Page 31
Relays and Timer Specifications
700-HJ Magnetic Latching Relays
Specifications Cat. No. 700-HJ… Electrical Ratings Pilot Duty Rating, th
Rated Thermal Current (I )
10 A
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA Inductive 120V AC 240V AC
Contacts
Make
Break
Hp
30 A 15 A
3A 1.5 A
1/4 1/3
DC
24V DC, 10 A 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC
Permissible Coil Voltage Variation
AC Coils Coil Consumption ±10%
Inrush Sealed
DC Coils
Single AC Coil
Single DC Coil
Dual DC Coil
1.44 VA 1.44 VA, - - 1.2 W
12V 1.63 W 24V 1.67 W
Design Specification/Test Requirements Dielectric Withstand Voltage
Pole-to-Pole
1500V AC
Contact-to-Pole
1500V AC
Contact-to-Frame
1500V AC Mechanical Open Type (Guarded Terminal Sockets)
Degree of Protection Mechanical Life Operations
10 x 106
Switching Frequency Operations
1800/HR
Coil Voltages
See Product Selection
Operating Time at Nominal Voltage at 20 °C
Pickup Dropout
25 ms 25 ms
Maximum Operating Rate, Environmental Operating
–45…+50 °C (–49…+122 °F)
Storage
–45…+100 °C (–49…+212 °F)
Temperature
Altitude
2000 m (6560 ft.) Construction
Insulating Material Enclosure Contact Material Terminal Markings on Socket Sockets
Molded High Dielectric Material Transparent Dust Cover Silver Cad. Ox. In accordance with EN50 0005 11-Blade Socket Cat. No. 700-HN153 Cat. No. 700-HN154
Certifications
CSA Certified, File LR700026, UL Recognized, File E3125, Guide NLDX 2
Standards
UL 508, CSA 22.2 No. 14, EN/IEC 60947-4-1, -5-1
Rockwell Automation Publication 700-TD552A-EN-P
31
Page 32
700-HJ Magnetic Latching Relays
Relays and Timer Specifications
Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
Bulletin 700-HJ Relay
Cat. No. 700-HN153 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)
Cat. No. 700-HN154 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)
6.2 (15/64)
50 (1-63/64)
5.2 (13/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38)
27.0 (1.06)
7.5 (0.3)
1000 (39-3/8)
Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes
32
Cat. No.
A
B
C
D
Approx. Shipping Wt.
199-DR1
35 (1-3/8)
27 (1-1/16)
7.5 (19/64)
1.02 (1/64)
1.85 kg (4.07 lbs.) (10/pkg)
199-DR4
35 (1-3/8)
27 (1-1/16)
15 (19/32)
2.3 (3/32)
3.68 kg (8 lbs.) (5/pkg)
Rockwell Automation Publication 700-TD552A-EN-P
Page 33
Relays and Timer Specifications
700-HG Power Relays
Specifications Cat. No. 700-HG... Electrical Ratings Pilot Duty Rating ‡
A600
Rated Thermal Current (/th)
40 A
Rated Insulation Voltage (Ui)
600V UL
Contact Ratings: AC Ratings SPST-NO-DM
Contact Ratings: AC Ratings SPDT, DPST - NO and DPDT
Inductive Volts
Make
Resistive Make/Break HP Volts and Continuous Continuous
Break
120
60 A
6A
10 A
40 A
240
30 A
3A
10 A
40 A
480
15 A
1.5 A
10 A
12 A
600
12 A
1.2 A
10 A
10 A
DC Ratings: Without Magnetic Blowouts - 28V 40 A - Make, Break and Continuous
2
Make
Break
Resistive Make/Break and Continuous Continuous
120
60 A
6A
10 A
40 A
240
30 A
3A
10 A
40 A
480
15 A
1.5 A
10 A
5A
600
12 A
1.2 A
10 A
5A
HP§
1 - 1/2 1 - 1/2
Est Drop 125V 1.2...3 A
SPST - NO - DM
SPDT, DPST - NO and DPDT
110V
20 A
10 A
220V
8A
4A
325V
4A
2A
500V
2A
DC Ratings: With Magnetic Blowouts:
Make, Break and Continuous
2
Inductive, 80...100% of Nominal Voltage at 50 Hz
Permissible Coil Voltage Variation
85...110% of Nominal Voltage at 60 Hz 80...110% of Nominal Voltage at DC
Coil Consumption ±10%
AC Coils
Dielectric Withstand Voltage
Pole-to-Pole
50 HZ
60 HZ
Inrush
13 VA
16 VA
Sealed
10 VA
11 VA
DC Coils
2.0 W Design Specification/Test Requirements 2200V AC
Contact to Pole
2200V
Contact to Frame
2200V AC Mechanical
Degree of Protection
Open Type 5 x 106
Mechanical Life Operations Switching Frequency Operations
1600/Hr
Coil Voltage Operating Time at Nominal Voltage at 20 °C
See Overview/Product Selection Pickup Dropout
40 ms 35 ms
Maximum Operating Rate, Environmental -30...+55 °C
Operating
(-22...+149 °F)
Temperature
-30...+65 °C
Storage
(-22...+149 °F)
Altitude
2000 m (6560 ft.) Construction Molded Thermo
Insulating Material
Setting Plastic
Enclosure, Contact Material
Silver Cadmium Oxide
Terminal Markings on Socket, Sockets
N/A
Certifications
CSA Certified, File 225674, UL Listed, File E3125, Guide NLDX, CE Marked
Standards
UL 508, CSA 22.2 No. 14, EN/IEC 60947-1, -5-1
‡ NEMA Rating Chart is on page 19 of publication 700-SG003B-EN-P. § For DPDT only: 2 Hp Switching 2 Poles, 200...600V AV, 50/60 Hz.
Rockwell Automation Publication 700-TD552A-EN-P
33
Page 34
700-HG Power Relays
Relays and Timer Specifications
Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
Bulletin 700-HG Relays, SPST-NO-DM
Bulletin 700-HG Relays
34
Rockwell Automation Publication 700-TD552A-EN-P
Page 35
Relays and Timer Specifications
700-HHF Flange Mount Power Relays
Specifications Cat. No. 700-HHF… Electrical Ratings SPST-NO-DM
NEMA A600
DPDT
NEMA B600
Pilot Duty Rating‡
3PDT
NEMA B300 th
Rated Thermal Current (I )
SPST-NO-DM 30 A, DPDT 25A, 3PDT 20 A
Rated Insulation Voltage (Ui)
Contacts
250V IEC-300V UL/CSA
Inductive
SPST-NO-DM
120V AC
60 A
6A
1
30 A
3A
1
30 A
3A
1/2
240V AC
30 A
3.0 A
1-1/2
15 A
1.5 A
1-1/2
15 A
1.5 A, DC
Hp
DPDT
28V DC, 30 A
Hp
3PDT
28V DC, 13 A
Hp, 85…110% of Nominal Voltage at 50 Hz Permissible Coil Voltage Variation
85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC SPST-NO-DM
Coil Consumption ±10%
AC Coils
DPDT
3PDT
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
Inrush
7.2 VA
6.3 VA
7.2 VA
6.3 VA
7.2 VA
6.3 VA
Sealed
4.8 VA
4.2 VA
4.8 VA
4.2 VA
4.8 VA
4.2 VA
DC Coils
1.4 W 25% of VA
Max. Allowable Leakage
10% of W Design Specification/Test Requirements
Dielectric Withstand Voltage
Pole-to-Pole
2200V AC
Contact-to-Pole
2200V AC
Contact-to-Frame
1600V AC Mechanical
Mechanical Life Operations
5 x 106
Switching Frequency Operations
3600/Hr
Coil Voltages
See Overview/Product Selection
Pickup Operating Time at Nominal Voltage at 20 °C Dropout
20 ms
Maximum Operating Rate
4 Ops/s.
15 ms Environmental –30…+50 °C
Operating
(–22…+122 °F)
Temperature
–30…+100 °C
Storage
(–22…+212 °F)
Altitude
2000 m (6560 ft) Construction
Insulating Material Enclosure
Molded High Dielectric Material Transparent Dust Cover
Contact Material
Silver Cadmium Oxide
Terminal Markings
In accordance with EN50 0005
Sockets
§
Certifications cURus Recognized, File E3125,Guide NLDX2/NLDX8, CE Marked
Standards
UL 508, CSA 22.2 No.14, EN/IEC 60947-1, -5-1
‡ NEMA Rating Chart is in 700-SG003_-EN-P. § Bulletin 700-HHF relay wiring and terminals are the quick connect/solder type 6.35 x 0.82 mm (0.250 x 0.032 in) termination.
Rockwell Automation Publication 700-TD552A-EN-P
35
Page 36
700-HHF Flange Mount Power Relays
Relays and Timer Specifications
Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
35.7 (1-13/32)
3.97 (5/32)
63.5 (2-1/2)
38.9 (1-17/32)
73.8 (2-29/32)
Bulletin 700-HHF Relays
36
Rockwell Automation Publication 700-TD552A-EN-P
Page 37
Relays and Timer Specifications
700-HTA - Alternating Relays
Specifications Cat. No. 700-HTA… Electrical Ratings Pilot Duty Rating‡
NEMA B300 AC 15 th
Rated Thermal Current (I )
10 A
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA Inductive
Contacts
Make
HP
120V AC
30 A
3A
1/3
240V AC
15 A
1.5 A
1/2
Resistive 30V DC
10 A
10 A, 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz
Permissible Coil Voltage Variation Power Consumption ±10%
Break
AC
24V AC
2 VA
120V AC
4 VA
240V AC
4 VA
Design Specification/Test Requirements
Dielectric Withstand Voltage
Pole-to-Pole, same circuit (VRMS)
1000V AC
Pole-to-Pole, different circuits (VRMS)
2000V AC
Contact-to-Coil (VRMS)
2000V AC
Electrical Life Operations
100,000 minimum
Switching Frequency Operations
1800/hr
Coil Voltages
See product selection Mechanical
Degree of Protection
Open Type (Guarded Terminal Sockets)
Mechanical Life Operations
10 x 106
Switching Frequency Operations
18,000/hr
Start-up Time (max. time from power application until unit is timing)
0.05 sec
Max. Function Time (max. time power can drop out and unit continues timing)
0.01 sec
Min. Cycle Time
100 ms on release of the control switch Environmental Operating
–28…+65 °C (50 °C max., 240V AC coil) (–18…+149 °F) (122 °F max., 240V AC coil)
Storage
–55…+85 °C (–67…+185 °F)
Temperature
Altitude
2000 m (6560 ft) Construction
Insulating Material
Molded High Dielectric Material
Enclosure
Impact Resistant Dust Cover
Contact Material
Silver Tin Oxide
Terminal Markings on Socket
In accordance with EN50 005 8- or 11-Pin Socket 700-HN100, -HN125 700-HN101, -HN126
Sockets
Certifications
CSA Certified, File 223833, UL Recognized (File E3125 Guide NLDX2/NLDX8), cULus Listed with 700-HN100, 700-HN101, 700-HN125, and 700-HN126 Sockets (File No. E3125 Guide NLDX/NLDX7), CE-Marked (per EU Low Voltage Directive)
Standards
EN 61812-1, EN/IEC 60947-1, -5-1, CSA 22.2 No. 14, UL 508
‡ NEMA Rating Chart is in publication 700-SG003_-EN-P.
Rockwell Automation Publication 700-TD552A-EN-P
37
Page 38
700-HTA - Alternating Relays
Relays and Timer Specifications
Trigger Signal Cat. Nos. 700-HTA Contact closure provides signal to timer. A low energy signal is generated by the 700-HTA alternating relay. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Example: Bul. 800F-X__V, 800T-X__V). No external voltage should be connected to the contact signal.
Load Diagrams
Common Input/Output SPDT/DPDT
Cross Wired
B1
Lead/Lag/Lag/lead Sequence
Lead
Load A
Lag
Load B
Load A
LED A
Load B
LED B
LED A
Power
LED B Power Socket Pinout Map SPDT Relay Socket
Socket Pinout Map DPDT Relay Socket
A1
4
A1
4
A2
3
A2
8
Note: pin out in wiring diagram may not match actual printed socket see pinout map for wiring up the power source
Socket Pinout Map Cross-Wired Relay Socket A1
3
A2
6
Note: pin out in wiring diagram may not match actual printed socket see pinout map for wiring up the power source
38
Rockwell Automation Publication 700-TD552A-EN-P
Page 39
Relays and Timer Specifications
700-HTA - Alternating Relays
Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
79 (3-7/64)
74 (2-29/32)
60 (2-23/64)
(1-11/16)
24.6 (31/32)
40.1 (1-37/64) 30.0 (1-3/16)
20.8 (53/64) 26 (1-1/32)
24.9 (63/64)
65.0 (2-35/64)
54.9 (2-5/32)
4.2 (5/32)
51.1 (2-1/64)
38.0 (1-1/2) #4–40 M3
33.0 (1-19/64)
14.7 (37/64) Cat. No. 700-HN125
Cat. No. 700-HN100 Panel Mounting Double Wire, 2 x 2.5 mm2 (#2 – 14 AWG…#2 – 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)
Wire Size: 2 x 2.5 mm2 Single Wire, Up to #12 AWG Double Wire, 2 x 2.5 mm2 (#2 – 14 AWG… #2 – 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in), Torque: 0.8 N•m (7 lb•in)
Rockwell Automation Publication 700-TD552A-EN-P
39
Page 40
700-HTA - Alternating Relays
Relays and Timer Specifications 59.2 (2-1/3)
30 (1-3/16)
7.9 (0.31)
26 (1-1/32)
24.6 (31/32) 20.8 (53/64)
26.9 (1.06) 54.9 (2-5/32)
65.0 (2-35/64)
4.2 (5/32)
38.0 (1-1/2)
52.3 (2.06)
#4-40 M3 Cat. No. 700-HN101 Panel Mounting Double Wire – 2 x 2.5 mm2 (#2 – 14 AWG…#2 – 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)
40
51.1 (2-1/64)
Cat. No. 700-HN126 Wire Size: 2 x 2.5 mm2 Single Wire, Up to 12 AWG Double Wire, 2 x 2.5 mm2 (#2 – 14 AWG…#2 – 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in), Torque: 0.8 N•m (7 lb•in)
Rockwell Automation Publication 700-TD552A-EN-P