Page 217
Appendix
B
Upgrade the Drive Firmware
This appendix provides procedures for upgrading Kinetix® 6000 drive firmware by using ControlFLASH™ software.
Upgrade Kinetix 6000M System Firmware
Topic
Page
Upgrade Kinetix 6000M System Firmware
217
Upgrade Drive Firmware with ControlFLASH Software
218
Upgrading firmware for the Kinetix 6000M integrated drive-motor (IDM) system is done by using ControlFLASH software. The procedure for upgrading the IDM units uses the Sercos interface, similar to the axis modules. However, upgrading firmware on the IPIM module is accomplished over the EtherNet/IP network. IMPORTANT
DriveExplorer™ software does not apply to Kinetix 6000M firmware upgrades.
For the firmware upgrade procedure specific to the IDM system, refer to the Kinetix 6000M Integrated Drive-Motor System User Manual, publication 2094-UM003.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
217
Page 218
Appendix B
Upgrade the Drive Firmware
Upgrade Drive Firmware with ControlFLASH Software
Upgrading axis module firmware by using ControlFLASH software involves configuring your controller communication, selecting the drive to upgrade, and upgrading the firmware.
Before You Begin You need the following software and information before you begin. Description
Cat. No.
Firmware Revision or Software Version
RSLogix 5000® software or Studio 5000 Logix Designer®
RSLogix 5000 software
15.x or later
Logix Designer application
21.x or later
1756-MxxSE
15.32 or later
1756-L60M03SE
15.4 or later
CompactLogix™ Sercos module
1768-M04SE
15.35 or later
SoftLogix™ Sercos PCI card
1784-PM16SE
15.33 or later
ControlLogix® Sercos module
RSLinx® software
2.50 or later
ControlFLASH software kit (1)
4.00.09 or later
Catalog number of the targeted IAM/AM module you want to upgrade Network path to the targeted IAM/AM module. (1) Download the ControlFLASH kit from http://support.rockwellautomation.com/controlflash. Contact Rockwell Automation Technical Support at (440) 646-5800 for assistance. For more ControlFLASH information (not drive specific), refer to the ControlFLASH Firmware Upgrade Kit User Manual, publication 1756-UM105.
IMPORTANT
Control power must be present at CPD-1 and CPD-2 prior to upgrading your target drive. The seven-segment status indicator on the target IAM (inverter) module or AM module must be displaying a fixed 2, 3, or 4 before beginning this procedure.
ATTENTION: To avoid personal injury or damage to equipment during the firmware upgrade due to unpredictable motor activity, do not apply threephase AC or common-bus DC input power to the drive.
218
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 219
Upgrade the Drive Firmware
Appendix B
Configure Logix5000 Communication This procedure assumes that your communication method to the Logix5000™ controller is using the Ethernet protocol. It is also assumed that your Logix5000 Ethernet module has already been configured. For more information, refer to the ControlLogix System User Manual, publication 1756-UM001. Follow these steps to configure Logix5000 communication. 1. Open your RSLinx Classic software. 2. From the Communications pull-down menu, choose Configure Drivers. The Configure Drivers dialog box opens.
3. From the Available Drive Types pull-down menu, choose Ethernet devices. 4. Click Add New. The Add New RSLinx Classic Driver dialog box opens. 5. Type the new driver name.
6. Click OK. The Configure driver dialog box opens.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
219
Page 220
Appendix B
Upgrade the Drive Firmware
7. Type the IP address of your Logix5000 Ethernet module. The IP address shown is an example. Yours will be different. 8. Click OK. The new Ethernet driver appears under Configured Drivers.
9. Click Close. 10. Minimize the RSLinx application dialog box.
220
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 221
Upgrade the Drive Firmware
Appendix B
Upgrade Firmware Follow these steps to select the drive module to upgrade. 1. Open your ControlFLASH software. You can access the ControlFLASH software by either of these methods: • From the Tools menu in the Logix Designer application, choose ControlFLASH. • Choose Start>Programs>FLASH Programming Tools> ControlFLASH. The Welcome to ControlFLASH dialog box opens.
2. Click Next. The Catalog Number dialog box opens.
3. Select your drive module. In this example, the 2094-BC01-MP5 IAM module is selected. 4. Click Next.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
221
Page 222
Appendix B
Upgrade the Drive Firmware
The Select Device to Update dialog box opens.
5. Expand your Ethernet node, Logix5000 backplane, and EtherNet/IP network module. 6. Select the servo drive to upgrade. 7. Click OK. The Firmware Revision dialog box opens.
8. Select the firmware revision to upgrade. 9. Click Next.
222
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 223
Upgrade the Drive Firmware
Appendix B
The Summary dialog box opens.
10. Confirm the drive catalog number and firmware revision. 11. Click Finish. This ControlFLASH warning dialog box opens.
12. Click Yes (only if you are ready). This ControlFLASH warning dialog box opens.
13. Acknowledge the warning and click OK.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
223
Page 224
Appendix B
Upgrade the Drive Firmware
The Progress dialog box opens and upgrading begins.
The drive module seven-segment status indicator changes from the fixed 2, 3, or 4 to F, which indicates that upgrading is in progress. After the upgrade information is sent to the drive, the drive resets and performs diagnostic checking. 14. Wait for the Progress dialog box to time out.
15. The Update Status dialog box opens and indicates success or failure as described below. Upgrading Status
If
Success
1. Update complete appears in a GREEN Status dialog box. 2. Go to step 16.
Failure
1. Update failure appears in a RED Status dialog box. 2. Refer to ControlFLASH Firmware Upgrade Kit Quick Start, publication 1756-QS105, for troubleshooting information.
16. Click OK.
224
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
Page 225
Upgrade the Drive Firmware
Appendix B
Verify the Firmware Upgrade Follow these steps to verify your firmware upgrade was successful. TIP
Verifying the firmware upgrade is optional.
1. Open your RSLinx software. 2. From the Communications pull-down menu, choose RSWho.
3. Expand your Ethernet node, Logix5000 backplane, and EtherNet/IP network module. 4. Right-click the drive module and choose Device Properties. The Device Properties dialog box opens.
5. Verify the new firmware revision level. 6. Click Close.
Rockwell Automation Publication 2094-UM001J-EN-P - March 2017
225
Page 226
Appendix B
Upgrade the Drive Firmware
Notes:
226