Kinetix 6000 Multi-axis Servo Drives User Manual: AppE - Changing the Default IDN Parameter Values
Pages 253 to 258 of 290, from Kinetix 6000 Multi-axis Servo Drives User Manual
The original document is the PDF (21 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 2094-BM01 and Allen-Bradley 2094-PRF
Page 253
Appendix
E
Changing the Default IDN Parameter Values
This appendix provides a procedure, specific to the Kinetix® 6000 (Sercos) drive systems, for changing IDN parameter values to non-default values when your application does not match the default configuration. The procedure also applies when one or more Kinetix 6000M IDM systems are present.
Before You Begin
Topic
Page
Before You Begin
253
Change IDN Parameter Values
254
The Logix5000™ processor contains a motion planner that sends real-time and non real-time data to the drive. This drive communication is performed via a set of Sercos interface telegrams. Each telegram has an identification or Ident (IDN) number. All parametric data, such as scaling and loop gains, and realtime loop closure information is configured this way. Table 130 - IDN Instruction Format in the IEC Standard Document Name IDN Number
Function/Description Length in bytes
Minimum input value/ Maximum input value
Scaling/resolution
Units
There are default parameters in the Logix5000-to-Kinetix 6000 drive product structure you can reconfigure when the default configuration does not match the Integrated Architecture™ machine configuration. By using this procedure, you can change the Additional Bus Capacitance value in common-bus configurations. TIP
You can also set the Additional Bus Capacitance parameter by using DriveExplorer™ software (refer to Appendix C), the Logix Designer application, or RSLogix 5000® software, version 20.00 or later, from I/O configuration>Sercos module>Drive module properties>Power tab (refer to Chapter 6).
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
253
Page 254
Appendix E
Changing the Default IDN Parameter Values
Use this flowchart to determine if changing your default configuration is required. Figure 121 - Configuration Flowchart Start
Read the present IDN default parameter value by using the Sercos IDN Read instruction. page 254
Calculate the correct IDN value for your application. page 256
No
Change the IDN parameter value by using the Sercos IDN Write instruction.
Does the calculated IDN value match the IDN Read instruction value?
Yes
Parameters are already set correctly. You do not need to change IDN parameter values.
page 257
Change IDN Parameter Values
In this section you follow the Configuration Flowchart on page 254 to determine if you need to use the Sercos IDN Write instruction in the Logix Designer application to change the IDN parameter values.
Read the Present IDN Parameter Value Follow these steps to read the present IDN value. 1. Start your Logix Designer application program. 2. Configure a Message Configuration (MSG) instruction to read your present IDN parameter values.
254
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 255
Changing the Default IDN Parameter Values
Appendix E
In this example, the Message Configuration (MSG) instruction is set to read the additional bus capacitance of your leader IAM power module.
a. From the Message Type pull-down menu, choose Sercos IDN Read. b. From the Identification Number pull-down menus, choose P-0-99. 3. Click New Tag. 4. The New Tag dialog box opens.
5. Type the name of your Destination tag. In this example, the tag name is Read_Value. 6. Click OK. In this example, the MSG instruction reads the P-0-99 IDN value and places it in the destination as specified by the new tag. 7. Click the Communication tab.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
255
Page 256
Appendix E
Changing the Default IDN Parameter Values
8. Click Browse.
9. Select the Bulletin 2094 module to read the MSG instruction. 10. Click OK.
Calculate the New IDN Value Changing the additional bus capacitance value requires calculations. Determine the sum of all capacitance values for the follower IAM module, each AM module, and each IPIM module on the follower IAM power rail. Refer to Calculate Additional Bus Capacitance on page 229 for more information.
256
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 257
Changing the Default IDN Parameter Values
Appendix E
Write the New IDN Parameter Value Follow these steps to write the new IDN parameter value. 1. Configure a Message Configuration (MSG) instruction to write the IDN parameter value required for your application. In this example, the Message Configuration (MSG) instruction is set to write the additional bus capacitance of your leader IAM power module.
a. From the Message Type pull-down menu, choose Sercos IDN Write. b. From the Identification Number pull-down menus, choose P-0-99. 2. Click New Tag. 3. The New Tag dialog box opens.
4. Type the name of your Source tag. In this example, the tag name is Write_Value. 5. Click OK. In this example, the new tag creates a source value (that you entered) that the MSG instruction uses to overwrite the existing P-0-099 IDN value. Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
257
Page 258
Appendix E
Changing the Default IDN Parameter Values
6. Click the Communication tab. The Communication tab opens.
7. Click Browse. 8. Select your Bulletin 2094 module. 9. Click OK. The MSG instruction writes the new IDN value to your drive. TIP
To verify your Sercos IDN Write instruction was successful, you can perform another Sercos IDN Read instruction for the IDN in question.
10. Click OK to close the Message Configuration dialog box.
258