For the Allen-Bradley 700-HN122

Page 11

Relays and Timer Specifications

700-HB General Purpose Relay

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

60.9 (2.40)

35.8 (1.41)

38.2 (1.50)

30.25 (1.19)

27.0 (1.06)

40 (1.57)

34.3 (1.35) Ø 3.2 (0.13)

51.4 (2.02)

91.3 (3.59)

35.4 (1.39)

95.3 (3.75) 46.3 (1.82)

21.6 (0.85)

35.5 (1.40)

Bulletin 700-HB Relay

32.0 (1.26)

Cat. No. 700-HN153 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)

Rockwell Automation Publication 700-TD552A-EN-P

11

Page 12

700-HB General Purpose Relay

Relays and Timer Specifications

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

38.0 (1.50)

49.5 (1.95)

25.6 (1.01)

35.4 (1.40)

54 (2.13)

84.85 (3.34) 84.3 (3.32)

6.3 (0.25)

10.5 (0.41)

41.5 (1.63)

4.0 (0.16)

Cat. No. 700-HN154 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)

12

Cat. No. 700-HT3 Wire Size: 2 x 1.5 mm2 (#2–16 AWG…#1–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)

Rockwell Automation Publication 700-TD552A-EN-P

Page 13

Relays and Timer Specifications

700-HD General Purpose Relay

Specifications Cat. No. 700-HD… Electrical Ratings Pilot Duty Rating‡

NEMA B300

Rated Thermal Current ( Ith )

15 A§ – 120V 15 A§ – 240V

Rated Insulation Voltage (Ui)

250V IEC-300V UL/CSA Make

Inductive

Contacts

Break

Hp

2-Pole

3-Pole

2-Pole

120V AC

60 A

30 A

6A

3A

3/4

240V AC

30 A

15 A

3A

1.5 A

2

General Purpose

3-Pole

15 A, 240V AC

Resistive

15 A, 30V DC

Min. Low Energy Permissible Load

1000 mW (10V, 10 mA)

Permissible Coil Voltage Variation

80…110% of Nominal Voltage at 50 Hz 80…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC

Coil Consumption ±10%

AC Coils

50 Hz

60 Hz

Inrush

3.3 VA

2.85 VA

Sealed

2.2 VA

1.9 VA

DC Coils

1.3 W

Maximum Contact Resistance

50 mΩ 20% of Nominal V AC 10% of Nominal V DC

Must Dropout Voltage

Design Specification/Test Requirements Electrical Dielectric Withstand Voltage Pole-to-Pole

2500V

Contact to Coil

4000V Mechanical

Degree of Protection (Open Type) IEC 529

IP 40 > 10 x 106 / 30 x 106

Mechanical Life Cycles (AC/DC) Switching Frequency Operations

3600/HR

Coil Voltages Operating Time

See Overview/Product Selection Pickup

20 ms

Dropout

4 ms

Maximum Operating Rate

4 Ops/s

Minimum Low Energy Permissible Load

1000 mN (10V, 10mA) Environmental

Temperature

Operating

–40…+70 °C

Storage

–40…+100 °C

Altitude

2000 m (6560 ft) Construction

Insulating Material

Molded High Dielectric Material

Enclosure

Transparent Dust Cover

Contact Material

Silver Cad. Ox.

Terminal Markings

In accordance with EN50 0005

Certifications cURs Recognized (File No. E3125, Guide NLDX2/NLDX8), CSA Certified (File No. 229473), CE Marked, UR Certified

Standards

UL 508, CSA C22.2 No. 14, EN 61810-1

‡ NEMA Rating Chart is on page 19 of publication 700-SG003* § 3-pole relays have a 20 A maximum total current rating for all three poles.

Note: Bulletin 700-HD wiring terminals are the quick connect/solder type 4.7 x 0.5 mm (0.187 x 0.020 in.) termination.

Rockwell Automation Publication 700-TD552A-EN-P

13

Page 14

Relays and Timer Specifications

Cycles

Maximum Switching Current (A)

700-HD General Purpose Relay

Voltage DC (V)

Load (kVA)

Breaking capacity for DC1 load at 600 cycles/h.

Contact life vs AC1 load at 600 cycles/h.

Reduction Factor

Load applied to 1 contact. A = for N.O. types B= other types

(Highly Resistive)

COS

(Inductive)

Load Reduction factor vs cos φ

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes. 35.9 (1.41)

63 (2.48)

68 (2.67)

38.2 (1.50) Bulletin 700-HD Relay

14

Rockwell Automation Publication 700-TD552A-EN-P

Page 15

Relays and Timer Specifications

700-HC Relays

Specifications Cat. No. 700-HC… Electrical Ratings Pilot Duty Rating ‡

NEMA C300, R300

Rated Thermal Current (Ith)

7 A and 10 A

Rated Insulation Voltage (Ui)

250V IEC – 300V UL/CSA Inductive

Contacts

700-HC_4

Hp

700-HC22

Hp

120V AC

15 A

1.5 A

1/8

15 A

1.5 A

1/3

240V AC

7.5 A

0.75 A

1/3

7.5 A

0.75 A

3/4

General Purpose

7 A, 277V AC

10 A, 277V AC

Resistive

7 A, 30V DC

10 A, 24V DC

100 mW (10V, 10 mA) - Silver Contacts 50 mW (5V, 10 mA or 25V, 2 mA) - Gold Contacts

Min. Low Energy Permissible Load

80…110% of Nominal Voltage at 50 Hz Permissible Coil Voltage Variation

Pickup:

20% of Nominal Voltage at AC

80…110% of Nominal Voltage at 60 Hz

Must Dropout Voltage:

10% of Nominal Voltage at DC

80…110% of Nominal Voltage at DC

Coil Consumption ±10%

AC Coils

50 Hz

60 Hz

Inrush

2.2 VA

1.6 VA

Sealed

1.3 VA

1.1 VA

DC Coils

1.0 W 20% of VA (AC)

Max. Allowable Leakage

10% of W (DC) Design Specification/Test Requirements Electrical

Dielectric Withstand Voltage

Pole-to-Pole

2000V

Contact to Coil

4000V

Electrical Life (Cycles)

100 000 minimum Mechanical

Degree of Protection (Open Type) IEC 529

IP 20 (Guarded Terminal Sockets)

Mechanical Life Cycles

20 x 106 (AC) 50 x 106 (DC)

Switching Frequency Operations

1800/HR

Coil Voltages Operating Time (ms)

See Product Selection Max. Pickup

10

Max. Dropout

3

Maximum Operating Rate

8 cycles/s Environmental Operating

Temperature Storage Altitude Insulating Material

–30…+55 °C (–22…+131 °F) –55…+85 °C (–67…+185 °F) 2000 m (6560 ft) Molded High Dielectric Material

Enclosure

Transparent Dust Cover

Contact Material

AgNi (700-HC2) AgNi + 5 μm All (700-HC1)

Terminal Markings on Socket Sockets

In accordance with EN50 0005 700-HN103, -HN128, -HN104

Certifications cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), cULus Listed when used with Bulletin 700HN103, -HN104, and -HN128 sockets (File No. E14843, Guide NRNT/NRNT7), CE Marked, LR Certified

Standards

UL 508, CSA 22.2 No. 14, EN 61810-1

‡ NEMA Rating Chart is in publication 700-SG003*

Rockwell Automation Publication 700-TD552A-EN-P

15

Page 16

700-HC Relay

Relays and Timer Specifications

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

37.2 (1.46)

36.7 (1.44)

5.6 (0.22)

6.1 (0.24)

20.7 (0.82)

27.7 (1.09)

20.7 (0.82)

27.7 (1.09)

Bulletin 700-HC Relay (Two-Pole)

Bulletin 700-HC Relay (Four-Pole) 27.0 (1.06)

60.9 (2.40) 21.5 (0.85)

35.6 (1.40)

76.0 (2.99) 3.2 (0.13)

18.9 (0.74) 34.9 (1.37)

32.0 (1.26) 35.5 (1.40) 2.5 (0.10)

Cat. No. 700-HN104 Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…14 AWG) Double Wire: 2 x 0.2 mm2…2 x2.5 mm2 (2 x 24 AWG…2 x 14 AWG) Wire Type: solid or stranded, copper only Strip Length: 7 mm (9/32 in.), Torque: 0.5 N•m (4.4 lb•in)

30.0 (1-3/16) 6.1 (15/64)

Panel Mounting 28.9 (1-9/64) 24.5 (31/32)

8

7

6

5

4

3

2

1

24.9 (57/64) 21.1 (53/64)

67.0 (2-5/8)

4.2 (5/32)

#4-40 M3

30.0 (1-11/64)

14 12

13 11

10

62.0 (2-15/64)

65.0 (2-9/16)

9

26.0 (1-1/64)

16

Cat. No. 700-HN103

Cat. No. 700-HN128

Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…14 AWG) Double Wire: 2 x 0.2 mm2…2 x 1.5 mm2 (2 x 24 AWG…2 x 16 AWG) Wire Type: Solid or Stranded, Copper only Strip Length: 8 mm (5/16 in.), Torque: 0.5 N•m (4.4 lb•in)

Wire Size: 2 x 1.5mm2 (#2-16 AWG…#1-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Toque: 0.8 N•m (7 lb•in)

Rockwell Automation Publication 700-TD552A-EN-P

Page 17

Relays and Timer Specifications

700-HK Relay Cat. No. 700-HK… Electrical Ratings

Rated Thermal Current ( Ith )

1-Pole, 1 CO, SPDT, 16 A

Rated Insulation Voltage (Ui) 120V AC

AC-15, 6.2 A B300 Pilot Duty, 3 A A300 (700-HKM_) 1/3 Hp (0.24 kW) 1-phase

120V AC

AC-15, 2.9 A B300 Pilot Duty, 3.0 A 1/4 Hp (0.18 kW), 1-phase

240V AC

AC-15, 3.1 A B300 Pilot Duty, 1.5 A A300 (700-HKM_) 3/4 Hp (0.55 kW), 1-phase

240V AC

AC-15, 1.4 A B300 Pilot Duty, 1.5 A 1/2 Hp (0.37 kW), 1-phase

230V AC

0.55 kW, 1-phase

230V AC

0.37 kW, 1-phase

24V DC

DC-13, 5.0 A

24V DC

DC-13, 3.0 A

125V DC

DC-13, 0.2 A R300 Pilot Duty, 0.22 A

125V DC

DC-13, 0.2 A R300 Pilot Duty, 0.22 A

250V DC

DC-13, 0.1 A R300 Pilot Duty, 0.11 A

5 A, 250V AC

DC-13, 0.1 A R300 Pilot Duty, 0.11 A

230V AC

AC-1, 16 A

230V AC

AC-1, 8 A

277V AC

16 A, General Use

277V AC

8 A, General Use

30V DC

DC-1, 12 A 10 A, Resistive

30V DC

DC-1, 6 A 6 A, Resistive

Inductive V AC

Contacts Inductive V DC

Resisitive Make, Break & Continuous Min. Permissible Contact Ratings Permissible Coil Voltage Variation

Pickup: holding Voltage: Must Dropout Voltage:

2-Pole, 2 CO, DPDT, 8 A 250V IEC, 300V UL/CSA

300 mW (5V/60 mA or 60V/5 mA) for AgNi Contacts (700-HK3_) 50 mW (5V/10 mA or 25V/2 mA) for AgNi + Gold Contacts (700-HKX_) 500 mW (100V/5 mA or 5V/100 mA) for AgSnO2 Contacts (700-HKM_) 80…110% of Nominal Voltage at 50/60 Hz, 73...110% of Nominal Voltage at DC 80% of Nominal V AC at 50/60 Hz, 40% of Nominal V DC 20% of Nominal V AC at 50/60 Hz, 10% Nominal V DC

Power Consumption

1.2V A (V AC Coils), 0.5 W (V DC Coils)

Coil Voltages

See Overview/Product Selection Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole to Pole (VRMS)

2000V AC

Contact to Coil (VRMS)

4000V AC

Degree of Protection

Mechanical IP 20 (guarded terminal sockets), RT II, Flux-proof (Relay) 10 x 106

Mechanical Life Operations

Electrical Life Cycles

230V AC, 16 A Resistive: 100 000 min. 277V AC, 16 A Resistive: 30 000 min. 30V DC, 10 A Resisitive: 30 000 min. B300, R300, Hp (kW): 6000 min. A300 (700-HKM_): 100,000 min.

Mechanical: 18,000 cycles/hr. Electrical: 900 cycles/hr.

Switching Frequency Operating Time at Nominal Voltage at 20 °C (ms) Vibration

Pickup

15 ms max.

Dropout

5 ms max.

Operational

10…2000 Hz, 0.76 mm (0.03 in.) 2.5 G 10…2000 Hz, 0.76 mm (0.03 in.) 5.0 G

Non-Operational

Shock

230V AC, 8 A Resistive: 100 000 min. 277V AC, 8 A Resistive: 30 000 min. 30V DC, 6 A Resistive: 30 000 min. B300, R300, Hp (kW): 6000 min.

Operational

15 G

Non-Operational

50 G Environmental

Operating

–40…+70 °C (–40…+158 °F)

Storage

–40…+85 °C (–40…+185 °F)

Temperature

Altitude

2000 m (6560 ft) Construction

Insulating Material

Molded High Dielectric Material

Enclosure

Transparent Dust Cover

Contact Material

700-HK3_: Silver nickel (AgNi); 700-HKX_: Silver Nickel + Gold Plating (AgNi + Au); 700-HKM_: Silver Tin Oxide (AgSnO2)

Terminal Markings on Socket

In accordance with EN 50005 1-Pole

2-Pole

Screw Terminal

700-HN121 (10 A @ 70 °C) 700-HN221 (16 A @ 50 °C, 12 A @ 70 °C)

700-HN122 (2 x 5 A @ 70 °C) 700-HN222 ( 2 x 8 A @ 70 °C)

Spring Clamp (Available September 2006)

700-HN223 (15 A @ 40 °C with 2 conductors per terminal) (10 A @ 70 °C with 1 conductor per terminal)

700-HN224 (2 x 8 A@ 70 °C)

Sockets

Approvals

Rockwell Automation Publication 700-TD552A-EN-P

17

Page 18

700-HK Relay

Relays and Timer Specifications

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

12.4 (1/2)

29.0 (1-9/64)

12.4 (1/2)

29.0 (1-9/64)

32.8 (1-19/64)

32.8 (1-19/64)

30.1 (1-3/16)

6.5 (1/4)

6.5 (1/4)

2.5 (3/32) 4.75 (3/16)

0.5 (1/32)

A1 5

A2 1

A1 8

COM 11 4

NO 14 4

NC 12 2

0.5 (1/32) COM 11 3 NC 12 2

A2 NC 22 1 7 NC 12 NO 14 2 3

COM 21 6

COM 11 NO 14 NC 12 3 4 2

A1 8

NO 24 5

NC 22 7

15.8 (5/8) COM 21 NO 24 NC 22 6 5 7

A2 1

NO 14 3

NC 12 2

A2 1 Cat. No. 700-HN222

Cat. No. 700-HN224

COM 11 4

A1 5

COM 11 NO 14 NC 12 4 3 2

A1 5

15.8 (5/8)

15.8 (5/8)

A2 1

A2 1 Cat. No. 700-HN221

Cat. No. 700-HN223

64.9 (2-9/16)

44.7 (1-3/4)

18

NO 24 5

A1 8

15.8 (5/8) COM 21 6

NO 14 4

Cat. No. 700-HK32_ (DPDT)

Cat. No. 700-HK36_ (SPDT) COM 11 3

30.1 (1-3/16)

32.5 22.6 (1-9/32) (57/64)

35.3 (1-25/64)

34.7 (1-3/8) 95.6 (3-49/64)

35.4 (1-13/32) 82.85 (3-17/64)

Cat. No. 700-HN223, 700-HN224 Wire Size: 0.2 mm2...1.5 mm2 (#24 AWG....#14 AWG) Either Solid or Stranded Strip Length: 8 mm (5/16 in)

Cat. No. 700-HN221, 700-HN222 Wire Size: 0.2 mm2...2.5 mm2 (#24 AWG....#12 AWG) Either Solid or Stranded Strip Length: 8 mm (5/16 in), Torque: 0.8Nm (7.0 lb.-in.)

Rockwell Automation Publication 700-TD552A-EN-P

Page 19

Relays and Timer Specifications

700-HK Relay

Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes. 46.0 (1-13/16) 14.4 (37/64)

3.6 (9/64)

14.4 (37/64)

38.0 (1-1/2)

46.9 (1-27/32)

42.4 (1-43/64)

36.6 (1-11/16)

39.8 (1-37/64)

18.1 (23/32)

2.0 (5/64)

34.8 (1-3/8) Cat. No. 700-HN227

Cat. No. 700-HN226

1.0 (0.04)

12.5 6.2 (1/2) (15/64)

50 (1-63/64)

27.0 (1.06)

35.0 (1.38)

5.2 (13/64)

7.5 (0.30)

1000 (39-3/8) Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes Cat. No. 199-DR1 DIN Mounting Rail Series B

Cat. No.

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lb) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lb) (5/pkg)

7.11 (9/32)

11 4 14 3

2.03 (5/64)

Five M3.5 x 0.315 Screws

4.06 (5/32)

12 2 3.0 Ø (1/8) Use M3 Screws

84.1 5 (+) (3-5/16) (A1)

21 6

39.5 (1-17/32)

35.5 (1-13/32)

1 (-) (A2) 4.06 (5/32) 15.6 (5/8)

29.9 (1-3/16) 54.1 (2-1/8)

7.11 (9/32)

11 3

22 7 24 5

Eight M3.5 x 0.315 Screws

14 4

84.1 (3-5/16) 8 (+) (A1) 4.06 (5/32)

2.03 (5/64)

12 2

4.06 (5/32) 39.5 (1-17/32)

3.0 Ø (1/8) Use M3 Screws

15.6 (5/8)

35.5 (1-13/32)

1 (-) (A2) 29.9 (1-3/16) 54.1 (2-1/8)

Cat. No. 700-HN121 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #14 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)

Cat. No. 700-HN122 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #14 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)

Holes required for mounting [3 mm (1/8 in.) diameter].

Rockwell Automation Publication 700-TD552A-EN-P

19

Page 20

700-HLT Relay

Relays and Timer Specifications Cat. No. 700-HLT… (Relay Output) Electrical Ratings

Pilot Duty Rating

B 300, R 300

Rated Thermal Current (Ith)

1-Pole, 6 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA Inductive

Contacts

1-Pole

24V AC, 1-phase

30 A

5A

120V AC, 1-phase

30 A

3A

240V AC, 1-phase

15 A

1.5 A

Make, Break & Continuous V DC

1.0 A 0.2 A

240V DC

0.1 A

AC-15 250V, 3 A N.O. Contact, 1.5 A N.C. Contact DC-13 24V, 1 A N.O. and N.C. Contact

Inductive Load Min. Permissible Contact Ratings

12V, 6 mA (72 mW) for Silver Contacts, 8V, 2.5 mA (20 mW) for Gold Contacts Pickup:

Must Dropout 10% of Nominal Voltage at AC Voltage: 5% of Nominal Voltage at DC

85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC

Permissible Coil Voltage Variation

Power Consumption ±10%

24V DC 120V DC

AC

0.3 VA

DC

0.2 W Design Specification/Test Requirements

Dielectric Withstand Voltage

Input Voltage Impedance (Ohms)

Pole to Pole (VRMS)

1000V

Contact to Coil (VRMS)

4000V

12V AC/DC

24V AC/DC

48V AC/DC

120V AC/DC

240V AC/DC

120V LCSC

240V LCSC

1K

2K

6K

26 K

56 K

16 K

35 K

Mechanical Degree of Protection

IP20

Mechanical Life Operations

1 x 107

Electrical Life Operations

6 A Resistive: 100 000 min. 24V DC, 1 A Inductive: 200 000 min. 120V AC 1 A Inductive: 300 000 min.

Switching Frequency Operations (no-load)

10 cycles/sec

Coil Voltages Operating Time at Nominal Voltage at 20 °C (ms)

See Overview/Product Selection Pickup

7 ms

Dropout

3 ms

Maximum Operating Rate (full load = 6 A)

6 cycles/min. Per EN 61000-4.5; Surge Immunity (801-5) Class III: 2 kV common and 1 kV differential mode

Coil Surge Protection

Environmental Temperature

Operating

–40…+55 °C

Storage

–40…100 °C

Altitude

2000 m (6560 ft) Construction

Insulating Material

Molded High Dielectric Material

Enclosure

Relay IP67 Silver Tin Ox., AgSnO2 or Silver with Gold Plating, AgSnO2 + Au

Contact Material Terminal Markings on Socket

In accordance with EN50 0005

Certifications cULus Listed (File No. E3125, Guide NLDX/NLDX7) with Allen-Bradley socket, CE Marked, ABS (American Bureau of Shipping)

Standards

EN 61810-1, CSA 22.2,UL 508,NEMA IEE MAC Compliant, ICS-2 Compliant Class 1, Zn 2, Groups IIC, Ex nC IIC T5 Ta < 55 °C

Hazardous Location Approvals

20

UL Listed (UL 60079-15)

700-HLT1Z12-EX (12V DC supply) 700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply) 700-HLT1U1-EX, 700-HLS1U1-EX (110V/125V AC/DC supply)

CSA Certified‡ (CAN/CSA E60079-15)

700-HLT1Z12-EX (12V DC supply) 700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)

Rockwell Automation Publication 700-TD552A-EN-P