The text of a spec sheet · part 3 of 13
Relays and Timers Specifications, Bulletin Number 700, pages 21 to 30
Pages 21 to 30 of 128
The original document is the PDF (10 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HN122
Page 21
Relays and Timer Specifications
700-HLS Relay Cat. No. 700-HLS… (Solid State Output) Electrical
Rated Thermal Current (Ith)
2 A (DC output)
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA
Control Circuit
Outputs
Power Consumption ±10%
1 A (AC output)
Min. Control Voltage
80% nominal voltage
Maximum Control Voltage
110% nominal voltage
Control Current
9 mA ±10% (24V) 4 mA ±10% (120/240V)
Release Voltage
0.4 x nominal voltage (24V), 0.35 x nominal voltage (120/240V)
Min. Control Circuit Resistance
3200 ohms (24V), 16k ohms (120V), 32k ohms (240V)
2500 ohms (24V), 12k ohms (120V), 24k ohms (240V)
Load Voltage Range
0…24V DC
24…240V AC
Max. Repetitive Blocking Voltage
33V
600V
Max. Switching Current (inductive/resistive)
2 A DC
1 A AC
On State Voltage Drop @ Max. Switching Current
<120 mV DC
<1V AC
Leakage Current max. 100 μA (@U = 24V)
AC
0.6 VA (120V), 1 VA (240V)
DC
0.2 W
0.3 W
Design Specification/Test Requirements Dielectric Withstand Voltage Input Voltage Impedance (Ohms)
Pole to Pole (VRMS)
2500V
Contact to Coil (VRMS)
2500V
24V DC
48V DC
120V AC/DC
240V AC/DC
120V LCSC
240V LCSC
2K
9K
26 K
58 K
16 K
35 K
Mechanical Degree of Protection
IP20
Input Voltages Operating Time at Nominal Voltage at 20 °C (ms)
See Overview/Product Selection Turn on Time
30 μs (DC only input voltage), 7 ms (AC/DC input voltage)
Drop Out Time
350 μs (DC only input voltage), 10 ms (AC/DC input voltage)
Maximum Operating Rate
300 Hz Environmental
Temperature
Operating
–20…+55 °C
Storage
–40…70 °C
Altitude
2000 m (6560 ft) Construction
Insulating Material
Molded High-Dielectric Material
Enclosure
Relay IP67
Terminal Markings on Socket Certifications
In accordance with EN50 0005 cULus Listed (File No. E14843, Guide NLDX/NLDX7), CE Marked, ABS (American Bureau of Shipping)
Standards
UL 508, CSA C22.2 No. 14, EN 61810-1 Class 1, Zn 2, Groups IIC, Ex nC IIC T5 Ta < 55 °C
Hazardous Location Approvals
UL Listed (UL 60079-15)
700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply) 700-HLT1U1-EX, 700-HLS1U1-EX (110V/125V AC/DC supply)
CSA (CAN/CSA 60079-15)
700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)
Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.
Rockwell Automation Publication 700-TD552A-EN-P
21
Page 22
700-HL Relay
Relays and Timer Specifications
Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
76.0 (2.99)
76.0 (2.99)
93.0 (3.66)
88.0 (3.46)
6.2 (0.24)
6.2 (0.24)
Bulletin 700-HL Spring Terminal Design Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…#14 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in.)
12.5 (1/2)
6.2 (15/64)
50 (1-63/64)
5.2 (13/64)
1.0 (0.04)
35.0 (1.38)
27.0 (1.06)
7.5 (0.3)
1000 (39-3/8)
Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes
Cat. No.
A
B
C
D
Approx. Shipping Wt.
199-DR1
35 (1-3/8)
27 (1-1/16)
7.5 (19/64)
1.02 (1/64)
1.85 kg (4.07 lb) (10/pkg)
199-DR4
35 (1-3/8)
27 (1-1/16)
15 (19/32)
2.3 (3/32)
3.68 kg (8 lb) (5/pkg)
22
Rockwell Automation Publication 700-TD552A-EN-P
Page 23
Relays and Timer Specifications
700-HLT Relay Cat. No. 700-HLT…2-Pole (Relay Output) Electrical Ratings
Rated Thermal Current (Ith)
2-Pole, 10 A
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA
Inductive V AC UL
Contacts
Inductive V DC Resistive Make, Break and Continuous
Min. Permissible Contact Ratings
120V AC
AC-15, 3.0A B 300, 3.0 A
1/4 HP (186 W), 1-phase
240V AC
AC-15, 3.0 A B 300, 1.5 A
1/2 HP (373 W), 1-phase
24V DC
DC-13, 2.0 A
125V DC
DC-13, 0.3 A
250V DC
DC-13, 0.2 A
250V AC
10 A
24V DC
10 A
250V DC
0.28 A
12V, 10 mA (120 mW) for Silver Contacts, 5V, 1 mA (50 mW) for Gold Contacts
Pickup: Permissible Coil Voltage Variation
85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC
Must Dropout Voltage:
10% of Nominal Voltage at AC 5% of Nominal Voltage at DC
Design Specification/Test Requirements
Dielectric Withstand Voltage
Input Voltage
±10%
1000V
Contact to Coil (VRMS)
5000V
Adjacent Contacts (VRMS)
2500V
12V AC/DC
24V AC/DC
48V DC
120V AC/DC
1K
2K
3K
34 K
72 K
AC
N/A
0.5V A
N/A
0.4V A
0.8V A
DC
0.4 W
0.5 W
0.8 W
0.5 W
0.7 W
Impedance (Ohms) Power Consumption
Pole to Pole (VRMS)
240V AC/DC
Mechanical Degree of Protection
IP20
Mechanical Life Operations
3 x 107 250V AC/24V DC, 8 A Resistive: 100 000 min. 24V DC, 10 A Resistive: 6000 min.
Electrical Life Operations 250V DC, 0.28 A Resistive: 6000 min. 250V AC, 10 A Resistive: 30 000 min. Switching Frequency Operations (no-load)
1200 cycles/sec
Coil Voltages Operating Time at Nominal Voltage at 20 °C (ms)
See Overview/Product Selection Pickup typical 10 ms
Dropout typical 10 ms
Maximum Operating Rate (full load = 6 A)
6 cycles/min. Environmental
Temperature
Operating
–40…+60 °C
Storage
–40…+100 °C
Altitude
2000 m (6560 ft) Construction
Insulating Material Enclosure Contact Material Terminal Markings on Socket
Molded High-Dielectric Material Relay RT II, flux-proof, pollution degree 2 installation environment AgNi 90/10 or AgNi 90/10 + Au In accordance with EN50 0005
Certifications cULus Listed (File No. E3125, Guide NRNT/NRNT7), CE Marked
Standards
UL 508, CSA C22.2 No. 14, EN 61810-1
Rockwell Automation Publication 700-TD552A-EN-P
23
Page 24
700 Interposing Relays
Relays and Timer Specifications
Approximate Dimensions Approximate dimensions are shown in millimeters (inches). Approximate dimensions are not intended to be used for manufacturing purposes.
92.8 (3.65)
87.7 (3.45)
14 (0.55)
14 (0.55)
75 (2.95)
75 (2.95)
Bulletin 700-HL Screw Terminal Design Single Wire: 0.14 mm2…2.5 mm2 (#26 AWG…14 AWG) Double Wire: 2 x 0.14 mm2…2 x 1.5 mm2 (2 x #26 AWG…2 x 16 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in). Torque: 0.5 N•m (4.4 lb•in)
Bulletin 700-HL Spring Terminal Design Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…#14 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in)
97.8 (3.85)
Bulletin 700-TBJ08_ 8-Way Jumper 6.2 (15/64)
50 (1-63/64)
5.2 (13/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38)
27.0 (1.06)
7.5 (0.3)
1000 (39-3/8)
Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes
Cat. No.
A
B
C
D
Approx. Shipping Wt.
199-DR1
35 (1-3/8)
27 (1-1/16)
7.5 (19/64)
1.02 (1/64)
1.85 kg (4.07 lb) (10/pkg)
199-DR4
35 (1-3/8)
27 (1-1/16)
15 (19/32)
2.3 (3/32)
3.68 kg (8 lb) (5/pkg)
24
Rockwell Automation Publication 700-TD552A-EN-P
Page 25
Relays and Timer Specifications
700 Interposing Relays
Function and Connection Diagrams On-Delay 15
A1 U (A1/A2)
1 c/o (SPST) t
R LED
A2
18 16
One Shot 15
A1 U (A1/A2)
U (A1/A2)
1 c/o (SPST)
R t
R
1 c/o15 (SPST)
A1 t
LED t t A2
LED
18 16
A2
18 16
Pulse A1
15
U (A1/A2)
1 c/o (SPST) t
R 0.5s LED
A2
18 16
Flasher
Rockwell Automation Publication 700-TD552A-EN-P
25
Page 26
700-HLF Relay
Relays and Timer Specifications
Specifications Cat. No. 700-HLF… (Relay Output) Electrical Ratings Pilot Duty Rating
B 300, R 300
Rated Thermal Current (Ith)
1-Pole, 6 A
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA Inductive
Contacts
1-Pole
24V AC, 1-phase
30 A
5A
120V AC, 1-phase
30 A
3A
240V AC, 1-phase
15 A
1.5 A
Make, Break & Continuous V DC
1.0 A
120V DC
0.2 A
240V DC
0.1 A
AC-15 250V, 3 A N.O. Contact, 1.5 A N.C. Contact DC-13 24V, 1 A N.O. and N.C. Contact
Inductive Load Min. Permissible Contact Ratings
12V, 6 mA (72 mW) for Silver Contacts, 8V, 2.5 mA (20 mW) for Gold Contacts Pickup:
85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC
Permissible Coil Voltage Variation
Power Consumption ±10%
24V DC
AC/DC
Must Dropout Voltage:
10% of Nominal Voltage at AC 5% of Nominal Voltage at DC
0.5 VA
Design Specification/Test Requirements
Dielectric Withstand Voltage
Pole to Pole (VRMS)
1000V
Contact to Coil (VRMS)
4000V
Input Voltage
24V AC/DC
Impedance (Ohms)
2K Mechanical
Degree of Protection
IP20
Mechanical Life Operations
1 x 107
Electrical Life Operations
6 A Resistive: 100 000 min. 24V DC, 1 A Inductive: 200 000 min. 120V AC 1 A Inductive: 300 000 min.
Switching Frequency Operations (no-load)
10 cycles/sec
Coil Voltages
See Overview/Product Selection
Timer Functions
On-Delay, One Shot, Pulse and Flasher
Timer Settings
0.1...3 s, 3...60 s, 1...20 min, and 0.3...6 hr
Timer Adjustments
Min and Max adjustments with Potentionmeter
Timer Accuracy
Repeatability 1%, Recovery Time < 50 ms, Setting Accuracy Full Range 5% Per EN 61000-4.5; Surge Immunity (801-5) Class III: 2 kV common and 1 kV differential mode
Coil Surge Protection
Environmental Temperature
Operating
–40…55 °C
Storage
–40…100 °C
Altitude
2000 m (6560 ft) Construction
Insulating Material Enclosure Contact Material Terminal Markings on Socket
Molded High Dielectric Material Relay IP67 Silver Tin Ox., AgSnO2 or Silver with Gold Plating, AgSnO2 + Au In accordance with EN50 0005
Certifications cULus Listed (File No. E3125, Guide NLDX/NLDX7) with Allen-Bradley socket, CE Marked
Standards
EN60947-4-1,EN60947-5-1,CSA 22.2,UL 508,NEMA IEE MAC Compliant, ICS-2 Compliant
‡ Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.
26
Rockwell Automation Publication 700-TD552A-EN-P
Page 27
Relays and Timer Specifications
700-HLF
Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes. 76.0 (2.99)
6.20 (0.24)
88.0 (3.46)
Bulletin 700-HLF Screw Terminal Design Single Wire: 0.14 mm2…2.5 mm2 (#26 AWG…14 AWG) Double Wire: 2 x 0.14 mm2…2 x 1.5 mm2 (2 x #26 AWG…2 x 16 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in.). Torque: 0.5 N•m (4.4 lb•in)
6.2 (15/64)
50 (1-63/64)
5.2 (13/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38)
27.0 (1.06)
7.5 (0.3)
1000 (39-3/8) Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes
Cat. No.
A
B
C
D
Approx. Shipping Wt.
199-DR1
35 (1-3/8)
27 (1-1/16)
7.5 (19/64)
1.02 (1/64)
1.85 kg (4.07 lb) (10/pkg)
199-DR4
35 (1-3/8)
27 (1-1/16)
15 (19/32)
2.3 (3/32)
3.68 kg (8 lb) (5/pkg)
Bulletin 700-HP Pin Style (PCB) Slim Line Relay, Socket, and Retainer Clip Reference Chart Relay Type
Socket Cat. No.
700-HPX2
700-HN123
700-HN119
700-HP32
700-HN123
700-HN119
700-HPS2
700-HN123
700-HN119
700-HPSX
700-HN123
700-HN119
Rockwell Automation Publication 700-TD552A-EN-P
Retainer Clip Cat. No.
27
Page 28
700-HP Relay
Relays and Timer Specifications
Specifications 1 Cat. No. 700-HP…
Cat. No. 700-HP3…, 700-HPX
Cat. No. 700-HPS…
AC 15 @ 500V AC V AC
C300
B300
1/3 Hp @ 240V AC
1/2 Hp @ 240V AC
1/6 Hp @ 120V AC
1/3 Hp @ 120V AC AC-1 2000VA
Inductive
⎯
R300 Contacts
V DC
Resistive
DC-1: 8A @ 30V DC DC-1: 0.3A @ 110V DC
DC-1: 0.65A @ 110V DC
DC-1: 0.1A @ 220V DC
DC-1: 0.2A @ 220V DC
AC
8 A @ 277V AC (per pole)
DC
8 A @ 30V DC (per pole) 700-HPS2: 500 mW (10V, 10 mA) 700-HPSX: 50 mW (5V, 5 mA)
700-HP32: 300mW (5V, 5 mA) 700-HPX2: 50mW (5V, 5 mA)
Minimum Load Nominal Coil Power (AC/DC)
1.2 VA / 0.65 W
0.7 W
Operating Range (AC/DC)
80...110% / 73...150% Nominal Voltage
75...120% Nominal Voltage DC
Holding Voltage (AC/DC)
80 / 40% Nominal Voltage
40% Nominal Voltage DC
Must Drop Out Voltage (AC/DC)
20 / 10% Nominal Voltage
10% Nominal Voltage DC
Insulation Voltage
250V AC Design Specification/Test Requirements
Dielectric Withstand Voltage for one minute
700-HP3, 700-HPX
Pole to Pole (VRMS)
700-HPS 2000V AC
Contact to Coil (VRMS)
4000V AC Mechanical
Degree of Protection
Open Type (Sockets)
Mechanical Life Cycles Switching Frequency Operations
10 x 106 (AC Coils), 20 x 106 (DC coils)
10 x 106 (DC Coils)
1800/hr (no load)
900/hr (no load)
Coil Voltages Operating Time at Nominal Voltage at 20 °C (ms)
See Overview/Product Selection Pickup
12 4
Maximum Operating Rate Vibration Shock
10
Dropout 16 Ops/s (full load)
8 Ops/s (full load)
Enclosure
5G
Fragility
2.5 G
Endurance
50 G
Fragility
15 G
Max. Socket Torque
0.5 N•m (4.4 lb•in) Environmental
Temperature
Operating
–40…+85 °C
Storage
–45…+100 °C
Altitude
–40…+70 °C –50…+80 °C 2000 m (6560 ft)
Construction Insulating Material
Molded High-Dielectric Material
Enclosure
Transparent Dust Cover
Red Transparent Dust Cover
Silver Nickel, (AgNi) (700-HP32 and 700-HPS2), Silver Nickel + Gold Plating (AgNi + Au) (700-HPX2 and 700-HPSX)
Contact Material Terminal Markings on Socket
In accordance with EN50 0005 2-Pole
Sockets
700-HN123 Approvals
Certifications cURus Recognized (File No. E3125, Guide NLDX2/NLDX8), cULus Listed when used with Bulletin 700-HN123 socket (File No. E3125, Guide NLDX/NLDC7), CSA Certified (files 229473), CE Marked, LR Certified (700-HP), IMQ & TUV Certified (700HPS)
Standards
UL 508, CSA 22.2 No. 14, EN 61810-1, EN 50205 (700-HPS)
‡ NEMA Rating Chart is in publication 700-SG003* § The inrush VA equals 1.5 times the sealed VA.
28
Rockwell Automation Publication 700-TD552A-EN-P
Page 29
Relays and Timer Specifications
700-HP Relay
Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
29.0 (1.14)
12.4 (0.49)
25.0 (0.98)
Bulletin 700-HP Relay
6.2 (15/64)
50 (1-63/64)
5.2 (13/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38)
27.0 (1.06)
7.5 (0.3)
1000 (39-3/8) Cat. No. 700-HN123 Single Wire: 0.2.....2.5 mm2 (#24.....14 AWG) Double Wire: 2 X 0.2.....2 X 2.5 mm2 (#2 X 24....2 X 14 AWG) Wire Type: solid or stranded, copper only Strip Length: 7 mm (9/32 in.), Torque: 0.5 N•m (4.4 lb•in)
Cat. No.
A
B
C
D
Approx. Shipping Wt.
199-DR1
35 (1-3/8)
27 (1-1/16)
7.5 (19/64)
1.02 (1/64)
1.85 kg (4.07 lb) (10/pkg)
199-DR4
35 (1-3/8)
27 (1-1/16)
15 (19/32)
2.3 (3/32)
3.68 kg (8 lb) (5/pkg)
Rockwell Automation Publication 700-TD552A-EN-P
29
Page 30
700 Interposing Relays
Relays and Timer Specifications
21 6
11 3
24 5
14 4
22 7
12 2
17.5 (0.69)
60.9 (2.40) 17.5 (0.69)
21.6 (0.85)
Ø 3.2 (0.12) Use M3 Screws
78.6 (3.09)
8 (+) A1
1 (-) A2
4.0 (0.16) 15.8 (0.62)
Cat. No. 700-HN123 Single Wire: 0.2.....2.5 mm2 (#24.....14 AWG) Double Wire: 2 X 0.2.....2 X 2.5 mm2 (#2 X 24....2 X 14 AWG) Wire Type: solid or stranded, copper only Strip Length: 7 mm (9/32 in.), Torque: 0.5 N•m (4.4 lb•in)
30
Rockwell Automation Publication 700-TD552A-EN-P
35.4 (1.39)
21.6 (0.85)