Configure the Load Observer Feature
Appendix D
2. Click the Output tab in the Axis Properties dialog box and verify that the Load Inertia Ratio > 0.
3. Click the Gains tab in the Axis Properties dialog box. The current Position and Velocity gain values are used to recalculate other gain values.
4. Determine if the mechanical load connected to the motor is rigid or compliant. • Rigid systems typically involve high-performance load mechanics that are tightly coupled directly to the motor shaft and there is no lost motion. Refer to Rigid Mechanical Loads on page 245, for rigid applications. • Everything else is compliant, including systems with belts and pulleys, long shafts, short shafts with heavy loads, and couplings and gearboxes with backlash and/or lost motion. Refer to Compliant Mechanical Loads on page 246, for compliant applications.
Rigid Mechanical Loads Follow these steps if the load is rigid. 1. Calculate the Load Observer Bandwidth. Load Observer Bandwidth: Kop = Velocity Proportional Gain 1 4z 2 K pp
K vp
K op
2
0, K pi
1 4z 2
1
T bw
2
K pp 4000
0, K vi
K vp 4000
0 K oi
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
245
Page 246
Appendix D
Configure the Load Observer Feature
2. Configure these IDN parameter values. a. IDN P-431 = 2 (Load Observer with Velocity Estimate) b. IDN P-432 = Kop c. IDN P-433 = 0 d. IDN P-065 = 1
3. If the Low-pass Output Filter is enabled, verify that the Low-pass Output Filter Bandwidth is ≥ the Velocity Proportional Gain x 2/(2pi). Sercos IDN P-065 has an impact on how the Low-pass Output Filter functions. Refer to Torque Low-pass Filter Bandwidth on page 241 for more information. 4. Refer to Compensate for High Frequency Resonances on page 251, to tune-out resonant frequencies.
Compliant Mechanical Loads The compliant setting reduces all of the gains by a factor of (Load Inertia Ratio +1) and then calculates the Load Observer Bandwidth. Typically, this reduction is too conservative, making the loop response sluggish and the error too large. However, it does assure stability. Follow these steps if the load is compliant. 1. Make the following calculations to de-tune all gains by a factor of the (Load Inertia Ratio + 1): a. Position Loop Bandwidth: Kpp = Position Proportional Gain/(Load Inertia Ratio + 1) b. Position Integral Bandwidth: Kpi = Position Integral Gain/(Load Inertia Ratio + 1)2 c. Velocity Loop Bandwidth: Kvp = Velocity Proportional Gain/(Load Inertia Ratio + 1) d. Velocity Integral Bandwidth: Kvi = Velocity Integral Gain/(Load Inertia Ratio + 1)2 e. Load Observer Bandwidth: Kop = Kvp 1 4z 2 K pp
K vp 0,
246
T bw
K op
2
K pi
1 4z 2 (R+1)
1 2
K pp 4000
0, K vi
K vp 4000
0 K oi
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 247
Configure the Load Observer Feature
Appendix D
2. Configure these settings and values on the Gains tab. a. Set the Position Proportional Gain = Kpp b. Position Integral gain = Kpi c. Velocity Proportional Gain = Kvp d. Velocity Integral Gain = Kvi
To manually increase the gains by some factor to optimize the response, refer to Manual Tuning for Further Optimization on page 248. 3. Configure these IDN parameter values. a. IDN P-431 = 2 (Load Observer with Velocity Estimate) b. IDN P-432 = Kop c. IDN P-433 = 0 d. IDN P-065 = 1
4. If the Low-pass Output Filter is enabled, verify that the Low-pass Output Filter Bandwidth ≥ Velocity Proportional Gain x 5/(2pi). Sercos IDN P-065 has an impact on how the Low-pass Output Filter functions. Refer to Torque Low-pass Filter Bandwidth on page 241 for more information. 5. Refer to Compensate for High Frequency Resonances on page 251, to tune-out resonant frequencies.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
247
Page 248
Appendix D
Configure the Load Observer Feature
Tuning Mode Summary This table summarizes the primary difference between the two tuning modes. Table 129 - Tuning Mode Comparison Tuning Mode
Description
Out-of-box or unknown load Load Inertia Ratio = 0
Load Observer Bandwidth Kop = 4 times the new Velocity Proportional Gain, Kvp
Auto-tuning or known load Load Inertia Ratio > 0
Load Observer Bandwidth = Velocity Proportional Gain
Manual Tuning for Further Optimization The out-of-box and auto-tune rigid methods achieve relatively high performance. However, the manual tuning method can help to optimize performance for the auto-tune compliant method, or if every ounce of performance is required. It involves incrementally increasing controller gains to the point of marginal stability, then backing them off by a given percentage. Typical ranges for various gains are also given to provide guidelines. Follow these steps to manually tune your drive. 1. Select a factor (N) that you can incrementally increase the gains by in an iterative process, for example, 1.5>N>2. 2. Create a trend to monitor Torque Reference. 3. Manually tune the velocity loop. a. Make note of the Position and Feedforward Gains. You must change them temporarily to isolate the velocity loop and later restore them to the original values. b. Isolate the velocity loop. • Zero out the Position Proportional Gain, Position Integral Gain, and Acceleration Feedforward Gain • Set the Velocity Feedforward = 100 c. While Jogging the axis and monitoring the Torque Reference trend, incrementally increase the following gains simultaneously and stop when the Torque Reference begins to become oscillatory or unstable: • Low-pass Output Filter Bandwidth = Low-pass Output Filter Bandwidth x N • Load Observer Proportional Gain = Load Observer Proportional Gain x N • Load Observer Integral Gain = Load Observer Integral Gain x N • Velocity Proportional Gain = Velocity Proportional Gain x N • Velocity Integral Gain = Velocity Integral Gain x N2
248
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 249
Configure the Load Observer Feature
Appendix D d. Decrease the gains by using the previous equations with N = 0.5. A typical range of values for various integral gains are given: • 0 ≤ Load Observer Integral Gain ≤ Load Observer Proportional Gain/4 • 0 ≤ Velocity Integral Gain ≤ Velocity Proportional Gain2/4000 e. If the Low-pass Output Filter is enabled, a typical range of values for the Low-pass Output Filter Bandwidth are given: • Rigid: Low-pass Output Filter Bandwidth ≥ Velocity Proportional Gain x 2/(2pi) • Compliant: Low-pass Output Filter Bandwidth ≥ Velocity Proportional Gain x 5/(2pi) 4. Manually tune the position loop. a. Restore the Position and Feedforward Gains to the original values to re-enable the position loop. b. While Jogging the axis and monitoring the Torque Reference trend, incrementally increase the following gains simultaneously and stop when the Torque Reference begins to become oscillatory or unstable: • Position Proportional Gain = Position Proportional Gain x N • Position Integral Gain = Position Integral Gain x N2 c. Decrease the gains by using the previous equations with an N = 0.5. A typical range of values for the Position Integral Gain is given: 0 ≤ Position Integral Gain ≤ Position Proportional Gain2/4000
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
249
Page 250
Appendix D
Configure the Load Observer Feature
Setting Gains with Sercos IDN Write the Load Observer Configuration attribute and the Load Observer gains each time the drive gets initialized after applying power. Write Messages The Sercos IDN write instruction is accomplished by using RSLogix 5000® software or the Logix Designer application. Refer to Appendix E on page 253 for more information on changing IDN parameter values by using this method. 1. Upon initialization of the drive, read the INT value of the configuration of the drive at Sercos IDN P:0:431.
2. If the value is not what you want, latch it and write the new value back to the drive at the same address, again as type INT.
250
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 251
Configure the Load Observer Feature
Appendix D
3. Verify the change with another Sercos IDN Read Message from IDN P:0:431.
TIP
Compensate for High Frequency Resonances
The procedure for setting each of the gains is similar.
Approximately 15% of all motion applications exhibit a high-frequency resonance that is apparent by an audible high-frequency squealing of the load mechanics. Follow these steps to identify and reduce the presence of high-frequency resonances. 1. Perform the following move sequence by using Motion Direct Commands: a. Enable the axis with an MSO b. Slowly jog the axis with an MAJ c. Stop the axis with an MAS d. Disable the axis with a MSO IMPORTANT
Sometimes an audible resonance is heard before the axis is jogged, making the MAJ and MAS unnecessary.
2. Determine if an audible high-frequency resonance exists in your motion application. • If an audible high frequency resonance is not present during the move sequence, skip the remaining steps and tuning is complete. • If an audible high frequency resonance is present during the move sequence, use an FFT smart phone or tablet application to identify the dominant resonant frequencies.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
251
Page 252
Appendix D
Configure the Load Observer Feature
3. Click the Output tab in the Axis Properties dialog box.
a. Check Enable Notch Filter Frequency and set the Notch Filter Frequency to the resonant frequency with the largest amplitude. b. If multiple resonances have nearly the same amplitude, set the Notch Filter Frequency to the lowest resonant frequency. c. If the problem persists, also check Enable Low-pass Output Filter and set the Low-pass Output Filter Frequency to the next largest resonant frequency. d. Click OK.
252
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017