screws within this range:
0.5 - 0.6 Nm (4.4 to 5.3 lbs-in.)
Publication 2090-IN009F-EN-P, November 2004
Page 16
16
Resistive Brake Module Installation Instructions
Applying the Power Cable Shield Clamp To apply your power cable shield clamp: 1. Use a small flat blade screwdriver to depress the spring loaded clamping plate as shown in Figure 11. Figure 11 Depressing the Spring Clamp Flat Blade Screwdriver 3.5 mm (0.14 in.) tip
Cable Clamp
Screwdriver tip in slot
2. Position the exposed portion of the cable braid directly in line with the clamp. 3. Release the spring, making sure the cable and cable braid are held secure by the clamp. 4. Attach tie wrap around cable and clamp, if additional strain relief is required (refer to Figure 12). Figure 12 Motor Cable and Clamp
Exposed Braid (under clamp) Cable Clamp
Tie Wrap
Outer Insulation
Publication 2090-IN009F-EN-P, November 2004
Motor Cable