For the Allen-Bradley 700-HN122

Page 21

Relays and Timer Specifications

700-HLS Relay Cat. No. 700-HLS… (Solid State Output) Electrical

Rated Thermal Current (Ith)

2 A (DC output)

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA

Control Circuit

Outputs

Power Consumption ±10%

1 A (AC output)

Min. Control Voltage

80% nominal voltage

Maximum Control Voltage

110% nominal voltage

Control Current

9 mA ±10% (24V) 4 mA ±10% (120/240V)

Release Voltage

0.4 x nominal voltage (24V), 0.35 x nominal voltage (120/240V)

Min. Control Circuit Resistance

3200 ohms (24V), 16k ohms (120V), 32k ohms (240V)

2500 ohms (24V), 12k ohms (120V), 24k ohms (240V)

Load Voltage Range

0…24V DC

24…240V AC

Max. Repetitive Blocking Voltage

33V

600V

Max. Switching Current (inductive/resistive)

2 A DC

1 A AC

On State Voltage Drop @ Max. Switching Current

<120 mV DC

<1V AC

Leakage Current max. 100 μA (@U = 24V)

AC

0.6 VA (120V), 1 VA (240V)

DC

0.2 W

0.3 W

Design Specification/Test Requirements Dielectric Withstand Voltage Input Voltage Impedance (Ohms)

Pole to Pole (VRMS)

2500V

Contact to Coil (VRMS)

2500V

24V DC

48V DC

120V AC/DC

240V AC/DC

120V LCSC

240V LCSC

2K

9K

26 K

58 K

16 K

35 K

Mechanical Degree of Protection

IP20

Input Voltages Operating Time at Nominal Voltage at 20 °C (ms)

See Overview/Product Selection Turn on Time

30 μs (DC only input voltage), 7 ms (AC/DC input voltage)

Drop Out Time

350 μs (DC only input voltage), 10 ms (AC/DC input voltage)

Maximum Operating Rate

300 Hz Environmental

Temperature

Operating

–20…+55 °C

Storage

–40…70 °C

Altitude

2000 m (6560 ft) Construction

Insulating Material

Molded High-Dielectric Material

Enclosure

Relay IP67

Terminal Markings on Socket Certifications

In accordance with EN50 0005 cULus Listed (File No. E14843, Guide NLDX/NLDX7), CE Marked, ABS (American Bureau of Shipping)

Standards

UL 508, CSA C22.2 No. 14, EN 61810-1 Class 1, Zn 2, Groups IIC, Ex nC IIC T5 Ta < 55 °C

Hazardous Location Approvals

UL Listed (UL 60079-15)

700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply) 700-HLT1U1-EX, 700-HLS1U1-EX (110V/125V AC/DC supply)

CSA (CAN/CSA 60079-15)

700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)

Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.

Rockwell Automation Publication 700-TD552A-EN-P

21

Page 22

700-HL Relay

Relays and Timer Specifications

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

76.0 (2.99)

76.0 (2.99)

93.0 (3.66)

88.0 (3.46)

6.2 (0.24)

6.2 (0.24)

Bulletin 700-HL Spring Terminal Design Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…#14 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in.)

12.5 (1/2)

6.2 (15/64)

50 (1-63/64)

5.2 (13/64)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

7.5 (0.3)

1000 (39-3/8)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No.

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lb) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lb) (5/pkg)

22

Rockwell Automation Publication 700-TD552A-EN-P

Page 23

Relays and Timer Specifications

700-HLT Relay Cat. No. 700-HLT…2-Pole (Relay Output) Electrical Ratings

Rated Thermal Current (Ith)

2-Pole, 10 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA

Inductive V AC UL

Contacts

Inductive V DC Resistive Make, Break and Continuous

Min. Permissible Contact Ratings

120V AC

AC-15, 3.0A B 300, 3.0 A

1/4 HP (186 W), 1-phase

240V AC

AC-15, 3.0 A B 300, 1.5 A

1/2 HP (373 W), 1-phase

24V DC

DC-13, 2.0 A

125V DC

DC-13, 0.3 A

250V DC

DC-13, 0.2 A

250V AC

10 A

24V DC

10 A

250V DC

0.28 A

12V, 10 mA (120 mW) for Silver Contacts, 5V, 1 mA (50 mW) for Gold Contacts

Pickup: Permissible Coil Voltage Variation

85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC

Must Dropout Voltage:

10% of Nominal Voltage at AC 5% of Nominal Voltage at DC

Design Specification/Test Requirements

Dielectric Withstand Voltage

Input Voltage

±10%

1000V

Contact to Coil (VRMS)

5000V

Adjacent Contacts (VRMS)

2500V

12V AC/DC

24V AC/DC

48V DC

120V AC/DC

1K

2K

3K

34 K

72 K

AC

N/A

0.5V A

N/A

0.4V A

0.8V A

DC

0.4 W

0.5 W

0.8 W

0.5 W

0.7 W

Impedance (Ohms) Power Consumption

Pole to Pole (VRMS)

240V AC/DC

Mechanical Degree of Protection

IP20

Mechanical Life Operations

3 x 107 250V AC/24V DC, 8 A Resistive: 100 000 min. 24V DC, 10 A Resistive: 6000 min.

Electrical Life Operations 250V DC, 0.28 A Resistive: 6000 min. 250V AC, 10 A Resistive: 30 000 min. Switching Frequency Operations (no-load)

1200 cycles/sec

Coil Voltages Operating Time at Nominal Voltage at 20 °C (ms)

See Overview/Product Selection Pickup typical 10 ms

Dropout typical 10 ms

Maximum Operating Rate (full load = 6 A)

6 cycles/min. Environmental

Temperature

Operating

–40…+60 °C

Storage

–40…+100 °C

Altitude

2000 m (6560 ft) Construction

Insulating Material Enclosure Contact Material Terminal Markings on Socket

Molded High-Dielectric Material Relay RT II, flux-proof, pollution degree 2 installation environment AgNi 90/10 or AgNi 90/10 + Au In accordance with EN50 0005

Certifications cULus Listed (File No. E3125, Guide NRNT/NRNT7), CE Marked

Standards

UL 508, CSA C22.2 No. 14, EN 61810-1

Rockwell Automation Publication 700-TD552A-EN-P

23

Page 24

700 Interposing Relays

Relays and Timer Specifications

Approximate Dimensions Approximate dimensions are shown in millimeters (inches). Approximate dimensions are not intended to be used for manufacturing purposes.

92.8 (3.65)

87.7 (3.45)

14 (0.55)

14 (0.55)

75 (2.95)

75 (2.95)

Bulletin 700-HL Screw Terminal Design Single Wire: 0.14 mm2…2.5 mm2 (#26 AWG…14 AWG) Double Wire: 2 x 0.14 mm2…2 x 1.5 mm2 (2 x #26 AWG…2 x 16 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in). Torque: 0.5 N•m (4.4 lb•in)

Bulletin 700-HL Spring Terminal Design Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…#14 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in)

97.8 (3.85)

Bulletin 700-TBJ08_ 8-Way Jumper 6.2 (15/64)

50 (1-63/64)

5.2 (13/64)

12.5 (1/2)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

7.5 (0.3)

1000 (39-3/8)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No.

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lb) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lb) (5/pkg)

24

Rockwell Automation Publication 700-TD552A-EN-P

Page 25

Relays and Timer Specifications

700 Interposing Relays

Function and Connection Diagrams On-Delay 15

A1 U (A1/A2)

1 c/o (SPST) t

R LED

A2

18 16

One Shot 15

A1 U (A1/A2)

U (A1/A2)

1 c/o (SPST)

R t

R

1 c/o15 (SPST)

A1 t

LED t t A2

LED

18 16

A2

18 16

Pulse A1

15

U (A1/A2)

1 c/o (SPST) t

R 0.5s LED

A2

18 16

Flasher

Rockwell Automation Publication 700-TD552A-EN-P

25

Page 26

700-HLF Relay

Relays and Timer Specifications

Specifications Cat. No. 700-HLF… (Relay Output) Electrical Ratings Pilot Duty Rating

B 300, R 300

Rated Thermal Current (Ith)

1-Pole, 6 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA Inductive

Contacts

1-Pole

24V AC, 1-phase

30 A

5A

120V AC, 1-phase

30 A

3A

240V AC, 1-phase

15 A

1.5 A

Make, Break & Continuous V DC

1.0 A

120V DC

0.2 A

240V DC

0.1 A

AC-15 250V, 3 A N.O. Contact, 1.5 A N.C. Contact DC-13 24V, 1 A N.O. and N.C. Contact

Inductive Load Min. Permissible Contact Ratings

12V, 6 mA (72 mW) for Silver Contacts, 8V, 2.5 mA (20 mW) for Gold Contacts Pickup:

85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC

Permissible Coil Voltage Variation

Power Consumption ±10%

24V DC

AC/DC

Must Dropout Voltage:

10% of Nominal Voltage at AC 5% of Nominal Voltage at DC

0.5 VA

Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole to Pole (VRMS)

1000V

Contact to Coil (VRMS)

4000V

Input Voltage

24V AC/DC

Impedance (Ohms)

2K Mechanical

Degree of Protection

IP20

Mechanical Life Operations

1 x 107

Electrical Life Operations

6 A Resistive: 100 000 min. 24V DC, 1 A Inductive: 200 000 min. 120V AC 1 A Inductive: 300 000 min.

Switching Frequency Operations (no-load)

10 cycles/sec

Coil Voltages

See Overview/Product Selection

Timer Functions

On-Delay, One Shot, Pulse and Flasher

Timer Settings

0.1...3 s, 3...60 s, 1...20 min, and 0.3...6 hr

Timer Adjustments

Min and Max adjustments with Potentionmeter

Timer Accuracy

Repeatability 1%, Recovery Time < 50 ms, Setting Accuracy Full Range 5% Per EN 61000-4.5; Surge Immunity (801-5) Class III: 2 kV common and 1 kV differential mode

Coil Surge Protection

Environmental Temperature

Operating

–40…55 °C

Storage

–40…100 °C

Altitude

2000 m (6560 ft) Construction

Insulating Material Enclosure Contact Material Terminal Markings on Socket

Molded High Dielectric Material Relay IP67 Silver Tin Ox., AgSnO2 or Silver with Gold Plating, AgSnO2 + Au In accordance with EN50 0005

Certifications cULus Listed (File No. E3125, Guide NLDX/NLDX7) with Allen-Bradley socket, CE Marked

Standards

EN60947-4-1,EN60947-5-1,CSA 22.2,UL 508,NEMA IEE MAC Compliant, ICS-2 Compliant

‡ Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.

26

Rockwell Automation Publication 700-TD552A-EN-P

Page 27

Relays and Timer Specifications

700-HLF

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes. 76.0 (2.99)

6.20 (0.24)

88.0 (3.46)

Bulletin 700-HLF Screw Terminal Design Single Wire: 0.14 mm2…2.5 mm2 (#26 AWG…14 AWG) Double Wire: 2 x 0.14 mm2…2 x 1.5 mm2 (2 x #26 AWG…2 x 16 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in.). Torque: 0.5 N•m (4.4 lb•in)

6.2 (15/64)

50 (1-63/64)

5.2 (13/64)

12.5 (1/2)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

7.5 (0.3)

1000 (39-3/8) Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No.

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lb) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lb) (5/pkg)

Bulletin 700-HP Pin Style (PCB) Slim Line Relay, Socket, and Retainer Clip Reference Chart Relay Type

Socket Cat. No.

700-HPX2

700-HN123

700-HN119

700-HP32

700-HN123

700-HN119

700-HPS2

700-HN123

700-HN119

700-HPSX

700-HN123

700-HN119

Rockwell Automation Publication 700-TD552A-EN-P

Retainer Clip Cat. No.

27

Page 28

700-HP Relay

Relays and Timer Specifications

Specifications 1 Cat. No. 700-HP…

Cat. No. 700-HP3…, 700-HPX

Cat. No. 700-HPS…

AC 15 @ 500V AC V AC

C300

B300

1/3 Hp @ 240V AC

1/2 Hp @ 240V AC

1/6 Hp @ 120V AC

1/3 Hp @ 120V AC AC-1 2000VA

Inductive

⎯

R300 Contacts

V DC

Resistive

DC-1: 8A @ 30V DC DC-1: 0.3A @ 110V DC

DC-1: 0.65A @ 110V DC

DC-1: 0.1A @ 220V DC

DC-1: 0.2A @ 220V DC

AC

8 A @ 277V AC (per pole)

DC

8 A @ 30V DC (per pole) 700-HPS2: 500 mW (10V, 10 mA) 700-HPSX: 50 mW (5V, 5 mA)

700-HP32: 300mW (5V, 5 mA) 700-HPX2: 50mW (5V, 5 mA)

Minimum Load Nominal Coil Power (AC/DC)

1.2 VA / 0.65 W

0.7 W

Operating Range (AC/DC)

80...110% / 73...150% Nominal Voltage

75...120% Nominal Voltage DC

Holding Voltage (AC/DC)

80 / 40% Nominal Voltage

40% Nominal Voltage DC

Must Drop Out Voltage (AC/DC)

20 / 10% Nominal Voltage

10% Nominal Voltage DC

Insulation Voltage

250V AC Design Specification/Test Requirements

Dielectric Withstand Voltage for one minute

700-HP3, 700-HPX

Pole to Pole (VRMS)

700-HPS 2000V AC

Contact to Coil (VRMS)

4000V AC Mechanical

Degree of Protection

Open Type (Sockets)

Mechanical Life Cycles Switching Frequency Operations

10 x 106 (AC Coils), 20 x 106 (DC coils)

10 x 106 (DC Coils)

1800/hr (no load)

900/hr (no load)

Coil Voltages Operating Time at Nominal Voltage at 20 °C (ms)

See Overview/Product Selection Pickup

12 4

Maximum Operating Rate Vibration Shock

10

Dropout 16 Ops/s (full load)

8 Ops/s (full load)

Enclosure

5G

Fragility

2.5 G

Endurance

50 G

Fragility

15 G

Max. Socket Torque

0.5 N•m (4.4 lb•in) Environmental

Temperature

Operating

–40…+85 °C

Storage

–45…+100 °C

Altitude

–40…+70 °C –50…+80 °C 2000 m (6560 ft)

Construction Insulating Material

Molded High-Dielectric Material

Enclosure

Transparent Dust Cover

Red Transparent Dust Cover

Silver Nickel, (AgNi) (700-HP32 and 700-HPS2), Silver Nickel + Gold Plating (AgNi + Au) (700-HPX2 and 700-HPSX)

Contact Material Terminal Markings on Socket

In accordance with EN50 0005 2-Pole

Sockets

700-HN123 Approvals

Certifications cURus Recognized (File No. E3125, Guide NLDX2/NLDX8), cULus Listed when used with Bulletin 700-HN123 socket (File No. E3125, Guide NLDX/NLDC7), CSA Certified (files 229473), CE Marked, LR Certified (700-HP), IMQ & TUV Certified (700HPS)

Standards

UL 508, CSA 22.2 No. 14, EN 61810-1, EN 50205 (700-HPS)

‡ NEMA Rating Chart is in publication 700-SG003* § The inrush VA equals 1.5 times the sealed VA.

28

Rockwell Automation Publication 700-TD552A-EN-P

Page 29

Relays and Timer Specifications

700-HP Relay

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

29.0 (1.14)

12.4 (0.49)

25.0 (0.98)

Bulletin 700-HP Relay

6.2 (15/64)

50 (1-63/64)

5.2 (13/64)

12.5 (1/2)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

7.5 (0.3)

1000 (39-3/8) Cat. No. 700-HN123 Single Wire: 0.2.....2.5 mm2 (#24.....14 AWG) Double Wire: 2 X 0.2.....2 X 2.5 mm2 (#2 X 24....2 X 14 AWG) Wire Type: solid or stranded, copper only Strip Length: 7 mm (9/32 in.), Torque: 0.5 N•m (4.4 lb•in)

Cat. No.

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lb) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lb) (5/pkg)

Rockwell Automation Publication 700-TD552A-EN-P

29

Page 30

700 Interposing Relays

Relays and Timer Specifications

21 6

11 3

24 5

14 4

22 7

12 2

17.5 (0.69)

60.9 (2.40) 17.5 (0.69)

21.6 (0.85)

Ø 3.2 (0.12) Use M3 Screws

78.6 (3.09)

8 (+) A1

1 (-) A2

4.0 (0.16) 15.8 (0.62)

Cat. No. 700-HN123 Single Wire: 0.2.....2.5 mm2 (#24.....14 AWG) Double Wire: 2 X 0.2.....2 X 2.5 mm2 (#2 X 24....2 X 14 AWG) Wire Type: solid or stranded, copper only Strip Length: 7 mm (9/32 in.), Torque: 0.5 N•m (4.4 lb•in)

30

Rockwell Automation Publication 700-TD552A-EN-P

35.4 (1.39)

21.6 (0.85)