For the Allen-Bradley 700-HN122

Page 31

Relays and Timer Specifications

700-HJ Magnetic Latching Relays

Specifications Cat. No. 700-HJ… Electrical Ratings Pilot Duty Rating, th

Rated Thermal Current (I )

10 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA Inductive 120V AC 240V AC

Contacts

Make

Break

Hp

30 A 15 A

3A 1.5 A

1/4 1/3

DC

24V DC, 10 A 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC

Permissible Coil Voltage Variation

AC Coils Coil Consumption ±10%

Inrush Sealed

DC Coils

Single AC Coil

Single DC Coil

Dual DC Coil

1.44 VA 1.44 VA, - - 1.2 W

12V 1.63 W 24V 1.67 W

Design Specification/Test Requirements Dielectric Withstand Voltage

Pole-to-Pole

1500V AC

Contact-to-Pole

1500V AC

Contact-to-Frame

1500V AC Mechanical Open Type (Guarded Terminal Sockets)

Degree of Protection Mechanical Life Operations

10 x 106

Switching Frequency Operations

1800/HR

Coil Voltages

See Product Selection

Operating Time at Nominal Voltage at 20 °C

Pickup Dropout

25 ms 25 ms

Maximum Operating Rate, Environmental Operating

–45…+50 °C (–49…+122 °F)

Storage

–45…+100 °C (–49…+212 °F)

Temperature

Altitude

2000 m (6560 ft.) Construction

Insulating Material Enclosure Contact Material Terminal Markings on Socket Sockets

Molded High Dielectric Material Transparent Dust Cover Silver Cad. Ox. In accordance with EN50 0005 11-Blade Socket Cat. No. 700-HN153 Cat. No. 700-HN154

Certifications

CSA Certified, File LR700026, UL Recognized, File E3125, Guide NLDX 2

Standards

UL 508, CSA 22.2 No. 14, EN/IEC 60947-4-1, -5-1

Rockwell Automation Publication 700-TD552A-EN-P

31

Page 32

700-HJ Magnetic Latching Relays

Relays and Timer Specifications

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

Bulletin 700-HJ Relay

Cat. No. 700-HN153 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)

Cat. No. 700-HN154 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)

6.2 (15/64)

50 (1-63/64)

5.2 (13/64)

12.5 (1/2)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

7.5 (0.3)

1000 (39-3/8)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

32

Cat. No.

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lbs.) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lbs.) (5/pkg)

Rockwell Automation Publication 700-TD552A-EN-P

Page 33

Relays and Timer Specifications

700-HG Power Relays

Specifications Cat. No. 700-HG... Electrical Ratings Pilot Duty Rating ‡

A600

Rated Thermal Current (/th)

40 A

Rated Insulation Voltage (Ui)

600V UL

Contact Ratings: AC Ratings SPST-NO-DM

Contact Ratings: AC Ratings SPDT, DPST - NO and DPDT

Inductive Volts

Make

Resistive Make/Break HP Volts and Continuous Continuous

Break

120

60 A

6A

10 A

40 A

240

30 A

3A

10 A

40 A

480

15 A

1.5 A

10 A

12 A

600

12 A

1.2 A

10 A

10 A

DC Ratings: Without Magnetic Blowouts - 28V 40 A - Make, Break and Continuous

2

Make

Break

Resistive Make/Break and Continuous Continuous

120

60 A

6A

10 A

40 A

240

30 A

3A

10 A

40 A

480

15 A

1.5 A

10 A

5A

600

12 A

1.2 A

10 A

5A

HP§

1 - 1/2 1 - 1/2

Est Drop 125V 1.2...3 A

SPST - NO - DM

SPDT, DPST - NO and DPDT

110V

20 A

10 A

220V

8A

4A

325V

4A

2A

500V

2A

DC Ratings: With Magnetic Blowouts:

Make, Break and Continuous

2

Inductive, 80...100% of Nominal Voltage at 50 Hz

Permissible Coil Voltage Variation

85...110% of Nominal Voltage at 60 Hz 80...110% of Nominal Voltage at DC

Coil Consumption ±10%

AC Coils

Dielectric Withstand Voltage

Pole-to-Pole

50 HZ

60 HZ

Inrush

13 VA

16 VA

Sealed

10 VA

11 VA

DC Coils

2.0 W Design Specification/Test Requirements 2200V AC

Contact to Pole

2200V

Contact to Frame

2200V AC Mechanical

Degree of Protection

Open Type 5 x 106

Mechanical Life Operations Switching Frequency Operations

1600/Hr

Coil Voltage Operating Time at Nominal Voltage at 20 °C

See Overview/Product Selection Pickup Dropout

40 ms 35 ms

Maximum Operating Rate, Environmental -30...+55 °C

Operating

(-22...+149 °F)

Temperature

-30...+65 °C

Storage

(-22...+149 °F)

Altitude

2000 m (6560 ft.) Construction Molded Thermo

Insulating Material

Setting Plastic

Enclosure, Contact Material

Silver Cadmium Oxide

Terminal Markings on Socket, Sockets

N/A

Certifications

CSA Certified, File 225674, UL Listed, File E3125, Guide NLDX, CE Marked

Standards

UL 508, CSA 22.2 No. 14, EN/IEC 60947-1, -5-1

‡ NEMA Rating Chart is on page 19 of publication 700-SG003B-EN-P. § For DPDT only: 2 Hp Switching 2 Poles, 200...600V AV, 50/60 Hz.

Rockwell Automation Publication 700-TD552A-EN-P

33

Page 34

700-HG Power Relays

Relays and Timer Specifications

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

Bulletin 700-HG Relays, SPST-NO-DM

Bulletin 700-HG Relays

34

Rockwell Automation Publication 700-TD552A-EN-P

Page 35

Relays and Timer Specifications

700-HHF Flange Mount Power Relays

Specifications Cat. No. 700-HHF… Electrical Ratings SPST-NO-DM

NEMA A600

DPDT

NEMA B600

Pilot Duty Rating‡

3PDT

NEMA B300 th

Rated Thermal Current (I )

SPST-NO-DM 30 A, DPDT 25A, 3PDT 20 A

Rated Insulation Voltage (Ui)

Contacts

250V IEC-300V UL/CSA

Inductive

SPST-NO-DM

120V AC

60 A

6A

1

30 A

3A

1

30 A

3A

1/2

240V AC

30 A

3.0 A

1-1/2

15 A

1.5 A

1-1/2

15 A

1.5 A, DC

Hp

DPDT

28V DC, 30 A

Hp

3PDT

28V DC, 13 A

Hp, 85…110% of Nominal Voltage at 50 Hz Permissible Coil Voltage Variation

85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC SPST-NO-DM

Coil Consumption ±10%

AC Coils

DPDT

3PDT

50 Hz

60 Hz

50 Hz

60 Hz

50 Hz

60 Hz

Inrush

7.2 VA

6.3 VA

7.2 VA

6.3 VA

7.2 VA

6.3 VA

Sealed

4.8 VA

4.2 VA

4.8 VA

4.2 VA

4.8 VA

4.2 VA

DC Coils

1.4 W 25% of VA

Max. Allowable Leakage

10% of W Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole-to-Pole

2200V AC

Contact-to-Pole

2200V AC

Contact-to-Frame

1600V AC Mechanical

Mechanical Life Operations

5 x 106

Switching Frequency Operations

3600/Hr

Coil Voltages

See Overview/Product Selection

Pickup Operating Time at Nominal Voltage at 20 °C Dropout

20 ms

Maximum Operating Rate

4 Ops/s.

15 ms Environmental –30…+50 °C

Operating

(–22…+122 °F)

Temperature

–30…+100 °C

Storage

(–22…+212 °F)

Altitude

2000 m (6560 ft) Construction

Insulating Material Enclosure

Molded High Dielectric Material Transparent Dust Cover

Contact Material

Silver Cadmium Oxide

Terminal Markings

In accordance with EN50 0005

Sockets

§

Certifications cURus Recognized, File E3125,Guide NLDX2/NLDX8, CE Marked

Standards

UL 508, CSA 22.2 No.14, EN/IEC 60947-1, -5-1

‡ NEMA Rating Chart is in 700-SG003_-EN-P. § Bulletin 700-HHF relay wiring and terminals are the quick connect/solder type 6.35 x 0.82 mm (0.250 x 0.032 in) termination.

Rockwell Automation Publication 700-TD552A-EN-P

35

Page 36

700-HHF Flange Mount Power Relays

Relays and Timer Specifications

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

35.7 (1-13/32)

3.97 (5/32)

63.5 (2-1/2)

38.9 (1-17/32)

73.8 (2-29/32)

Bulletin 700-HHF Relays

36

Rockwell Automation Publication 700-TD552A-EN-P

Page 37

Relays and Timer Specifications

700-HTA - Alternating Relays

Specifications Cat. No. 700-HTA… Electrical Ratings Pilot Duty Rating‡

NEMA B300 AC 15 th

Rated Thermal Current (I )

10 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA Inductive

Contacts

Make

HP

120V AC

30 A

3A

1/3

240V AC

15 A

1.5 A

1/2

Resistive 30V DC

10 A

10 A, 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz

Permissible Coil Voltage Variation Power Consumption ±10%

Break

AC

24V AC

2 VA

120V AC

4 VA

240V AC

4 VA

Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole-to-Pole, same circuit (VRMS)

1000V AC

Pole-to-Pole, different circuits (VRMS)

2000V AC

Contact-to-Coil (VRMS)

2000V AC

Electrical Life Operations

100,000 minimum

Switching Frequency Operations

1800/hr

Coil Voltages

See product selection Mechanical

Degree of Protection

Open Type (Guarded Terminal Sockets)

Mechanical Life Operations

10 x 106

Switching Frequency Operations

18,000/hr

Start-up Time (max. time from power application until unit is timing)

0.05 sec

Max. Function Time (max. time power can drop out and unit continues timing)

0.01 sec

Min. Cycle Time

100 ms on release of the control switch Environmental Operating

–28…+65 °C (50 °C max., 240V AC coil) (–18…+149 °F) (122 °F max., 240V AC coil)

Storage

–55…+85 °C (–67…+185 °F)

Temperature

Altitude

2000 m (6560 ft) Construction

Insulating Material

Molded High Dielectric Material

Enclosure

Impact Resistant Dust Cover

Contact Material

Silver Tin Oxide

Terminal Markings on Socket

In accordance with EN50 005 8- or 11-Pin Socket 700-HN100, -HN125 700-HN101, -HN126

Sockets

Certifications

CSA Certified, File 223833, UL Recognized (File E3125 Guide NLDX2/NLDX8), cULus Listed with 700-HN100, 700-HN101, 700-HN125, and 700-HN126 Sockets (File No. E3125 Guide NLDX/NLDX7), CE-Marked (per EU Low Voltage Directive)

Standards

EN 61812-1, EN/IEC 60947-1, -5-1, CSA 22.2 No. 14, UL 508

‡ NEMA Rating Chart is in publication 700-SG003_-EN-P.

Rockwell Automation Publication 700-TD552A-EN-P

37

Page 38

700-HTA - Alternating Relays

Relays and Timer Specifications

Trigger Signal Cat. Nos. 700-HTA Contact closure provides signal to timer. A low energy signal is generated by the 700-HTA alternating relay. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Example: Bul. 800F-X__V, 800T-X__V). No external voltage should be connected to the contact signal.

Load Diagrams

Common Input/Output SPDT/DPDT

Cross Wired

B1

Lead/Lag/Lag/lead Sequence

Lead

Load A

Lag

Load B

Load A

LED A

Load B

LED B

LED A

Power

LED B Power Socket Pinout Map SPDT Relay Socket

Socket Pinout Map DPDT Relay Socket

A1

4

A1

4

A2

3

A2

8

Note: pin out in wiring diagram may not match actual printed socket see pinout map for wiring up the power source

Socket Pinout Map Cross-Wired Relay Socket A1

3

A2

6

Note: pin out in wiring diagram may not match actual printed socket see pinout map for wiring up the power source

38

Rockwell Automation Publication 700-TD552A-EN-P

Page 39

Relays and Timer Specifications

700-HTA - Alternating Relays

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

79 (3-7/64)

74 (2-29/32)

60 (2-23/64)

(1-11/16)

24.6 (31/32)

40.1 (1-37/64) 30.0 (1-3/16)

20.8 (53/64) 26 (1-1/32)

24.9 (63/64)

65.0 (2-35/64)

54.9 (2-5/32)

4.2 (5/32)

51.1 (2-1/64)

38.0 (1-1/2) #4–40 M3

33.0 (1-19/64)

14.7 (37/64) Cat. No. 700-HN125

Cat. No. 700-HN100 Panel Mounting Double Wire, 2 x 2.5 mm2 (#2 – 14 AWG…#2 – 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)

Wire Size: 2 x 2.5 mm2 Single Wire, Up to #12 AWG Double Wire, 2 x 2.5 mm2 (#2 – 14 AWG… #2 – 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in), Torque: 0.8 N•m (7 lb•in)

Rockwell Automation Publication 700-TD552A-EN-P

39

Page 40

700-HTA - Alternating Relays

Relays and Timer Specifications 59.2 (2-1/3)

30 (1-3/16)

7.9 (0.31)

26 (1-1/32)

24.6 (31/32) 20.8 (53/64)

26.9 (1.06) 54.9 (2-5/32)

65.0 (2-35/64)

4.2 (5/32)

38.0 (1-1/2)

52.3 (2.06)

#4-40 M3 Cat. No. 700-HN101 Panel Mounting Double Wire – 2 x 2.5 mm2 (#2 – 14 AWG…#2 – 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)

40

51.1 (2-1/64)

Cat. No. 700-HN126 Wire Size: 2 x 2.5 mm2 Single Wire, Up to 12 AWG Double Wire, 2 x 2.5 mm2 (#2 – 14 AWG…#2 – 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in), Torque: 0.8 N•m (7 lb•in)

Rockwell Automation Publication 700-TD552A-EN-P