Page 259

Appendix

F

Enhanced Peak Performance

This appendix provides procedures and information, specific to Kinetix® 6000 drive systems, for enabling the peak enhancement feature in each drive.

Before You Begin

Topic

Page

Before You Begin

259

Enhanced Peak Example

261

Change the Drive Parameter

266

The peak current ratings of the Kinetix 6000 460V drives (series A, B, and C) are configured at the factory as 150% of continuous current. However, you can program 460V (series B and C) AM modules and the equivalent IAM (inverter) modules, for up to 250% of continuous inverter current. To achieve the enhanced peak performance, you must determine the values of maximum acceleration, deceleration, and torque. This feature is present only in the Kinetix 6000 (series B and C) drives listed in Table 131. Table 131 - Kinetix 6000 Series Change IAM Module Cat. No.

AM Module Cat. No.

Peak Current Rating Series A (inverter)

Series B and C (inverter)

2094-BC01-MP5-S

2094-BMP5-S

150%

250%

2094-BC01-M01-S

2094-BM01-S

150%

250%

2094-BC02-M02-S

2094-BM02-S

150%

250%

2094-BC04-M03-S

2094-BM03-S

150%

250%

2094-BC07-M05-S

2094-BM05-S

150%

200%

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

259

Page 260

Appendix F

Enhanced Peak Performance

The default values that populate the AXIS_SERVO_DRIVE properties in the Logix Designer application are calculated for each motor and drive, but assume 150% peak torque in those calculations. For the drive to command more current, you must enter new values for some of those parameters, including the following: • TorqueLimitBipolar • TorqueLimitPositive • TorqueLimitNegative • MaximumAcceleration • MaximumDeceleration • AccelerationLimitBipolar • AccelerationLimitPositive • AccelerationLimitNegative You can access these parameters offline in the Logix Designer application Axis Properties tabs or online as sent to the drive in an SSV instruction. To calculate the new values, you also need to determine these values: • Drive electrical data (Motion Analyzer solution page, under Drive tab) • Motor electrical data (Motion Analyzer solution page, under Motor tab) • TorqueScaling (the Logix Designer application, Axis Properties, Output tab) Figure 122 - Drive and Motor Data in Motion Analyzer Software

IMPORTANT

260

The default unit in Motion Analyzer software for drive and motor current is A (0-pk). Because the example formula is in A (RMS), you must change the units in the Drive and Motor tabs to A (RMS). Pause your mouse over A (0-pk) and use the pull-down menu to change the units to A (RMS). Refer to Figure 122 for an example.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 261

Enhanced Peak Performance

Appendix F

In this example, the following motor and drive combination is used: • Drive = 2094-BC02-M02-S • Motor = MPL-B540K

Enhanced Peak Example

Table 132 - Example Definitions Description

Symbol

IDN

Example

Motor continuous current (Arms)

Imtr, cont

S:0:0111

14.49525

Motor peak current (Arms)

Imtr, pk

S:0:0109

42.42641

Drive continuous current (Arms)

Idr, cont

S:0:0112

10.3379

Drive peak current (Arms)

Idr, pk

S:0:0110

150%: 15.5069 250%: 25.8094

Figure 123 - Example Torque Formula

Torque max = min (I mtr, pk , I dr, pk ) I mtr, cont

= min (42.4 A rms , 25.8 A rms ) 14.5 A rms

= 178.1%

1. Navigate to Axis Properties and click the Limits tab.

Default Peak Torque Limit Value

2. Overwrite the existing Peak Torque Limit (TorqueLimitBipolar) value. In this example, the calculated value is 178.1. 3. Click Set Custom Limits.

Default TorqueLimit Values

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

261

Page 262

Appendix F

Enhanced Peak Performance

4. Overwrite the existing TorqueLimitPositive and TorqueLimitNegative values. In this example, the calculated values are 178.1 and -178.1 (respectively). The calculated value for Torquemax is the maximum value for the following: • TorqueLimitBipolar • TorqueLimitPositive (+) • TorqueLimitNegative (-) If you want to limit the torque, adjust the calculated values to a value closer to zero. The values shown are the default values for 150% peak torque with this motor and drive pair. TIP

For more information on system configuration with your Logix5000 controller and the Logix Designer application, refer to page 135.

5. Click the Output tab.

Default LoadInertiaRatio Value

Default TorqueScaling Value

The TorqueScaling and LoadInertiaRatio values are populated after an autotune. If an autotune is not possible, model the system in Motion Analyzer software and enter that value for the LoadInertiaRatio. The default value for the LoadInertiaRatio is 0.0, however for this example, a ratio of 10.20:1 is used (load inertia = 0.015 Kg-m^2). IMPORTANT

To obtain more accurate results, performing Autotune in the Logix Designer application is recommended.

To calculate the maximum acceleration and deceleration from Torquemax, use this equation. Accel max = Torque max

TIP

262

100 TorqueScaling

If autotune cannot be performed, enter the data for the LoadInertiaRatio, DriveResolution, and ConversionConstant as shown in step 5 through step 9.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 263

Enhanced Peak Performance

Appendix F

6. Change the Load Inertia Ratio value to 10.2. 7. Click Apply. The TorqueScaling values update.

Modified Load Inertia Ratio Value

New TorqueScaling value used in this example.

8. Click the Drive/Motor tab.

DriveResolution value used in this example.

The values for DriveResolution and ConversionConstant start out populated with default values, but can be changed for your specific needs. If you plan to change those values, enter the new values into the dialog boxes. Otherwise, use the defaults. 9. Click the Conversion tab.

ConversionConstant value used in this example.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

263

Page 264

Appendix F

Enhanced Peak Performance

Enhanced Peak Example Calculation Based on the values shown, this is the sample calculation. Accel max = 1.781

100 0.53308904 % rated

= 334.09 PU/s 2

PU/s 2

To provide safe headroom, this value needs to be reduced by 15% before being written to the controller. This is the sample calculation.

MaximumAcceleration = MaximumDeceleration = 0.85 • Accelmax = 283.98 PU/s 2 1. Click the Dynamics tab.

Default Acceleration and Deceleration Values

2. Overwrite the existing Maximum Acceleration and Maximum Deceleration values. In this example, the calculated values are 283.98 for each. 3. Click Calculate for the Maximum Acceleration Jerk and Maximum Deceleration Jerk fields to automatically calculate new values. 4. Adjust the new jerk values for your specific application needs. Setting the values for AccelerationLimitBipolar, AccelerationLimitPositive, and AccelerationLimitNegative requires one more calculation by using this formula.

AccelerationLimitBipolar = AccelerationLimitPositive = -AccelerationLimitNegative AccelerationLimitBipolar = 2 • MaximumAcceleration = 668.18 PU/s 2 0.85 5. Click the Limits tab.

264

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 265

Enhanced Peak Performance

Appendix F

6. Click Set Custom Limits.

Default AccelerationLimitBipolar Value

Default AccelerationLimitPositive and AccelerationLimitNegative Values

7. Overwrite the existing AccelerationLimitBipolar value. In this example, the calculated value is 668.18. 8. Overwrite the existing AccelerationLimitPositive and AccelerationLimitNegative values. In this example, the calculated values are +668.18 and -668.18 (respectively). 9. Repeat this process for each IAM and AM module in your system.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

265

Page 266

Appendix F

Enhanced Peak Performance

Change the Drive Parameter

Before the drive is capable of accepting a command for the new peak current ratings, you need to change a drive parameter. This needs to be done only once, and there are two methods to perform the task. IMPORTANT

The Sercos IDN method that uses the Logix Designer application supports automatic drive replacement (ADR).

Sercos IDN Write Instruction The Sercos IDN write instruction is accomplished by using the Logix Designer application. Refer to Appendix E on page 253 for more information on changing IDN parameter values by using this method. 1. On initialization of the drive, read the INT value of the configuration of the drive at Sercos IDN P:0:7.

2. If the value of bit zero is zero, latch it and write the new value back to the drive at the same address, again as type INT.

266

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 267

Enhanced Peak Performance

Appendix F

3. Verify change with another Sercos IDN Read Message from IDN P:0:7 and examine bit zero. Refer to this Logix Designer application example.

DriveExplorer Software To use DriveExplorer™ software to change IDN parameter values, you must also have the 1203-SSS Serial to SCANport™ adapter. Refer to Appendix C on page 227 for more information on changing IDN parameter values by using this method. 1. Connect a 1203-SSS Serial to SCANport adapter to the drive by using DriveExplorer software. 2. Change parameter P507 [Drv Peak Rating] from 150% to 250% (or 200% if applicable). 3. Save device values to nonvolatile memory.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

267

Page 268

Appendix F

Enhanced Peak Performance

Notes:

268

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017