For the Allen-Bradley 2803-VIM2

Page 375

F

Appendix

Objective

Discrete Bit Addressing

This appendix describes the format for addressing the discrete bits when using a PLC with the VIM2 module. The addressing is discussed for these cases: l

Two-slot addressing l

One-slot addressing l

Half-slot addressing

The block transfer addressing is also discussed for each of the three cases listed above.

Two-slot

Addressing

When two-slot addressing is used, the discrete bits are addressed as follows: l

Output (PLC to VIM2 module) - ORG / 10 to ORG /17 l

Input (VIM2 module to PLC) - IRG i 10 to IRG /17 where R = rack number, and G = module/group number.

Block transfers are addressed to RGO. For example, in the diagram below, the VIM2 module is located in rack 0, module group 3. In this case, discrete bit outputs are addressed 003 / 10 to 003 /17. Discrete bit inputs are addressed 103 / 10 to 103 07. Block transfers would be addressed to 030.

/

Rack 0

VIM2 Module

I ,1 I 1 I 1

P L C

1 ; I : 1: I 1:: I I 1: I:Ii 1. 1: (‘: I I.

roup

1

3

4

6

7

Page 376

Appendix

Discrete

Bit Addressing

F

F-2

One-dot

,4ddressing

When one-slot addressing is used, the discrete bits are addressed as follows: l

Output (PLC to VIM2 module) - ORG / 0 to ORG /7 l

Input (VIM2 module to PLC) - IRG / 0 to IRG 17 where R = rack number, and G = module group number of the right slot of the two occupied by the VIM2 module. Block transfers are addressed to RGO where R = rack number, and G = module group number of the left slot of the two occupied by the VIM2 module. For example, in the diagram below, the VIM2 module is located in rack 3, in module groups 4 and 5. In this case, the discrete bit outputs are addressed 035 10 to 035 /‘i. Discrete bit inputs are addressed 135 / 0 to 135 /7. Block transfers would be addressed to 340.

/

VIM2 Module Remote Rack 3

:

7 1 A s B

Module/G roup

Page 377

Appendix

Ha/f-slot

Addressing

Discrete Bit Addressing

F

F-3

When half-slot addressing is used, the discrete bits are addressed as follows: l

Output (PLC to VIM2 module) - ORG / 0 to ORG /7 l

Input (VIM2 module to PLC) - IRG / 0 to IRG /7 where R = rack number, and G = module group number of the last nodule of the two occupied by the VIM2 module. Block transfers are addressed to RGO where R = rack number, and G = module group number of the second module of the two occupied by the VIM2 module. For example, in the diagram below, the VIM2 module is located in rack 1, in module groups 0 to 3. In this case, the discrete bit outputs are addressed 013 / 0 to 013 / 7. Discrete bit inputs are addressed 113 / 0 to 113 / 7. Block transfers would be addressed to 110. Module/Group

Nos. \

Rack 0

Rack 1

<VIM2 Module/Group

Nos.

Module

Page 378

Appendix F-4

Discrete Bit Addressing F

(This page intentionally left blank)