Page 187
Appendix
A
Interconnect Diagrams
This appendix provides wiring examples and system block diagrams for your Kinetix® 6000 drive system components. Topic
Page
Interconnect Diagram Notes
188
Power Wiring Examples
189
Axis Module/Rotary Motor Wiring Examples
198
Axis Module/Linear Motor/Actuator Wiring Examples
207
Kinetix 6000M Integrated Drive-Motor Wiring Example
212
Controlling a Brake Example
213
System Block Diagrams
214
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
187
Page 188
Appendix A
Interconnect Diagrams
Interconnect Diagram Notes
This appendix provides wiring examples to assist you in wiring the Kinetix 6000 drive system. These notes apply to the wiring examples on the following pages.
Note
Information
1
For power wiring specifications, refer to Power Wiring Requirements on page 97.
2
For input fuse and circuit breaker sizes, refer to Circuit Breaker/Fuse Options on page 28.
3
Place AC (EMC) line filters as close to the drive as possible and do not route very dirty wires in wireway. If routing in wireway is unavoidable, use shielded cable with shields grounded to the drive chassis and filter case. For AC line filter specifications, refer to the Kinetix Motion Accessories Technical Data, publication KNX-TD004.
4
Terminal block is required to make connections.
5
2094-BCxx-Mxx-x (460V) IAM modules require a step-down transformer for single-phase control power input. Source the 2094-ACxx-Mxx-x (230V) IAM module control power from the three-phase input power (line-to-line) with neither leg bonded to ground or neutral potential. The National Electrical Code and local electrical codes take precedence over the values and methods provided. Implementation of these codes is the responsibility of the machine builder.
6
2094-ALxxS and 2094-BLxxS and 2094-XL75S-C2 LIM modules can supply input power for up to eight axes. 2094-XL75S-C1 LIM modules can supply input power for up to sixteen axes. For common-bus systems with more than sixteen axes, multiple LIM modules (or control power transformers) are required. For Kinetix 6000M systems, the control power current needs to be calculated and the LIM module needs to be sized.
7
2094-ALxxS, 2094-BLxxS, and 2094-XL75S-Cx LIM modules are capable of connecting to two IAM modules, providing each IAM module has its own line filter and the maximum current specification is not exceeded.
8
Contactor coil (M1) needs integrated surge suppressors for AC coil operation. Refer to the Kinetix Servo Drives Technical Data, publication KNX-TD003.
9
Drive Enable input must be opened when main power is removed, or a drive fault occurs. A delay of at least 1.0 second must be observed before attempting to enable the drive after main power is restored.
10
Cable shield clamp must be used to meet CE requirements. No external connection to ground is required.
11
Default configuration for jumper is for grounded power at user site. Ungrounded sites must jumper the bleeder resistor to prevent high electrostatic buildup. Refer to Determine the Input Power Configuration on page 85 for more information.
12
Leave jumper between PR2 and PR3 as shown to use the internal precharge resistor. Remove jumper when external precharge/circuit is required. For more information, refer to the 8720MC Regenerative Power Supply Installation Manual, publication 8720MC-RM001.
13
ATTENTION: Implementation of safety circuits and risk assessment is the responsibility of the machine builder. Please reference international standards EN 1050 and EN 954 estimation and safety performance categories. For more information refer to Understanding the Machinery Directive, publication SHB-900.
14
ATTENTION: Wiring the contactor enable relay is required. Refer to Contactor Enable Relay on page 70, for more information. The recommended minimum wire size for wiring the three-phase power enable control circuit to the contactor enable connector is 1.5 mm2 (16 AWG).
15
The Bulletin 2094 axis module referenced is either an individual axis module (catalog number 2094-xMxx-x) or the same axis module that resides within an integrated axis module (catalog number 2094-xCxx-Mxx-x).
16
For motor cable specifications, refer to the Kinetix Motion Accessories Technical Data, publication KNX-TD004.
17
Wire colors are for flying-lead cable and can vary from the premolded cable connectors.
18
Motor power cables (2090-XXNPMF-xxSxx and 2090-CPBM6DF-16AAxx) have a drain wire that must be folded back under the cable shield clamp.
19
MPL-A15xx…MPL-A45xx, MPM-A115xx…MPM-A130xx, MPF-A3xx…MPF-A45xx, MPS-Axxx, MPAR-Axxx, MPAS-Axxx (ballscrew), and MPAS-A/Bxxx (direct drive) encoders use the +5V DC supply.
20
MPL-Bxx, MPL-A5xx, MPM-Bxx, MPM-A165xx…MPM-A215xx, MPF-Bxx, MPF-A5xx, MPS-Bxxx, MPAR-Bxxx, and MPAS-Bxxx (ballscrew) encoders use the +9V DC supply.
21
Brake connector pins are labeled plus (+) and minus (-) or F and G respectively. Power connector pins are labeled U, V, W, and GND or A, B, C, and D respectively.
188
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 189
Interconnect Diagrams
Power Wiring Examples
Appendix A
These examples apply to power wiring configurations with and without the Bulletin 2094 line interface module (LIM), DC common bus wiring, and shunt module wiring. Figure 87 - Single IAM Module with 2094-AL09 or 2094-BL02 LIM Module 2094-ACxx-Mxx-x or 2094-BCxx-Mxx-x IAM Module
Refer to table on page 188 for note information.
Power Rail Ground Stud
Bonded Cabinet Ground Bus*
Note 10 Cable Shield Clamp 4
2094-AL09 or 2094-BL02 Line Interface Module Single-phase (CPL) Output 195…264V AC RMS Note 1
Motor Power (MP) Connector L2 L1
1
1
2
2 1 2
VAC LINE Three-phase (IPL) Input 195…264V AC RMS or 324…528V AC RMS Note 1
L3 L2 L1
Ground VAC LOAD Three-phase (OPL) Output 195…264V AC RMS or 324…528V AC RMS Note 1
CTRL 2 CTRL 1
4 5
L2'
6
L1'
Three-phase Motor Power Connections Note 16
3 2 1
DC-
DC Bus and Three-phase Input (IPD) Connector
DC+
3 L3'
Control Power (CPD) Connector
W V U
L3 L2 L1
Input Fusing * MBRK_PWR
24V DC Output (PSL) Connector
MBRK_COM MBRK_PWR MBRK_COM
1 2 3 4 MBRK MBRK +
Motor/Resistive Brake (BC) Connector IO_PWR
I/O (IOL) Connector Notes 13, 14
24-26
IO_COM COIL_A2
PWR DBRK DBRK +
STOP * COIL_A1
COM
6
BR-
5
BR+
Motor Brake Connections
4 3 2
BR-
1
BR+
Resistive Brake Connections
13 20-22
1
4
2
CONT ENCONT EN+
Contactor Enable (CED) Connector Note 14
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
* Indicates User Supplied Component
189
Page 190
Appendix A
Interconnect Diagrams
Figure 88 - Multiple IAM Module with LIM Module 2094-ACxx-Mxx-x or 2094-BCxx-Mxx-x IAM Module (IAM_1)
Refer to table on page 188 for note information.
Bonded Cabinet Ground Bus*
Note 10
Power Rail Ground Stud
Cable Shield Clamp
2094-ALxxS, 2094-BLxxS, or 2094-XL75S-Cx Line Interface Module
4
Control Power CTRL 2 Single-phase (CPL) Output 195…264V AC RMS CTRL 1 Note 1
1
Note 4
1 2
2
2
VAC LINE Three-phase (IPL) Input 195…264V AC RMS or 324…528V AC RMS Note 1
2 3 4
L3 L2 L1
VAC LOAD Three-phase (OPL) Output 195…264V AC RMS or 324…528V AC RMS Note 1
1 L3' L2' L1'
CTRL 2 CTRL 1
Control Power (CPD) Connector
Three-phase Motor Power Connections Note 16
3 2 1
To CPD Connector IAM_2 Notes 6, 7 1
1
W V U
Motor Power (MP) Connector
Note 4
2
3
Three-phase AC Line Filter Note 3
3 4
DCDC+
4 5 6
L3 L2
DC Bus and Three-phase Input (IPD) Connector
L1
To IPD Connector IAM_2 Note 7 Auxiliary Power 1 Single-phase (APL) Input 2 93…121V AC RMS or 196…253V AC RMS (this connector is present only on catalog number 2094-XL75S-Cx) Note 1
L1 L2/N
IO_PWR2 IO_COM2
24V DC (P1L) Output
IO_PWR2 IO_COM2 IO_PWR2 IO_COM2
1 2 3
To BC Connector IAM_2 Note 7
4 5 6
Motor Brake Connections MBRK MBRK +
Motor/Resistive Brake (BC) Connector IO_PWR1
1, 3, 5
COM PWR DBRK DBRK +
I/O (IOL) Connector Notes 13, 14
STOP * COIL_E1 IO_COM1 COIL_E2
* Indicates User Supplied Component
190
6
BR-
5
BR+
4 3 2
BR-
1
BR+
Resistive Brake Connections
7 2, 4, 6
1
8
2
CONT ENCONT EN+
Contactor Enable (CED) Connector Note 14
To CED Connector IAM_2 Note 7
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 191
Interconnect Diagrams
Appendix A
Figure 95 - Multiple IAM Module with LIM Module (continued) 2094-ACxx-Mxx-x or 2094-BCxx-Mxx-x IAM Module (IAM_2)
Refer to table on page 188 for note information.
Power Rail Ground Stud
Bonded Cabinet Ground Bus*
Note 10 Cable Shield Clamp 4
W V
Motor Power (MP) Connector 1
From CPL connector, LIM
2
1 2
CTRL 2 CTRL 1
DCDC+
3
From OPL connector, LIM
Three-phase AC Line Filter Note 3
4 5 6
L3 L2
U
Control Power (CPD) Connector
Motor/Resistive Brake (BC) Connector
COM PWR DBRK DBRK +
2
1
L1
MBRK +
1
2
DC Bus and Three-phase Input (IPD) Connector
MBRK -
From IOL connector, LIM and CED connector, IAM_1
Three-phase Motor Power Connections Note 16
3
CONT ENCONT EN+
6
BR-
5
BR+
Motor Brake Connections
4
From P1L connector, LIM
3 2
BR-
1
BR+
Resistive Brake Connections
Contactor Enable (CED) Connector Note 14
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
191
Page 192
Appendix A
Interconnect Diagrams
This configuration does not include a LIM module. You must supply input power components. The single-phase and three-phase line filters are wired downstream of fusing and the M1 contactor. ATTENTION: Wiring the contactor enable (CED) relay is required. To avoid injury or damage to the drive, wire the contactor enable relay into your control string. Refer to Contactor Enable Relay on page 70 for more information. Figure 89 - IAM Module (without LIM module) 2094-ACxx-Mxx-x or 2094-BCxx-Mxx-x IAM Module
Refer to table on page 188 for note information.
Bonded Cabinet Ground Bus *
Power Rail Ground Stud
Chassis Single-phase AC Line Filter Note 3
Single-phase Input 95…264V AC RMS Notes 1, 2
Input Fusing *
1 2
CTRL 2 CTRL 1
Control Power (CPD) Connector
Note 10 Cable Shield Clamp
Step-down Transformer * Note 5
4
Motor Power (MP) Connector 1 2
Note 4
DCDC+
3
Three-phase AC Line Filter Note 3
Three-phase Input 195…264V AC RMS or 324…528V AC RMS Notes 1, 2 Input Fusing *
4 5 6
L3 L2
DC Bus and Three-phase Input (IPD) Connector
MBRK MBRK +
Motor/Resistive Brake (BC) Connector
COM PWR DBRK -
Notes 8, 14
1 2
24V AC/DC or 120V AC 50/60 Hz
STOP *
START *
CR1 * M1 *
CONT ENCONT EN+
Contactor Enable (CED) Connector Note 14
CR1 * CR1 * Refer to Attention statement (Note 13).
192
V U
L1
M1 * Notes 8, 9
W
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
DBRK +
Three-phase Motor Power Connections Note 16
3 2 1
6
BR-
5
BR+
4
Motor Brake Connections User Supplied 24V DC
3 2
BR-
1
BR+
Resistive Brake Connections
Ground Jumper Note 11 * Indicates User Supplied Component
Page 193
Three-phase Input from LIM or Input Power Contactor (M1) 195…264V AC RMS or 324…528V AC RMS Notes 1, 2, 7, 8
Single-phase Input 95…264V AC RMS Notes 1, 2
Bonded Cabinet Ground Bus*
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017 2
1
6
5
4
DC Bus and Three-phase Input (IPD) Connector
Note 10
Contactor Enable (CED) Connector Note 14
DBRK +
DBRK -
PWR
COM
MBRK +
MBRK -
Motor Power (MP) Connector
Cable Shield Clamp Control Power (CPD) Connector
Motor/Resistive Brake (BC) Connector
CONT ENCONT EN+
L1
L2
L3
DC+
2 3
DC-
CTRL 2 CTRL 1
1
2
1
Power Rail Ground Stud
2094-ACxx-Mxx-x or 2094-BCxx-Mxx-x Common-bus Leader IAM Module
U
W V
Wire the leader and follower IAM contactor enable terminals in series with the control string or LIM I/O.
1
2
6
5
4
1
N.C.
N.C. N.C.
2
Three-phase Motor Power Connections Note 16
DC Bus and Three-phase Input (IPD) Connector
Note 10
Refer to table on page 188 for note information.
* Indicates User Supplied Component
Contactor Enable (CED) Connector Note 14
DBRK +
DBRK -
PWR
COM
MBRK +
MBRK -
Motor Power (MP) Connector
Cable Shield Clamp Control Power (CPD) Connector
Motor/Resistive Brake (BC) Connector
CONT ENCONT EN+
L1
L2
L3
DC+
2 3
DC-
CTRL 2 CTRL 1
Power Rail Ground Stud
1
2
1
3
4
5
6
1
2
3
4
Bonded Cabinet Ground Bus*
2094-ACxx-Mxx-x or 2094-BCxx-Mxx-x Common-bus Follower IAM Module
W V U
1
2
3
4
5
6
1
2
3
4
Three-phase Motor Power Connections Note 16
Interconnect Diagrams Appendix A
DC Common Bus Wiring Examples
Figure 90 - Leader IAM Module with Single Follower IAM Module
193
Page 194
Appendix A
Interconnect Diagrams
Figure 91 - Leader IAM Module with Multiple Follower IAM Modules
To Follower DC Bus Connections Refer to table on page 188 for note information. To Follower Control Power Connections
2094-ACxx-Mxx-x or 2094-BCxx-Mxx-x Common-bus Leader IAM Module
Bonded Cabinet Ground Bus *
Power Rail Ground Stud Cable Shield Clamp Single-phase Input 95…264V AC RMS Notes 1, 2
1 2
Note 10 CTRL 2 CTRL 1
Control Power (CPD) Connector
4
Note 4 1 2
DC+
3
Three-phase Input from LIM or Input Power Contactor (M1) 195…264V AC RMS or 324…528V AC RMS Notes 1, 2, 7, 8
4 5 6
Motor Power (MP) Connector
DC-
L3 L2
DC Bus and Three-phase Input (IPD) Connector
U
L1
MBRK MBRK + COM
Motor/Resistive Brake (BC) Connector
PWR DBRK DBRK +
1 2
CONT ENCONT EN+
W V
3 2 1
Three-phase Motor Power Connections Note 16
6 5 4 3 2 1
Contactor Enable (CED) Connector Note 14
To Follower Control Circuit Connections Wire the leader and follower IAM contactor enable terminals in series with the control string or LIM I/O.
194
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 195
Interconnect Diagrams
Appendix A
Figure 98 - Leader IAM Module with Multiple Follower IAM Modules (continued)
2094-ACxx-Mxx-x or 2094-BCxx-Mxx-x Common-bus Follower IAM Module
Refer to table on page 188 for note information. Bonded Cabinet Ground Bus *
Power Rail Ground Stud Cable Shield Clamp Note 4 From Leader Control Power Connections
1 2
CTRL 1
Note 4 1
From Leader DC Bus Connections
2
DC Bus Fusing * Note 2
DC Bus and Three-phase Input (IPD) Connector
DC+
N.C. N.C. N.C.
5 6
L3 L2
4
Motor Power (MP) Connector
DC-
3 4
Note 10
Control Power (CPD) Connector
CTRL 2
L1
W V U
4
COM
3
PWR
2
DBRK -
1
DBRK +
2
1
Three-phase Motor Power Connections Note 16
5
MBRK +
1
2
6
MBRK -
Motor/Resistive Brake (BC) Connector
3
Contactor Enable (CED) Connector Note 14
CONT ENCONT EN+
2094-ACxx-Mxx-x or 2094-BCxx-Mxx-x Common-bus Follower IAM Module
Bonded Cabinet Ground Bus *
Power Rail Ground Stud Cable Shield Clamp 1 2 1 2
DC Bus Fusing * Note 2
Note 10
DC+
4 5 6
L3 L2
4
Motor Power (MP) Connector
DC-
3 N.C. N.C. N.C.
Control Power (CPD) Connector
CTRL 2 CTRL 1
DC Bus and Three-phase Input (IPD) Connector
L1
MBRK MBRK +
Motor/Resistive Brake (BC) Connector
COM PWR DBRK DBRK +
From Leader Control Circuit Connections
1 2
CONT ENCONT EN+
W V U
3 2 1
Three-phase Motor Power Connections Note 16
6 5 4 3 2 1
Contactor Enable (CED) Connector Note 14
* Indicates User Supplied Component
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
195
Page 196
196
Three-phase AC Line Filter Note 3
R
S
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
IMPORTANT
Customer Supplied 120V AC
MC * Note 8
E/N
Bonded Cabinet Ground Bus *
MC
Note 12
Line Reactors
MC2
MC1
PR3
CR1*
Note 14
Start *
Refer to Attention statement (Note 13).
Stop *
CR1*
2
Contactor Enable (CED) Connector Note 14
Motor/Resistive Brake (BC) Connector
CONT ENCONT EN+
I/O (IOD) Connector
Note 10
DBRK +
DBRK -
PWR
COM
MBRK +
MBRK -
Motor Power (MP) Connector
Cable Shield Clamp Control Power (CPD) Connector
DC Bus and Three-phase Input (IPD) Connector
+24V_PWR ENABLE
L1
L2
L3
DC+
DC-
CTRL 2 CTRL 1
Power Rail Ground Stud
3 +24V_COM
2
1
6
5
1
+24V DC PWR
Motion Control I/O
N.C. N.C. N.C.
4
3
2
1
2
1
PR2
L3 AUX
T1
COM RDY
Set 8720MC-RPS for 650V DC, nom
P
N
Single-phase Input 95…264V AC RMS Notes 1, 2
Bonded Cabinet Ground Bus*
PR1
L2 AUX
S1
L3
R1
DCDC+
L2
TB3
TB1
L1
TB1
TB2 L1 AUX
T
S
R
G
8720MC-RPSxxx 8720MC Regenerative Power Supply
2094-BCxx-Mxx-x Common-bus Follower IAM Module
W V U
1
2
3
4
5
6
1
2
3
4
Three-phase Motor Power Connections Note 16
Use a push button circuit (instead of an SPST toggle switch) in series with the contactor enable string (between the 8720MC-RPS and servo drive) to allow a drive fault to remove the DC bus power, and to prevent the drive from applying DC bus power without your input after clearing a drive fault.
Refer to table on page 188 for note information.
* Indicates User Supplied Component
T
Harmonic Filter
To Motor Fan
Varistor
Motor Fan Fusing *
Input Fusing *
Three phase Input (+10/ 15%) 380V AC rms, 50 Hz or 460V AC rms, 60 Hz Notes 1, 2
Appendix A Interconnect Diagrams
Figure 92 - 8720MC-RPS Leader Drive with Single Follower IAM Module