Kinetix 6000 Multi-axis Servo Drives User Manual: AppC - DC Common Bus Applications

Pages 227 to 236 of 290, from Kinetix 6000 Multi-axis Servo Drives User Manual

The original document is the PDF (21 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 2094-BM01 and Allen-Bradley 2094-PRF

Page 227

Appendix

C

DC Common Bus Applications

This appendix provides integration procedures specific to Kinetix® 6000 multiaxis drive systems configured for DC common bus. The procedure involves calculating capacitance values and setting the Additional Bus Capacitance parameter by using DriveExplorer® software. Topic

Page

Before You Begin

227

Calculate Total Bus Capacitance

228

Calculate Additional Bus Capacitance

229

Bulletin 2094 Drive Capacitance Values

229

Common Bus Capacitance Example

230

Set the Additional Bus Capacitance Parameter

231

To set the Additional Bus Capacitance parameter by using the Logix Designer application, refer to Appendix E beginning on page 253. Calculating capacitance, as it applies to the Bulletin 2094 shunt module and Kinetix 6000M IPIM module, is also included in this appendix.

Before You Begin

These procedures assume you have mounted and wired your Kinetix 6000 DC common-bus system. Before you set the Additional Bus Capacitance (Add Bus Cap) parameter in DriveExplorer software or the Logix Designer application, you need to calculate these values: • Total bus capacitance • Additional bus capacitance

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

227

Page 228

Appendix C

DC Common Bus Applications

Calculate Total Bus Capacitance

Total bus capacitance is the sum of all capacitance values for your Bulletin 2094 common-bus modules. Specifically, this includes the capacitance values for each of these modules: • Leader IAM (converter and inverter) module • Each AM and shunt module (if present) on the leader IAM power rail • Each IPIM module (if present) on the leader IAM power rail • Each follower IAM (converter and inverter) module • Each AM module on the follower IAM power rail • Each IPIM module (if present) on the follower IAM power rail Refer to Bulletin 2094 Drive Capacitance Values on page 229 for IAM, AM, IPIM, and shunt module capacitance values. IMPORTANT

If total bus capacitance of your system exceeds the leader IAM module precharge rating and input power is applied, the IAM module sevensegment status indicator displays error code E90 (precharge timeout fault). To correct this condition, you must replace the leader IAM module with a larger module or decrease the total bus capacitance by removing AM modules or IPIM modules.

Table 119 - Maximum IAM Module Bus Capacitance Leader IAM (200V-class) Module 2094-AC05-MP5-x 2094-AC05-M01-x

7145

Leader IAM (400V-class) Modules 2094-BC01-MP5-x 2094-BC01-M01-x

Bus Capacitance, max μF 4585

2094-AC09-M02-x

15,295

2094-BC02-M02-x

8955

2094-AC16-M03-x

34,400

2094-BC04-M03-x

8955

2094-AC32-M05-x

62,825

2094-BC07-M05-x

17,915

IMPORTANT

228

Bus Capacitance, max μF

If your total bus capacitance value exceeds the value in the table above, you must increase the size of the leader IAM module or decrease the total bus capacitance by removing other modules on the power rail.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 229

DC Common Bus Applications

Calculate Additional Bus Capacitance

Appendix C

Additional bus capacitance is the sum of all follower IAM, AM, and IPIM module capacitance values for your Bulletin 2094 common-bus modules. Specifically, this includes the capacitance values for each of these modules: • Each follower IAM (converter and inverter) module • Each AM module on the follower IAM module power rail • Each IPIM module on the follower IAM module power rail Enter the additional bus capacitance value in Set the Additional Bus Capacitance Parameter beginning on page 232.

Bulletin 2094 Drive Capacitance Values

Use these tables when calculating total bus capacitance and additional bus capacitance for your Bulletin 2094 common-bus application. Table 120 - IAM/AM (200V-class) Modules IAM Converter (200V-class) 2094-AC05-MP5-x 2094-AC05-M01-x

Capacitance μF 270

AM Inverter (200V-class)

Capacitance μF

2094-AMP5-x

390

2094-AM01-x

660

2094-AC09-M02-x

540

2094-AM02-x

780

2094-AC16-M03-x

1320

2094-AM03-x

1320

2094-AC32-M05-x

1980

2094-AM05-x

2640

AM Inverter (400V-class)

Capacitance μF

2094-BMP5-x

75

2094-BM01-x

150

Table 121 - IAM/AM (400V-class) Modules IAM Converter (400V-class) 2094-BC01-MP5-x 2094-BC01-M01-x

Capacitance μF 110

2094-BC02-M02-x

220

2094-BM02-x

270

2094-BC04-M03-x

940

2094-BM03-x

840

2094-BC07-M05-x

1410

2094-BM05-x

1175

Table 122 - Shunt Module (200/400V-class) Shunt Module (200/400V-class)

Capacitance μF

2094-BSP2

470

Table 123 - IPIM Module (400V-class) IPIM Module (400V-class)

Capacitance μF

2094-SEPM-B24-S

840

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

229

Page 230

Appendix C

DC Common Bus Applications

Common Bus Capacitance Example

In this example, the sum of the leader IAM power rail modules capacitance (6530 µF) and the follower IAM power rail modules capacitance (5280 µF) equals 11,810 µF total bus capacitance. The sum of the follower IAM module power rail equals 5280 µF additional bus capacitance. Figure 113 - Calculating Common Bus Capacitance

AC Line Filter Three-phase Input Power

Kinetix 6000 (230V) Leader IAM Module

11,810 μF Total Bus Capacitance

LIM Module (optional component) 2094-PRF Slot-filler Module N/A 2094-BSP2 Shunt Module, 470 μF 2094-AM02-x AM Module, 780 μF 2094-AM03-x AM Module, 1320 μF 2094-AM03-x AM Module, 1320 μF 2094-AC16-M03-x IAM Converter, 1320 μF 2094-AC16-M03-x IAM Inverter, 1320 μF

DC Common Bus

Kinetix 6000 (230V) Follower IAM Module

5280 μF Additional Bus Capacitance

2094-PRF Slot-filler Module, N/A 2094-AM03-x AM Module, 1320 μF 2094-AM03-x AM Module, 1320 μF 2094-AC16-M03-x IAM Converter, 1320 μF 2094-AC16-M03-x IAM Inverter, 1320 μF

230

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 231

DC Common Bus Applications

Set the Additional Bus Capacitance Parameter

Appendix C

In this section you set the Add Bus Cap parameter by using DriveExplorer software. TIP

You can also set the Add Bus Cap parameter by changing IDN parameter values. Refer to Appendix E on page 253 for more information.

TIP

You can use this procedure to change other parameters too, the Analog Output parameters, for example.

The following hardware and software tools are required to provide the necessary communication link between your personal computer and the Kinetix 6200 and Kinetix 6500 drive system running DriveExplorer software. Table 124 - Kinetix 6000 System Requirements Description

Cat. No.

Version

DriveExplorer software (1) (2)

9306-4EXP02ENE

2.01 or later

Serial to SCANport™ adapter (2) (3)

1203-SSS (Series B)

3.004 or later

Studio 5000 Logix Designer® application RSLogix 5000® software

9324-RLD300xxE

21.0 or later 15.0 or later

(1) Refer to DriveExplorer Getting Results Manual, publication 9306-GR001, for instructions. (2) Additional information regarding these communication and software tools is available at http://www.ab.com/support/ abdrives. (3) Refer to 1203-SSS (series B) FRN 3.xxx User Manual, publication 20COMM-UM001, for instructions.

ATTENTION: To avoid personal injury or equipment damage, at least one end of a Sercos fiber-optic cable must be disconnected from the drive. This makes sure that motion does not occur while changes are being made to the Add Bus Cap parameter.

Remove Sercos Communication Follow these steps to remove (break) Sercos communication. 1. Remove three-phase and control power from the Kinetix 6200 and Kinetix 6500 drive system. 2. Remove one of the Sercos fiber-optic cables. Fiber-optic cable connections (Tx and Rx) are on the top of each IAM and AM module. 3. Re-apply three-phase and control power.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

231

Page 232

Appendix C

DC Common Bus Applications

Set the Additional Bus Capacitance Parameter Follow these steps to set the Additional Bus Capacitance parameter. 1. Start your DriveExplorer software. 2. From the Explore menu, choose Connect>Local or press CTRL+L. DriveExplorer software will read your system. 3. Observe the Linear List of parameters as grouped by Node, Port, and Axis hierarchy as shown below. Linear List Legend

N:

P.

x xxx Parameter Number 30 = Version Data Axis Number 0 = IAM (axis 1) 1 = AM (axis 2) 2 = AM (axis 3) 3 = AM (axis 4) DPI Port Number Network Node Number

4. Choose Devices>Node>Product and navigate to the parameter x:x:x599 as shown below.

5. Double-click the x:x:x599 Add Bus Cap parameter.

232

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 233

DC Common Bus Applications

Appendix C

The command dialog box for parameter x599 - Add Bus Cap opens.

6. Click the Value Edit tab and enter the Add Bus Cap Value (µF). 7. Click OK. The Add Bus Cap value is changed, but not saved in nonvolatile memory.

Save the Add Bus Cap Parameter to Nonvolatile Memory Follow these steps to save the Add Bus Cap parameter to nonvolatile memory. 1. From the Actions menu, choose Nonvolatile Memory. This message dialog box opens.

2. Click Save. The changes are saved to nonvolatile memory and this cautionary message dialog box opens.

3. Click Yes.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

233

Page 234

Appendix C

DC Common Bus Applications

The save to nonvolatile memory is complete and this confirmation message dialog box opens.

4. Click OK. 5. Close the DriveExplorer software.

Verify the Parameter Changes Follow these steps to verify your parameter change was successful. TIP

Verifying the parameter change is optional.

1. Open your DriveExplorer software. 2. Cycle the drive control power. 3. Reconnect the drive to your DriveExplorer software and read the Add Bus Cap value just like you did in Set the Additional Bus Capacitance Parameter on page 232.

4. Verify the new parameter value. In this example, the new value is 1780 µF. 5. Close the DriveExplorer software.

234

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

Page 235

DC Common Bus Applications

Appendix C

Reconnect Sercos Communication Follow these steps to reconnect Sercos communication. 1. Remove three-phase and control power from the Kinetix 6000 drive system. 2. Replace the Sercos fiber-optic cable removed earlier. Fiber-optic cable connections (Tx and Rx) are on the top of each IAM and AM module. 3. Re-apply three-phase and control power.

Rockwell Automation Publication 2094-UM001J-EN-P - March 2017

235

Page 236

Appendix C

DC Common Bus Applications

Notes: