The text of a spec sheet · part 5 of 13
Relays and Timers Specifications, Bulletin Number 700, pages 41 to 50
Pages 41 to 50 of 128
The original document is the PDF (10 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HN122
Page 41
Relays and Timer Specifications
700-FE DIN Rail Mounted Timing Relay
Function and Connection Diagrams (A) On-Delay A1/A2
U Output
(B) Off-Delay
A1/A3
15
18 15 t
LED
A1/A2
U
A2
18
1 N.O. (SPST)
Output LED t
B1 S
A1
A1/B1 18 15
S
15
A2
18
A1 B1 S
15
A2
18 16
1 N.O. (SPST) U Output LED
A1/A2 18 15 16 t
15
A1
A2
18 16
(D) One Shot
A1/B1
Output
15 18 16 t
1 C/O (SPDT)
(F) Flasher (Repeat Cycle Starting with Pulse) A1/A2 15 t
15
A1
18
A2
18
A1
15
1 N.O. (SPST) U Output LED
A1/A2
S LED
1 C/O (SPDT)
U Output LED
U
A1/A2
A1/A2
A1
15
A2
18
A1
15
A2
18 16
18 t t t t t 15
LED
1 N.O. (SPST)
18 1516 t
U Output
A2
18 16
U Output
A1/A2 t t t t
15 18 16 t
LED
1 C/O (SPDT) 1 C/O (SPDT) (L) Pulse Converter
(E) Fleeting Off-Delay
LED
1)
1)
A1/A2 B1
S A1 B1
15 t A2
18 16
A1/A2 A1/B1
U S Output LED t t
A1
S B1
15
18 15 16
A2
18 16
1 C/O (SPDT) (Y) Star-Delta Timing Relay U
A1/A2
A1
17
A2
18 28
17/18 ∆ LED tu = 50...65 ms
17/28
∆
Bi-Color LED: 1 C/O (SPDT) or 1 N.O. Contact Timers
Single Color LED: 2 N.O. with Common
LED U = green: Supply voltage available. LED Relay = red: Output is energized.
Rockwell Automation Publication 700-TD552A-EN-P
ON = green OFF = red
41
Page 42
700-FE DIN Rail Mounted Timing Relay
Relays and Timer Specifications
Specifications Time Characteristics (according to VDE 0435, part 2021)
1 N.O. Setting Accuracy
SPDT ±5% of full scale
Repeatability
±1% of setting (typical) By voltage: ±0.01%/%ΔU By temperature: ±0.25%/°C
Tolerance
By voltage: ±0.001%/%ΔU By temperature: ±0.025%/°C
Supply Supply Voltage
24V AC/DC‡ and 110…240V AC, 50/60 Hz AC
Voltage Tolerance
24…48V DC and 24…240V AC, 50/60 Hz
–15%/+10%
DC
–15%/+20%
Power Consumption
0.5 W at 24V DC, 5 VA at 240V AC
Time Energized
100%
Reset Time
100 ms
Cable Length (Supply Voltage Control)
Max. 250 m (750 feet) Pulse Control (B1) ≥ 250 ms
Impulse Duration
≥ 50 ms (AC), ≥ 30 ms (DC)
Input Voltage supply voltage range
Input Current
1 mA
Cable Length
Max. 250 m without parallel load between B1 and A2 Max. 50 m with load (< 3 kΩ) between B1 and A2 Outputs
Contact Type Dielectric Withstand Voltage
1 N.O. contact Contact-to-coil Power
Switching Capacity
According to IEC 947-5-1
1250 VA AC-1
5 A /250V AC (resistive load)
AC-14
1 A/250V AC (inductive load)
DC-13 According to UL 508 Short-Circuit Resistance
Life
1 Form C – SPDT contact 4000 V
1 A/24V DC (inductive load) NEMA D300 - 1 A/300V AC 6 A gL (Fast Blow Fuse)
Mechanical
20 million operations
Electrical
0.4 million at 1 A/250V AC, resistive 0.4 million at 0.5 A/250V AC, cos φ = 0.4 0.4 million at 1 A/24V DC, resistive
State Indicator
1 Bi-Color LED (Supply; Relay)
Certifications cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked
Standards
EN/IEC 60947-1, EN/IEC 60947-5-1, UL 508, CSA 22.2 No. 14
‡ Voltage is either 24V DC or AC 50/60 Hz.
42
Rockwell Automation Publication 700-TD552A-EN-P
Page 43
Relays and Timer Specifications
700-FE DIN Rail Mounted Timing Relay
General Specifications 1 N.O.
SPDT
Insulation Characteristics
2 kV AC/50 Hz test voltage according to VDE 0435 and 4 kV 1.2/50 μs surge voltage according to IEC 60947-1 between all inputs and outputs
EMC/Interference Immunity
The following requirements are fulfilled: Surge capacity of the supply voltage according to IEC 61000-4-5: Level 3 Burst according to IEC 61000-4-4: Level 3 ESD discharge according to IEC 61000-4-2: Level 3
EMC/Emmission electromagnetical fields according to EN 55 022: Class B
Safe Isolation according to VDE 0106 T 101
Climatic Withstand
56 cycles (24 hr) at 25…40 °C and 95% relative humidity according to IEC 60068-2-30
Vibration Resistance
4 g in three axes at 10…500 Hz, test FC according to IEC 60068-2-6
Shock Resistance
50 g according to IEC 68-2-27
Protection Class IEC 60947-1
Enclosure:IP 40 Terminal:IP 20
Weight Certifications Ambient Temperature
60 g
60 g cULus, CE Certified cULus, Germanischer Lloyd, CE Certified Open:–25…+60 °C Enclosed:–25…+45 °C Storage:–40…+85 °C
Connections
Screw terminal M3 for Pozidriv No.1, Philips and slotted screws No.2. suitable for power screw-driver. Rated tightening torque 8.8 lb.-in. (max. 1.0 Nm) For terminal cross-sections of 1 x 0.5 mm2…2 x 1.5 mm2 (solid) or 2 x 1.5 mm2 (stranded with sleeve), #20…14 AWG. Finger protection according to EN 50274
Mounting
For surface mounting in any position; snap-on mounting on 35 mm DIN Rail or by adapter and two screws (M4 type)
Disposal
Synthetic materials without dioxin according to EC/EFTA-Notification No. 93/0141/D electrical contacts are AgCdO
Rockwell Automation Publication 700-TD552A-EN-P
43
Page 44
700-FE DIN Rail Mounted Timing Relay
Relays and Timer Specifications
Approximate Dimensions Approximate dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
80.0 (3-5/32)
13 (0.51)
22.5 (0.89)
43.0 (1-11/16)
4.3 (0.17)
45.0 (1-25/32)
35.0 (1.38) 58.0 (2.28) 17 12 (0.67) (0.47)
17.5 (11/16)
66.0 (2-9/16) 70.0 (2-49/64)
4.3 (0.17) 9.0 (0.35)
Cat. No. 700-FE…
44
Rockwell Automation Publication 700-TD552A-EN-P
2.0 (0.08) 5.5 (0.22) Cat. No. 199-FSA…
75.0 (2.95)
Page 45
Relays and Timer Specifications
700-FS DIN Rail Mounted Timing Relay
Connection Diagrams (A) On-Delay
(G) Flasher (Repeat Cycle Starts with Pause) Output Output
Output
Output 1 Output 2 Output 2
(I) On-Delay Pulse Generator (B) Off-Delay (Min. Pulse AC 50 ms…DC 30 ms) Output LED
Output
‡ Output 1
(J) On-Delay (Pulse Controlled)
Output 2 Output 2
(C) On- and Off-Delay
Output LED
(K) One Shot/Watch Dog (Pulse Controlled) Output LED
‡
(D) One Shot
Output LED Output
(On) ON-Function (Off) OFF-Function
Output 1
Output 1
Output 2
Output 2
LED
LED
(E) Fleeting Off-Delay (Min. Pulse AC 50 ms…DC 30 ms) (L) Pulse Converter (Min. Pulse AC 50 ms…DC 30 ms) Output t
LED
‡
Output LED
‡
(F) Flasher (Repeat Cycle Starts with Pulse) Cleverly Designed Function Display LED (Green) Output
Output in Rest Position, No Timing Output in Rest Position, Time Running Output in Operation Position, No Time Running Output in Operation Position, Time Running * A VOLTAGE OTHER THAN THE SUPPLY VOLTAGE CAN BE USED AT B1, BUT MUST BE WITHIN VOLTAGES SPECIFIED ON TIMER.
A voltage other than the supply voltage can be used at B1, but must be within voltages specified on timer. † Output 2 is selectable as instantaneous contact with sliding switch (⊗) on front panel (instantaneous when switch is down, timed when switch is up). ‡ Available on multifunction "M," and single function "A" or "B" option timing relays along with code "4" (2PDT contacts). Bridge or potentiometer 10 kΩ, 0.25 W min. (low voltage) for external time setting. Set timer dial to 0.0.
Rockwell Automation Publication 700-TD552A-EN-P
45
Page 46
700-FS DIN Rail Mounted Timing Relay
Relays and Timer Specifications
Special Function Flasher (Repeat Cycle Starting with Pulse or Pause) Timing Relays Description t2 Setting Up Switch Down 1 Range Setting
Supply Voltages (A1/A2) Z12 12V DC
Seperate Range Settings
U23 24…48V DC, 24…240V AC, 50/60 Hz t1 Setting 700-FSH3V 700-FSH3U Function Diagram / Connection Diagram
(H) Flasher (Repeat Cycle Starting with Pulse or Pause) The repeat cycle timer permits different settings for on and off times. The following operating modes are possible: Oscillating mode; repeat cycle starts with voltage applied at A1 and B1, and continues to repeat until voltage is off. One cycle mode; started by energizing B1 with voltage on A1 and A2. Output starts with pulse or pause (switch ⊗ Up or Down). 700-FSH3U provides (1) range setting for t1 and t2. 700-FSH3V provides (2) range settings for t1 and t2. Supply Voltage Controlled, Oscillating Mode Starting with Pause, Switch ⊗ is Up
U S Output LED t2 t2 t1 t1
A1/A2 A1/B1 15 18 16
A1 B1
18 16
A2
Output LED
A1/A2 t1 t2
A1
A1/B1
U S Output
15
Pulse Controlled, Output Starts With Pause (Min. Pulse AC 50 ms, DC 30 ms), Switch ⊗ is Up One Cycle Mode, Voltage Supplied at A1 and A2, then Pulsing “s” to Energize B1 will Initiate One Cycle.
U S
Supply Voltage Controlled, Oscillating Mode Starting with Pulse, Switch ⊗ is Down
S B1 t1 t2 t2 15 18 16
LED
15
U S Output
18 16
A1/A2 t1
A1/B1 t2
LED
LED Operation Chart Ñ Green LED
46
15
A2
18 16
Output at Shelf State, No Timing - LED OFF Output at Shelf State, Time is Running - LED Flashing Output NO Contact is Closed, No Timing - LED On Output NO Contact is Closed, Time is Running - LED Long Flashing
Rockwell Automation Publication 700-TD552A-EN-P s A1 B1
15
A2
18 16 t1 t2 15 18 16
Note: If B1 is pulsed, a one full time cycle consisting of t1 and t2 is completed.
LED LED LED LED
A1 B1
Pulse Controlled, Output Starts with Pulse (Min. Pulse AC 50 ms, DC 30 ms), Switch ⊗ is Down One Cycle Mode, Voltage Supplied at A1 and A2, then Pulsing “s” to Energize B1 will Initiate One Cycle.
t1 t2 15 18 16 A2 t1
A1/A2 A1/B1
Page 47
Relays and Timer Specifications
700-FS DIN Rail Mounted Timing Relay Function Diagram / Connection Diagram
(Q) Off-Delay without Supply Voltage (True Off-Delay), When input power is turned on, the output contact changes state. When the power is removed, the time delay begins. The output contact returns to shelf state at the end of the time delay.
U Output tp
A1/A2 t
15
A1
15
18 16
LED
A2
18 16
U tp
Output 1 t
Output 2 LED t
A1/A2
A1
15
15 18 16 25 28 26
A2
18 16 28 26
25
Note: Min. pulse (tp) required: 800 ms (Y) Star-Delta Timing Relay, When power is applied, the output contact 17/18(Y) changes state. After the time setting, the output contact 17/18(Y) returns to shelf state. After the fixed time (50… 60 ms), the output contact 17/28Δ changes state. Both output contacts return to shelf state whenever the power is removed.
U
A1/A2 t tu = 50...65 ms
LED
A1
17
A2
18
17/18 17/28
Rockwell Automation Publication 700-TD552A-EN-P
28
47
Page 48
700-FS DIN Rail Mounted Timing Relay
Relays and Timer Specifications
Specifications Time Characteristics (according to VDE 0435, Part 2021) Setting Accuracy
±5% of full scale
Repeatability
±0.2% of the setting values
Tolerance
Voltage: ±0.001%/%ΔU Temperature: ±0.025%/°C
General Data Insulation Characteristics
2 kVAC/50 Hz test voltage according to VDE 0435 and 6 kV 1.2/50 μs surge voltage according to IEC 947-1 between all inputs and outputs
EMC/Interference Immunity
Performance of following requirements: Surge capacity of the supply voltage according to IEC 1000-4-5: 4 kV 1.2/50 μs Burst according to IEC 1000-4-4: 6 kV 6/50 ns ESD discharge according to IEC 10004-2: Contact 8 kV, air 8 kV Electromagnetic HF field according to IEC 801-3 and conducted electromagnetic HF signal according to IEC 801-6: Level 3
EMC/Emission
Electromagnetic fields according to EN 55 022: class B
Safe Isolation
According to VDE 106, part 101
Climatic Withstand
56 Cycles (24 hr) at 25…40 °C and 95% relative humidity according to IEC 68-2-30 and IEC 68-2-3
Supply Supply Voltages
24…48V DC and 24…240V AC, 50/60 Hz (multi voltage)
Voltage Tolerance
–20…+20% (DC), –15…+10% (AC)
Power Consumption
0.5 W at 24V DC, 5 VA at 240V AC
Time Energized
100%
Reset Time
50 ms
Voltage Interruption
≤20 ms without reset (supply voltage)
Input Impedance
Relay ON: 3K-13K ohms Relay OFF: 0.7K-4K ohms
Cable Length (Supply Voltage Control)
Max. 250 m (800 ft)
Pulse Control (B1) Pulse Duration
≥50 ms (AC), ≥30 ms (DC)
Vibration Resistance
4 g in three axes at 10…500 Hz, test FC according to IEC 68-2-6
Input Voltage
Supply voltage range
Shock Resistance
50 g according to IEC 68-2-27
Input Current
1 mA
Max. Leakage Current
400 micro Amps
Protection Class
Enclosure:IP 40 IP 30 (Single-function) Terminal:IP 20 according to IEC 947-1
Max. 250 m (800 ft) without parallel load between B1 and A2 Max. 50 m (160 ft) with load (<3 kΩ) between B1 and A2
Weight
100 g
Cable Length
Approval
UL, C-UL
Ambient Temperature
Open: –25…+60 °C Enclosed: –25…+45 °C Storage: –40…+85 °C
Terminals
Screw terminal M3.5 for Number 2 Posidrive, Philips, and slotted screws. Suitable for power screwdriver. Rated tightening torque 8.8 lb.-in. (0.8 N•m, max. 1.2 N•m). Dual-chamber system for terminal cross-sections of 1 x 0.5 mm2…2 x 2.5 mm2 (solid) or stranded 2 x 2.5 mm2 (flexible with sleeve), #20…14 AWG. Finger protection according to VDE 0106.
Mounting
Front mounting; For snap-on mounting on 35 mm DIN Rail or screw fixing by adapter and 2 screws (M4 type)
Disposal
Synthetic material without dioxin according to EC/EFTA notification Number 93/0141/D electrical contacts with cadmium
Certifications cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked
Standards
EN/IEC 60947-1, EN/IEC 60947-5-1, UL 508, CSA 22.2 No. 14
Outputs Contact Type
Relay as changeover switch
Dielectric Coil to Contact Withstand Voltage
5000 V Voltage: 440V AC Current Ith (AC-1): 8 A (5 A for 700FSQ) Power: 2000 VA According to IEC 947-5-1:
Switching Capacity
3 A/440V AC (inductive load, AC 14) 3 A/250V AC (inductive load, AC 15) 1 A/24V DC (inductive load, DC 13) According to UL 508: 1.5 A/250V AC (B300) 3 A/120V AC (B300)
Short-Circuit Resistance
10 A gL Mechanical: 30 million operations Electrical operations: 4 Mil. at 1 A/250V AC, cos φ = 1 0.2 Mil. at 6 A/250V AC, cos φ = 1 1.5 Mil. at 1 A/250V AC, cos φ = 0.3
Life
0.3 Mil. at 3 A/250V AC, cos φ = 0.3
Temp. Code T4A 2A 32VDC MAX.
0.5 Mil. at 6 A/24V DC, resistive 2 Mil. at 4 A/24V DC, resistive 2 Mil. at 0.2 A/230V DC, resistive 1 Mil. at 0.4 A/24V DC, L/R = 20 ms
Mounting: Product shall be installed in an enclosure constructed in accordance with the requirements of EN50021.
1 Mil. at 0.2 A/110V DC, L/R = 20 ms 1 Mil. at 0.1 A/230V DC, L/R = 20 ms State Indicator
48
1 LED, combination signal
Rockwell Automation Publication 700-TD552A-EN-P
Page 49
Accessories/ Specifications Specifications Ratings Item Pilot Duty Rating Pin type Operating voltage range Reset voltage
Power consumption
Control outputs
Make Break Hp at 120V AC Hp at 240V AC Accuracy of operating time Setting error Reset time Influence of voltage Influence of temperature Insulation resistance
Dielectric strength
Vibration resistance Shock resistance Ambient temperature Ambient humidity Life expectancy
120V AC 240V AC 120V AC 240V AC
700-HNC NEMA B300 Plug-in 85%…110% of rated supply voltage (12V DC: 90%…110% of rated supply voltage)‡ 10% min. of rated supply voltage§ Relay ON: 1.5 VA (1.1 W) (at 24V AC, 60 Hz) 24V AC: 0.2 VA (0.1 W) (at 24V AC, 60 Hz) Relay OFF: Relay ON: 1.5 VA (1.3 W) (at 120V AC, 60 Hz) 100…120V AC: Relay OFF: 0.8 VA (0.5 W) (at 120V AC, 60 Hz) Relay ON: 1.8 VA (1.5 W) (at 230V AC, 60 Hz) 200…230V AC: Relay OFF: 1.2 VA (0.9 W) (at 230V AC, 60 Hz) Relay ON: 0.9 W (at 12V DC) 12V DC: Relay OFF: 0.07 W (at 12V DC) Relay ON: 0.9 W (at 24V DC) 24V DC: Relay OFF: 0.07 W (at 24V DC) Relay ON: 1.0 W (at 48V DC) 48V DC: Relay OFF: 0.2 W (at 48V DC) Relay ON: 1.3 W (at 110V DC) 100…110V DC: Relay OFF: 0.3 W (at 110V DC) Relay ON: 1.3 W (at 125V DC) 125V DC: Relay OFF: 0.3 W (at 125V DC) 4PDT: 5 A at 250V AC, resistive load (cosφ = 1) Characteristics 30 A 15 A 3A 1.5 A 1/6 Hp 1/6 Hp ±1% FS max. (1 s range: ±1%±10 ms max.) ±10%±50 ms FS max. Min. power-opening time: 0.1 s max. (including halfway reset) ±2% FS max. ±2% FS max. 100 mΩ min. (at 500V DC) 2000V AC, 50/60 Hz for 1 min (between current-carrying terminals and exposed non-current-carrying metal 2000V AC, 50/60 Hz for 1 min (between operating power circuit and control output) 2000V AC, 50/60 Hz for 1 min (between different pole contacts; 2-pole model) 1500V AC, 50/60 Hz for 1 min (between different pole contacts; 4-pole model) 1000V AC, 50/60 Hz for 1 min (between non-continuous contacts) Malfunction:10…55 Hz, 0.5 mm single amplitude Malfunction:100 m/s2 (approx. 10G) Operating:-10 °C…50 °C (with no icing) Storage:-25 °C…65 °C (with no icing) Operating:35%…85% Mechanical:10 000 000 operations min. (under no load at 1800 operations/hr) Electrical:4PDT: 200 000 operations min. (3 A at 250V AC, resistive load at 1800 operations/hr)
Single-phase, full-wave-rectified power supplies can be used. ‡ When using the 700-HNC continuously in any place where the ambient temperature is in a range of 45 °C…50 °C, supply 90%…110% of the rated supply voltages supply 95%…110% with 12V DC type).
Rockwell Automation Publication 700-TD552A-EN-P
49
Page 50
700-HNC Plug-in Timing Relay
Relays and Timer Specifications
Characteristics, Continued Noise immunity
±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity
Destruction:8 kV Malfunction:4 kV
Enclosure rating
IP40
Weight
Approx. 50 g Emission Enclosure:EN55011 Group 1 class A Emission AC Mains:EN55011 Group 1 class A Immunity ESD:EN61000-4-2:4 kV contact discharge (level 2) 8 kV air discharge (level 3) Immunity RF-interference:ENV50140:10 V/m (amplitude modulated, 80 MHz to 1 GHz) (level 3)
EMC
10 V/m (pulse modulated, 900 MHz) Immunity Conducted Disturbance:ENV50141:10 V (0.15…80 MHz) (level 3) Immunity Burst:EN61000-4-4:2 kV power-line (level 3) 2 kV I/O signal-line (level 4) Standards
UL 508, CSA 22.2 No. 14, EN/IEC 61812-1
Certifications cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), CSA Certified (File 224268), CE Marked, CTick Marked
Timing Charts Note :t:Set time Rt:Reset time Operating Mode
Timing Charts / Wiring Diagram
Power (13-14) Time limit contact NC (9-1, 10-2, 11-3, 12-4) Time limit contact NO (9-5, 10-6, 11-7,12-8) Run/Power indicator (PW) Output indicator (UP)
Power (13-14)
One Shot
Power Output
Time limit contact NC (9-1, 10-2, 11-3, 12-4) Time limit contact NO (9-5, 10-6, 11-7,12-8) Run/Power indicator (PW) Output indicator (UP)
Power (13-14)
Repeat Cycle OFF-Start Time limit contact NC (9-1, 10-2, 11-3, 12-4)
Power Output
Time limit contact NO (9-5, 10-6, 11-7,12-8) Run/Power indicator (PW) Output indicator (UP)
Power (13-14)
Repeat Cycle ON-Start
Power Output
Time limit contact NC (9-1, 10-2, 11-3, 12-4) Time limit contact NO (9-5, 10-6, 11-7,12-8) Run/Power indicator (PW) Output indicator (UP)
50
Rockwell Automation Publication 700-TD552A-EN-P
Timer Circuit
UP
PW