Page 1
Technical Data
Relays and Timers Specifications Bulletin Number 700 Topic
Page
General Purpose Relays
2
Timing Relays
41
NEMA Industrial Relays
81
IEC Control Relays
93
Solid State Relays
109
Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource
Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, http://www.ab.com
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.
Page 2
700-HA General Purpose Relay
Relays and Timers Specifications Cat. No. 700-HA… Electrical Ratings
Pilot Duty Rating‡
NEMA B300
Rated Thermal Current (Ith )
HA = 10 A – 120V, 240V HAX = 6 A – 120V, 240V
Rated Insulation Voltage (Ui)
250V IEC – 300V UL/CSA Inductive
Contacts
Make
Break
Hp
120V AC
30 A
3A
1/3
240V AC
15 A
1.5 A
1
General Purpose
10 A, 240V AC
Resistive
10 A, 30V DC
Min. Low Energy Permissible Load
HA = 10V, 5 mA HAX = 5V, 2 mA
Permissible Coil Voltage Variation
Pickup: 80…110% of Nominal Voltage at 50 Hz 80…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC
Coil Consumption ±10%
AC Coils
50 Hz
60 Hz
Inrush
3.3 VA
2.85 VA
Sealed
2.2 VA
1.9 VA
DC Coils
1.3 W 20% of nominal V AC
Must Dropout Voltage
10% of nominal V DC 50 MΩ (700-HA and 700-HAB) 30 MΩ (700-HAX)
Max. Contact Resistance
Design Specification/Test Requirements Electrical Pole-to-Pole
2000V
Contact to Coil
2000V
Electrical Life (Operating)
100 000 min.
Degree of Protection (Open Type) IEC 529
IP 40
Mechanical Life Cycles (AC/DC)
> 20 x 106/ 50 x 106
Switching Frequency Operations
3600/HR
Coil Voltages
See Product Selection
Mechanical
Operating Time
Max. Pickup
10 ms
Max. Dropout
10 ms
Endurance
5G
Maximum Operating Rate Vibration Shock
4 Ops/s Operational
2.5 G
Endurance
50 G
Operational
9G
Operating
AC/DC
–40…+70 °C
Storage
AC/DC
–40…+100 °C
Environmental Temperature Altitude
2000 m (6560 ft)
Insulating Material
Molded High-Dielectric Material
Construction Enclosure Contact Material
Transparent Dust Cover 700-HA:
10 A– AgNi
700-HAX:
6 A–Bifurcated/Gold Plating AgNi
Terminal Markings on Socket
In accordance with EN50 0005
Sockets
8-Pin Socket, 700-HN100, -HN125, -HN204 11-Pin Socket, 700-HN101, -HN126, -HN205
Certifications cURus Recognized (File No. E3125, Guide NLDX2/NLDX8), cULus Listed when used with Bulletin 700-HN sockets noted above (File No. E3125, Guide NLDX/NLDX7), CE Marked, CSA Certified, UR Certified (File 229473)
Standards
UL508, CSA C22.2 No. 14, EN 61810-1
‡ NEMA Rating Chart is in publication 700-SG003*
2
Rockwell Automation Publication 700-TD552A-EN-P
Page 3
Relays and Timers Specifications
700-HA General Purpose Relay k Reduction Factor
Cycles
Max. Switching Current (A)
700-HA Relay Performance Graphs
Load (kVA) Contact life vs. AC1 load at 1,800 cycles/h
Voltage DC (V) Breaking capacity for DC1 load at 1,800 cycles/h.
COS
Load reduction factor vs. cos φ
A = load applied to one contact B = load applied to two contacts in series C = load applied to three contacts in series Time Module Cat. No. 700-HT3 Electrical Ratings Operating Voltage Range
12…240V AC (50/60 Hz) 12…240V DC
Power Consumption
0.1 W (12V) 1.0 W (230V)
Degree of Protection of Input (B1) Terminal
IP 20 (Guarded Terminal)
Input Terminal Wire Range
1.0 x 0.2 mm2…2.5 mm2 (24 AWG…14 AWG) 2.0 x 0.2 mm2…1.5 mm2 (24 AWG…16 AWG)
Input Terminal Torque Range
0.45…0.8 Nm (4…7 lb-in.)
LED Indicator
Red
Repeat Accuracy‡
±1%
Recovery Time
<50 ms
Selectable Timing Ranges
Three DIP switches, seven ranges (set from 5…100% of range): 1 s, 10 s, 100 s, 10 min, 100 min, 10 h, 100 h
Selectable Timing Modes
Three DIP switches, eight modes: 1. Power On–Delay 2. Power On One-Shot 3. Power On Repeat Cycle, On Start 4. Signal On-Delay and Signal Off-Delay 5. Signal Off-Delay 6. Signal On-One-Shot 7. Signal Off-One-Shot 8. Signal On and Signal Off Watchdog Monitor
Adjustable Trimmer Scale Accuracy
±5% of Time Range
Mechanical
Environmental Temperature
Operating Storage
–20 °C…+50 °C (–4 °F…+122 °F) –55 °C…+85 °C (–67…+185 °F)
Altitude
2000 m (6560 ft)
Enclosure
Gray Plastic Housing
Mounting with Socket Only
8- or 11-Pin Socket with Module Plug
Sockets
700-HN204 (8-Pin with Plug) 700-HN205 (11-Pin with Plug)
Certifications cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), CE Marked
Standards
UL508, CSA C22.2 No. 14, EN 61810-1
Construction
‡ At constant voltage and temperature.
Rockwell Automation Publication 700-TD552A-EN-P
3
Page 4
700-HA General Purpose Relay
Relays and Timer Specifications
Timing Charts, Cat. No. 700-HT3 Multi-Function Time Module (t = Time Range 0.05 s…100 h) Terms: U is Power Input R is Relay Output S Signal, +A1 Socket, B1 Timer t is the resulting Time Delay (Red LED)
3. Power On Repeat Cycle, On Start
Apply power (U) to timer. Relay contacts (R) change state immediately and the time delay (t) begins. When the time delay is complete, the contacts return to their shelf state for time delay (t) (time on = time off). This cycle will repeat until the power is removed. Terminal B1 is not used in this mode.
1. Power On-Delay Apply power (U) to timer. Relay contacts (R) change state after time delay (t) is complete. Contacts return to their shelf state when power is removed. Terminal B1 is not used in this mode.
4. Signal On-Delay and Signal Off-Delay
2. Power On One-Shot Apply power (U) to timer. Relay contacts (R) change state immediately and the time delay begins. When the time delay (t) is complete, contacts return to their shelf state. Contacts return to their shelf state when power is removed. Terminal B1 is not used in this mode.
4
Apply power (U) to timer. When the signal (S) is closed the time delay (t) begins, after the time delay is complete the relay contacts (R) change state. Opening the signal starts the time delay, after the time delay is complete the contacts return to their shelf state. If the signal is closed or opened before the time delay is complete, the time delay is reset. Contacts return to their shelf state when power is removed.
Rockwell Automation Publication 700-TD552A-EN-P
Page 5
Relays and Timer Specifications
700-HA General Purpose Relay
Cat. No. 700-HT3 Timing Modes, Time Description, Timing Charts, and DIP Switch Selections 5. Signal Off-Delay Apply power (U) to timer. When the signal (S) is closed, the relay contacts (R) change state immediately. When the signal is opened, the time delay (t) begins. If the signal is closed before the time delay is complete, the time delay is reset and the relay remains energized. When the time delay is complete, the contacts return to their shelf state. Contacts return to their shelf state when power is removed.
7. Signal Off One-Shot Apply power (U) to timer. When the signal (S) is closed and then opened, the relay contacts (R) change state immediately and the time delay (t) begins. After the time delay begins, opening or closing the signal will not reset the time delay. When the time delay is complete, the contacts return to their shelf state. Contacts return to their shelf state when power is removed.
8. Signal On and Signal Off Watchdog Monitor 6. Signal On One-Shot Apply power (U) to timer. When the signal (S) is closed, the relay contacts (R) change state immediately and the time delay (t) begins. After the time delay begins, opening or closing the signal will not reset the time delay. When the time delay is complete, the contacts return to their shelf state. Contacts return to their shelf state when power is removed.
Apply power (U) to timer. When the signal (S) is closed, the relay contacts (R) energize immediately and the time delay (t) begins. If the signal is opened before the time delay is complete, the relay remains energized and the time delay is reset. When the time delay is complete the contacts return to their shelf state. If the signal is opened after the time delay is complete, the relay contacts energize immediately and the same time delay begins. Continuous cycling of the signal at a rate that is faster than the time delay will cause the relay contacts to remain energized. Contacts return to their shelf state when power is removed.
Rockwell Automation Publication 700-TD552A-EN-P
5
Page 6
700-HA General Purpose Relay
Relays and Timer Specifications
Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
54.1 (2-1/8)
32.8 (1-3/10)
36.5 (1-9/20)
Bulletin 700-HA Relay
5.2 (13/64)
12.5 (1/2)
6.2 (15/64)
50 (1-63/64)
1.0 (0.04)
35.0 (1.38)
27.0 (1.06)
7.5 (0.3)
1000 (39-3/8)
Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes
6
Cat. No.
A
B
C
D
Approx. Shipping Wt.
199-DR1
35 (1-3/8)
27 (1-1/16)
7.5 (19/64)
1.02 (1/64)
1.85 kg (4.07 lb) (10/pkg)
199-DR4
35 (1-3/8)
27 (1-1/16)
15 (19/32)
2.3 (3/32)
3.68 kg (8 lb) (5/pkg)
Rockwell Automation Publication 700-TD552A-EN-P
Page 7
Relays and Timer Specifications
700-HA General Purpose Relay
Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes. 24.6 (31/32)
40.1 (1-37/64)
20.8 (53/64)
30.0 (1-3/16)
26 (1-1/32)
24.9 (63/64)
65.0 (2-35/64)
54.9 (2-5/32) 51.1 (2-1/64)
4.2 (5/32) 38.0 (1-1/2) #4–40 M3 Cat. No. 700-HN100
33.0 (1-19/64)
14.7 (37/64)
Panel Mounting
Cat. No. 700-HN125
2
Wire Size: 2 x 2.5 mm2 Single Wire – Up to 12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG…#2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)
Wire Size: 2 x 2.5 mm Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2-14 AWG… #2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)
26 (1-1/32)
30 (1-3/16)
59.2 (2-1/3) 7.9 (0.31)
24.6 (31/32) 20.8 (53/64)
26.9 (1.06)
65.0 (2-35/64)
54.9 (2-5/32) 4.2 (5/32)
51.1 (2-1/64)
38.0 (1-1/2) #4-40 M3 Cat. No. 700-HN101 2
52.3 (2.06)
Panel Mounting
Wire Size: 2 x 2.5 mm Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG…#2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)
Cat. No. 700-HN126 2
Wire Size: 2 x 2.5 mm Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG…#2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)
Rockwell Automation Publication 700-TD552A-EN-P
7
Page 8
700-HA General Purpose Relay
Relays and Timer Specifications
Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes. 33.5 (1.32) 33.5 (1.32)
26.9 (1.06)
11.0 (0.43)
77.5 (3.05)
3.2 (0.13)
26.9 (1.06)
11.0 (0.43) 20.4 (0.80)
20.4 (0.80)
77.5 (3.05)
49.7 (1.96)
3.2 (0.13)
35.5 (1.40)
16.8 (0.66)
21.6 (0.85)
16.8 (0.66)
38.0 (1.50)
38.0 (1.50)
Cat. No. 700-HN204
Cat. No. 700-HN205
Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG …#2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)
38.0 (1.50)
54 (2.13)
6.3 (0.25)
10.5 (0.41)
Cat. No. 700-HT3 2
Wire Size: 2 x 1.5 mm (#2 – 16 AWG…#1–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)
Rockwell Automation Publication 700-TD552A-EN-P
35.5 (1.40)
21.6 (0.85)
4.0 (0.16)
4.0 (0.16)
Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)
8
49.7 (1.96)
Page 9
Relays and Timer Specifications
700-HB General Purpose Relay
Specifications Cat. No. 700-HB… Electrical Ratings Pilot Duty Rating‡
NEMA B300
Rated Thermal Current ( Ith )
15 A – 120V, 240V
Rated Insulation Voltage (Ui)
250V IEC-300V UL/CSA Make
Break
Hp
Inductive Contacts
2 -Pole
3 -Pole
2 -Pole
120V AC
60 A
30 A
6A
3A
3/4
240V AC
30 A
15 A
3A
1.5 A
2
General Purpose
3 -Pole
15 A, 240V AC
Resistive
15 A, 30V DC
Min. Low Energy Permissible Load
1000 mW (10V, 10 mA) 80…110% of Nominal Voltage at 50 Hz
Permissible Coil Voltage Variation
80…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC
Coil Consumption ±10%
AC Coils
50 Hz
60 Hz
Inrush
3.3 VA
2.85 VA
Sealed
2.2 VA
1.9 VA
DC Coils
1.3 W 25% of VA
Max. Allowable Leakage
10% of W
Max. Contact Resistance
50 mΩ Design Specification/Test Requirements Electrical
Dielectric Withstand Voltage Pole-to-Pole
2500V
Contact to Coil
4000V Mechanical
Degree of Protection (Open Type) IEC 529
IP 40 > 10 x 106/30 x 106
Mechanical Life Cycles (AC/DC) Switching Frequency Operations
3600/HR
Coil Voltages Operating Time (ms)
See Overview/Product Selection Pickup
20 ms
Dropout
4 ms
Maximum Operating Rate Vibration Shock
4 Ops/s
Endurance
5G
Operational
1.5 G
Endurance
50 G
Operational
15 G Environmental
Temperature
Operating
AC/DC
–40…+70 °C
Storage
AC/DC
–40…+100 °C
Altitude
2000 m (6560 ft) Construction
Insulating Material
Molded High Dielectric Material
Enclosure
Transparent Dust Cover
Contact Material
AgCdO
Terminal Markings on Socket
In accordance with EN50 0005
Sockets
700-HN153, -HN154
Certifications cURus Recognized (File No. E3125, Guide NLDX2/NLDX8), cULus Listed when used with Bulletin 700-HN sockets noted above (File No. E3125, Guide NLDX/NLDX7), CE Marked, CSA Certified, UR Certified (File No. 229473)
Standards
UL508, CSA C22.2 No. 14, EN 61810-1
‡ NEMA Rating Chart is in publication 700-SG003*
Rockwell Automation Publication 700-TD552A-EN-P
9
Page 10
700-HB General Purpose Relay
Relays and Timer Specifications
Cycles
Technical Data
Load (kVA)
Maximum Switching Current (A)
Contact life vs AC1 load at 600 cycles/h.
Voltage DC (V)
Reduction Factor
Breaking capacity for DC1 load at 600 cycles/h. Load applied to 1 contact. A = for N.O. types B= other types
(Highly Resistive)
COS (Inductive) Load Reduction factor vs cos φ
10
Rockwell Automation Publication 700-TD552A-EN-P