Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 28 of 33

Kinetix 6000 Multi-axis Servo Drives User Manual: AppD - Configure the Load Observer Feature, pages 237 to 244

Pages 237 to 244 of 290, from Kinetix 6000 Multi-axis Servo Drives User Manual

The original document is the PDF (21 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 2094-BM01 and Allen-Bradley 2094-PRF

Page 237

Appendix

D

Configure the Load Observer Feature The load observer feature is a control loop inside the Kinetix® 6000 drive (firmware revision 1.124 or later) that estimates the mechanical load on the motor and compensates for it, thereby forcing the motor to behave as if it is unloaded and relatively easy to control. As a result, load observer automatically compensates for disturbances and load dynamics, such as sudden inertia/ torque changes, compliance, backlash, and resonances.

Benefits

Topic

Page

Benefits

237

How it Works

237

Configuration

238

Setting Gains with Sercos IDN Write Messages

250

Compensate for High Frequency Resonances

251

You can use load observer with out-of-box controller gains, where the load is unknown and thus the Load Inertia Ratio = 0, or with auto-tuned controller gains, where the Load Inertia Ratio is known or calculated by performing an auto-tune procedure. When used with out-of-box controller gains, load observer does the following. • Provides relatively high-performance motion control without tuning • Automatically compensates for load resonances and machine wear over time When used with auto-tuned controller gains, load observer does the following. • Increases controller bandwidth • Reduces tracking errors, so line speeds can be increased • Provides tighter control of moving parts, reducing wear and saving material costs

How it Works

Load observer acts on the acceleration signal within the control loops and monitors the Acceleration Reference and the Actual Position Feedback. Load observer models an ideal unloaded motor and generates a load Torque Estimate, in torque units, that represents any deviation in response of the actual motor and mechanics from the ideal model. This deviation represents the reaction torque placed on the motor shaft by the load mechanics. It is estimated in real time and compensated by closed loop operation. Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

237

Page 238

Appendix D

Configure the Load Observer Feature

Figure 114 - Load Observer and Control Loop Signals Relationship Block Diagram Mechanics

Servo Drive Pos Cmd

+

+ –

Control Loops

–

Torque Estimate Velocity Estimate

Fs

Power Conversion

+

Unloaded Motor

Acceleration Reference Torque Load

Load Observer Position Feedback

Load observer also generates a Velocity Estimate signal that you can apply to the velocity loop. The Velocity Estimate has less delay than the Velocity Feedback signal derived from the actual feedback device. It also helps to reduce high frequency output noise caused by load observer's aggressive action on the acceleration reference. Together, load observer with the Velocity Estimate setting provides the best overall performance.

You can configure the load observer feature in a variety of ways by writing to a set of configuration IDN parameters. The overall behavior of load observer is controlled by Load Observer Configuration (IDN P-431). This parameter is used to select the load observer mode. It can be set to the following values.

Configuration

Table 125 - Load Observer Modes Mode

Value

Description

Disabled (default)

0

Load Observer is inactive

Load Observer Only

1

Provides a Torque Estimate only

This setting is a filtered acceleration feedback with the addition of integral action in the acceleration forward path that is active below the observer bandwidth. This greatly increases the disturbance rejection properties (stiffness) over the acceleration feedback setting. However, it is also fairly aggressive and the observer bandwidth must be decreased for stable operation.

2

Standard Operation: Provides Torque and Velocity Estimates

This setting combines the best of the Load Observer Only and Velocity Estimate Only settings. Separately, load observer removes error, but increases phase lag and is fairly aggressive, whereas velocity estimate provides a smooth response and reduces phase lag, but creates error. Together, they remove error and provide a smooth response. Load observer performs well in situations that require adapting to changing inertia and velocity integrator anti-windup.

3

Provides a Velocity Estimate only

This setting creates a filtered velocity feedback signal that is void of phase lag. Less phase lag (delay around the loop) allows for higher performance. However, the signal is modeled at frequencies above the observer bandwidth, producing error in velocity feedback. This generates a fictitiously lower velocity error since velocity error equals velocity command minus velocity feedback. Nevertheless, the steady state error disappears when used in position mode with either the position integrator or the observer integrator. This configuration is not desirable for Velocity mode applications.

4

Provides acceleration setting creates a filtered acceleration feedback signal. This setting is fairly aggressive and the feedback by disconnecting This observer bandwidth must be decreased significantly for stable operation. The Load Observer Only Acceleration Reference to setting is similar, but without the additional phase lag (delay) created by necessary filtering. load observer

Load Observer with Velocity Estimate

Velocity Estimate Only

Acceleration Feedback

238

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 239

Configure the Load Observer Feature

Appendix D

The following figures illustrate the high-level operation of each observer mode. Figure 115 - Load Observer Disabled Configuration (Value 0) Position Command

Mechanics

Servo Drive

+

Control Loops

–

–

+

Power Conversion

+

Unloaded Motor

Acceleration Reference

Torque Estimate

Torque Load Velocity Estimate

Fs

Load Observer Position Feedback

Figure 116 - Load Observer Only Configuration (Value 1) Position Command

Mechanics

Servo Drive

+

Control Loops

–

–

+

Torque Estimate Velocity Estimate

Fs

Power Conversion Acceleration Reference

+

Unloaded Motor

Torque Load

Load Observer Position Feedback

Figure 117 - Load Observer with Velocity Estimate Configuration (Value 2) Position Command

Mechanics

Servo Drive

+

Control Loops

–

–

+

Acceleration Reference

Torque Estimate Velocity Estimate

Fs

Power Conversion

+

Unloaded Motor

Torque Load

Load Observer Position Feedback

Figure 118 - Velocity Estimate Only Configuration (Value 3) Position Command

Mechanics

Servo Drive

+

Control Loops

–

–

Torque Estimate Fs

Velocity Estimate

+

Power Conversion Acceleration Reference

+

Unloaded Motor

Torque Load

Load Observer Position Feedback

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

239

Page 240

Appendix D

Configure the Load Observer Feature

Figure 119 - Acceleration Feedback Configuration (Value 4) Mechanics

Servo Drive

Position Command

+

Control Loops

–

–

Torque Estimate Velocity Estimate

Fs

+

Power Conversion

+

Acceleration Reference

Unloaded Motor

Torque Load

Load Observer Position Feedback

You can configure the load observer feature in a variety of ways by writing to a set of configuration IDN parameters. The overall behavior of load observer is controlled by Load Observer Configuration (IDN P-431). This parameter is used to select the Load Observer mode. Use it to set the IDN values listed in Table 125 on page 238

Remaining IDN Parameter Descriptions Load observer gains that require user interaction are Load Observer Bandwidth (Kop) and Load Observer Integral Bandwidth (Koi). They are set by IDN P-432 and IDN P-433, respectively. Guidelines for setting these gains are provided in the following sections. In general, Kop acts like a velocity integrator without windup and Koi acts a like a position integrator without windup. Typically, Koi = 0. Figure 120 - Load Observer Gains Acceleration Command

Acceleration Reference

– Torque Estimate

Kjm Kou

Acceleration Estimate Feedback Position

Kof Velocity Estimate

Feedback Velocity

FIR Δ

1 s

Kop

– Koi

1 s

Load Observer Plant

Load observer gains that do not require user interaction are Load Observer Feedback Gain (Kof ) and the Load Observer Input Gain (Kou). They are automatically set internally based on the Load Observer Configuration. However, when in Acceleration Feedback mode, Kof can also be set manually by IDN P-434 with typical values between zero and one.

240

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 241

Configure the Load Observer Feature

Appendix D

Table 126 - Load Observer Gain Parameters IDN

Name

Units

P:0:432

Load Observer Bandwidth (Kop)

Rad/s

P:0:433

Load Observer Integral Bandwidth (Koi) Rad/s

P:0:434

Load Observer Feedback Gain (Kof)

Format 16 bit unsigned int

Value, min

Value, max

0

12,500 (1) 65,535 (2)

–

200

(1) This value applies to drive firmware revision 1.124. (2) This value applies to drive firmware revisions later than 1.124.

IMPORTANT

You must validate the input parameter to the message instruction when executing message instructions to the attributes in Table 126. The value being sent is interpreted by the drive as an unsigned 16-bit integer. Attempting to write negative values results in the binary-equivalent positive value being used by the drive.

The Acceleration Estimate and Torque Estimate signals are read by using IDN-435 and P-436, respectively. Definitions for these IDN parameters are given in the following table. Table 127 - Load Observer Output Signals IDN

Name

Units

Format

Value, min

Value, max

P:0:435

Load Observer Acceleration Estimate

Acceleration

32bit signed int

-2 31

2 31 -1

P:0:436

Load Observer Torque Estimate

Torque

16 bit signed int

-2 15

2 15 -1

When load observer and the torque low-pass filter are both enabled, and the low-pass filter bandwidth is less than 5 times the load observer bandwidth, their interaction can interfere with each other, causing instability. The low-pass filter is always limited to a bandwidth under 389 Hz in drive firmware prior to revision 1.116. As a result, IDN P-065 was added in drive firmware revision 1.116 to override the torque low-pass filter bandwidth limiting. The filter is also bypassed if the override IDN P-065 is set to 1 and the torque low-pass filter bandwidth is set to zero. Table 128 - Torque Low-pass Filter Bandwidth IDN P:0:065 0 (1) 1 (2)

Bandwidth in the Logix Designer Application

Actual Bandwidth in Drive

=0

389 Hz

>0

Limited to ≤ 389 Hz

=0

Filter bypassed

>0

Limited to ≤ 10,430 Hz

(1) Operation before firmware revision 1.116. (2) Operation with firmware revision 1.116 or later.

Refer to Appendix E on page 253 for more information on changing IDN parameter values with read/write messages in the Logix Designer application.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

241

Page 242

Appendix D

Configure the Load Observer Feature

Out-of-Box Gain Settings This method of setting controller gains works for unknown loads or when an auto-tune is not performed. It produces a relatively high level of performance in 90% of motion applications. Most of the time, there is no need to perform an auto-tune procedure or further optimize gain settings. TIP

Try this method before executing Auto-tune.

Follow these steps to configure the drive for high performance right out of the box. This procedure uses load observer to automatically account for the unknown load. As a result, you must be familiar with creating an axis in the Logix Designer application and accessing drive IDN parameters. 1. Create a new axis with type AXIS_SERVO_DRIVE. If you need more information to create a new axis, refer to Configure the Kinetix 6000 Drive Modules on page 146. 2. Click the Drive/Motor tab in the Axis Properties dialog box and add a motor.

If you need more information to add a motor, refer to Configure Axis Properties on page 151. 3. Click the Gains tab in the Axis Properties dialog box. The current Velocity Proportional Gain (Initial Kvp) value is used to recalculate other gain values.

4. Make the following calculations: a. Load Observer Bandwidth: Kop = Velocity Proportional Gain x 2.56 b. Velocity Loop Bandwidth: Kvp = Kop/4

242

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 243

Configure the Load Observer Feature

Appendix D c. Position Loop Bandwidth: Kpp = Kvp/4 1 4 K pp

1 4 K vp

0 K pi

2.56

0 K vi

Initial K vp

K op 0 K oi

5. Configure these settings and values on the Gains tab. a. Position Proportional Gain = Kpp b. Velocity Proportional Gain = Kvp c. Velocity Feedforward Gain = 100% d. Integrator Hold = Disabled

6. Configure these IDN parameter values. a. IDN P-431 = 2 (load observer with velocity estimate) b. IDN P-432 = Kop c. IDN P-433 = 0 d. IDN P-065 = 1

7. Click the Output tab in the Axis Properties dialog box and verify these settings. a. Load Inertia Ratio = 0

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

243

Page 244

Appendix D

Configure the Load Observer Feature b. Enable Low-pass Output Filter = Unchecked

8. If required, reduce the Maximum Acceleration and Maximum Deceleration values to meet application requirements and protect the drive and motor from overload. Acceleration limits, by default, are set to their maximum value, providing the best performance for a Load Inertia Ratio of zero. However, your application loads the motor and it will not be able to accelerate as fast.

9. Refer to Compensate for High Frequency Resonances on page 251, to tune-out resonant frequencies.

Auto-tune Gain Settings This procedure explains how to configure the load observer feature after running Auto-tune. This method also works for any existing set of gains where the Load Inertia Ratio is known or manually calculated, for example, when the Load Inertia Ratio > 0. TIP

Try the out-of-box method before executing Auto-tune. Refer to Out-of-Box Gain Settings on page 242.

1. Click the Tune tab in the Axis Properties dialog box and perform Autotune. For variable inertia loads, perform Auto-tune at the point of lowest mechanical inertia. If you manually calculate the Load Inertia Ratio, use the minimum load inertia.

244

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017