The text of a spec sheet · part 6 of 13
Relays and Timers Specifications, Bulletin Number 700, pages 51 to 60
Pages 51 to 60 of 128
The original document is the PDF (10 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HN122
Page 51
Relays and Timer Specifications
700-HNC Plug-in Timing Relay
General Timer Functions
Pulse Operation A pulse output for a certain period can be obtained with a random external input signal. Use the 700-HNC timing relay in interval mode as shown in the following timing charts.
Output Indicator (Orange) (Lit: Output ON)
Run/Power Indicator (Green) (Lit: Power ON)
1
2
3
4
5
6
7
8
Power (9-14)
Main Dial Set the desired time according to time range selectable by DIP switch.
External short circuit (5-13) External input (9-13)
9
10
11
Time limit contact NC (10-2, 11-3, 12-4) Run/Power indicator (PW) Output indicator (UP)
14
Timer ( - ) Circuit
(~)
Time limit contact NO (10-6, 11-7, 12-8)
12
13
(+) (~)
UP FW External Input
Note:
~ (
50 ms min.
)
t: Set time Rt: Reset time
DIP Switch Settings Time Ranges Cat. No.
Time Range
Time Setting Range
700-HNC44AZ12 700-HNC44AZ24 700-HNC44AZ48 700-HNC44AZ11 700-HNC44AZ25 700-HNC44AA24 700-HNC44AA12 700-HNC44AA23
1s
0.1 s…1 s
Yes
10 s
1 s…10 s
No
1 min
0.1 s…1 min
No
10 min
1…10 min
No
1 min
0.1…1 min
Yes
10 min
1…10 min
No
1 hr
0.1…1 hr
No
1 hr
1…10 hr
No
700-HNC44BZ12 700-HNC44BZ24 700-HNC44BZ48 700-HNC44BZ11 700-HNC44BZ25 700-HNC44BA24 700-HNC44BA12 700-HNC44BA23
Setting
Factory-Set
Note: The top two DIP switch pins are used to select the time ranges.
Operating Mode
Setting
Factory-set
ON-delay
Yes
One Shot
No
Repeat Cycle OFF-start
No
Repeat Cycle ON-start
No
Note: The bottom two DIP switch pins are used to select the time ranges.
Rockwell Automation Publication 700-TD552A-EN-P
51
Page 52
700-HNC Plug-in Timing Relay
Relays and Timer Specifications
Approximate Dimensions Approximate Dimensions are shown in millimeters (inches) where not specified. Approximate Dimensions are not intended to be used for manufacturing purposes.
Timers Front Mounting 30.0 (1-3/16) 6.1 (15/64)
Fourteen 3 x 1.2 mm Elliptic Holes
4.0 (0.15)
6.4 (0.25)
52.6 (2.07) 63.0 (2.48)
8
7
6
5
4
3
2
1
28 (1.10) 6.3 (.024) 21.5 max (084)
24.9 (57/64) 21.1 (53/64)
4.2 (5/32)
14
13
12
11
10
62.0 (2-15/64)
65.0 (2-9/16)
9
26.0 (1-1/64)
Cat. No. Wire Size: 2 x 1.5 mm2 (#2-16 AWG…#1-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) - Torque: 0.8 N•m (7 lb•in)
Cat.No. 700-HNC
27.0 (1.06)
Panel Mounting
60.9 (2.40) 21.5 (0.85)
28.9 (1-9/64) 24.5 (31/32) 35.6 (1.40)
76.0 (2.99)
67.0 (2-5/8)
3.2 (0.13) 18.9 (0.74) 34.9 (1.37)
32.0 (1.26) 35.5 (1.40) 2.5 (0.10)
#4-40 M3
30.0 (1-11/64) Cat. No. 700-HN103
Cat. No. HN-104
Single wire: 0.2…2.5 mm2 (#24 AWG…14 AWG) Double wire: 2 x 0.2 mm2…2 x 1.5 mm2 (2 x 24 AWG…2 x 16 AWG) Wire type: solid or stranded, copper only Strip length: 8 mm (5/16 in.), Torque: 0.5 N•m (4.4 lb•in)
Single Wire: 0.2…2.5 mm2 ( #24 AWG…14 AWG) Double Wire: 2 x 0.2 mm2…2 x2.5 mm2 (2 x 24 AWG…2 x 14 AWG) Wire Type: solid or stranded, copper only Strip Length: 7 mm (9/32 in.), Torque: 0.5 N•m (4.4 lb•in)
Total height of 700-HN128 + 700-HNC is 82.5 mm.
52
Rockwell Automation Publication 700-TD552A-EN-P
Page 53
Relays and Timer Specifications
700-HNC Plug-in Timing Relay
Specifications Ratings Item Pilot Duty Rating
NEMA B300
Rated Supply Voltage
24V AC; 12, 24V DC
Pin Type
Plug-in
Operating Mode
ON-delay, One Shot, Repeat Cycle OFF start, or Repeat Cycle ON start selectable with DIP switch.
Operating Voltage Range
85%…110% of rated supply voltage (12 VDC: 90%…110% of rated supply
Power Consumption
24V AC:Relay ON:approx. 0.8 VA (at 24 VAC, 60 Hz) Relay OFF:0.5 VA (at 24V AC, 60 Hz) 12V DC:Relay ON:approx. 0.4 W (at 12V DC) Relay OFF:0.1 W (at 12V DC) 24V DC:Relay ON:approx. 0.5 W (at 24V DC) Relay OFF:0.2 W (at 24V DC)
Control Outputs
5 A at 250V AC, resistive load (cosφ = 1) The minimum applicable load is 10 mA at 5 VDC (P reference value). Characteristics
Make Break
120V AC
30 A
240V AC
15 A
120V AC
3A
240V AC
1.5 A
Hp at 240V AC
1/6 Hp
Accuracy of Operating Time
±1% FS max. (1 s range: +1%±10 ms max.)
Setting Error
±15%+50 ms FS max.
Reset Time
Min. power-opening time:
Influence of Voltage
±2% FS max.
Influence of Temperature
±2% FS max.
Insulation Resistance
100 mΩ min. (at 500V DC)
Dielectric Strength
2000V AC, 50/60 Hz for 1 min (between operating circuit and control output, or contacts of different poles) 1000V AC, 50/60 Hz for 1 min (between non-continuous contacts)
Vibration Resistance
Malfunction:10…55 Hz, 0.5 mm single amplitude
Shock Resistance
Malfunction:100 m/s2 (approx. 10G)
Ambient Temperature
Operating:-10 °C…50 °C (with no icing) Storage:-25 °C…65 °C (with no icing)
12, 24V DC: 0.1 s max. (including halfway reset) 24V AC: 0.5 s max. (including halfway reset)
Ambient Humidity
Operating:35…85%
Life Expectancy
Mechanical:10 000 000 operations min. (under no load at 1800 operations/hr) Electrical:100 000 operations min. (3 A at 250V AC, resistive load at 1800 operations/hr)
Impulse Withstand Voltage
Between power terminals: 1 kV
Noise Immunity
±1.5 kV, square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static Immunity
Destruction:8 kV Malfunction:4 kV
Enclosure Rating
IP20
Weight
Approx. 18 g
EMC
Emission Enclosure:EN55011 Group 1 class A Emission AC Mains:EN55011 Group 1 class A Immunity ESD:EN61000-4-2:4 kV contact discharge (level 2) 8 kV air discharge (level 3) Immunity RF-interference:ENV50140:10 V/m (amplitude modulated, 80 MHz…1GHz) (level 3) 10 V/m (pulse modulated, 900 MHz) Immunity Conducted Disturbance:ENV50141:10 V (0.15…80 MHz) (level 3) Immunity Burst:EN61000-4-4:2 kV power-line (level 3) 2 kV I/O signal-line (level 4)
Standards
UL508, CSA C22.2 No. 14, EN/IEC 60947-5-1, EN/IEC 61812-1
Certifications cURus Recognized Component (File No. E14843, Guide NRNTZ/NRNT8), CE Marked, C-Tick Marked
When using 700-HNK timer in any place where the ambient temperature is more than 50 °C, supply 90…110% of the rated voltages (12V DC: 95…11 % of the rated voltage).
Note: t: Set time Rt: Reset time
Rockwell Automation Publication 700-TD552A-EN-P
53
Page 54
700-HNK - Ultra Slim Timing Relay
Relays and Timer Specifications
Bulletin 700-HNK, Ultra-Slim Timing Relay General Timer Functions
Run/Power Indicator (Green) (Lit: Power ON) Main Dial Set the desired time according to time range selectable by DIP switch.
Output Indicator (Orange) (Lit: Output ON)
Timing Chart Operating Mode
700-HNK41…
700-HNK42… Rt t t
Time limit contact NC (4-2)
t Output t
Power (1-8)
ON-Delay
Power
Rt t
Power (1-5)
Time limit contact NO 4-3, 5-6
Time limit contact NO (4-3)
Run/Power indicator (PW)
Run/ Power
Output indicator (OUT)
Indicator (PW) Output Indicator (OUT)
Power (1-5)
Rt t
One shot
Time limit contact NC (4-2)
Power
Time limit contact NO (4-3)
Output
Run/ Power t
Power (1-8) Time limit contact NO (4-3, 5-6) Run/Power indicator (PW) Output indicator (OUT)
Indicator (PW) Output Indicator (OUT) t t t t
Power (1-5)
t
Repeat Cycle OFF-Start
Time limit contact NC (4-2)
Power
Time limit contact NO (4-3)
t t t
Output indicator (OUT)
Output Indicator (OUT)
t t t t t
Power (1-5)
Repeat Cycle ON-Start
Time limit contact NC (4-2)
Power
Time limit contact NO (4-3)
Output t t
Run/ Power Indicator (PW) Output Indicator (OUT)
54 t
Run/Power indicator (PW)
Indicator (PW)
t t
Time limit contact NO (4-3, 5-6)
Run/ Power
Output t
Power (1-8)
Power (1-8) Time limit contact NO (4-3, 5-6) Run/Power indicator (PW) Output indicator (OUT)
Rockwell Automation Publication 700-TD552A-EN-P t t t
Page 55
700-HNK Ultra Slim Timing Relay
Relays and Timer Specifications Wiring Diagrams 3 4
5
4
2
6
3 Timer Circuit
1
( ) ( )
~
OUT
PW
Timer
1 Circuit ( ) ( ~ ) OUT PW
8
( ) ( )
~
5 ( ) (~)
Cat. No. 700-HNK41...
Cat. No. 700-HNK42... A pulse output for a certain period can be obtained with a random external input signal. Use the 700-HNK in interval mode as shown in the following timing chart.
t t
Rt t
Power (3-8)
5
4
Rt
External Short Circuit (1-4) External Input (1-3) 3 1 ( ) ( )
Time Limit Contact NO (6-5) Run/Power Indicator (PW) Output Indicator (OUT)
6 Timer Circuit
~ OUT PW
50 ms min.
8 ( ) ( )
~
Note: t: Set time Rt: Reset time
External Input
~
(
)
Mode
Terminals
Pulse Operation
Power supply between 3 and 8 Short-circuit between 4 and 1 Input signal between 3 and 1
Operating mode; One shot and all other modes
Power supply between 1 and 8
Rockwell Automation Publication 700-TD552A-EN-P
55
Page 56
700-HNK - Ultra Slim Timing Relay
Relays and Timer Specifications
Time Ranges Cat. No.
Time Range
Time Setting Range
1s
0.1…1 s
Yes
10 s
1…10 s
No
1 min
0.1 s…1 min
No
10 min
1…10 min
No
1 min
0.1…1 min
Yes
10 min
1…10 min
No
1 hr
0.1…1 hr
No
10 hr
1…10 hr
No
700-HNK41AZ12 700-HNK41AZ24 700-HNK41AA24 700-HNK42AZ12 700-HNK42AZ24 700-HNK42AA24
700-HNK41BZ12 700-HNK41BZ24 700-HNK41BA24 700-HNK42BZ12 700-HNK42BZ24 700-HNK42BA24
Setting
Factory-Set
Note: The left two DIP switch pins are used to select the time ranges.
Operating Modes Operating Mode
Setting
On-delay
Yes
One Shot
No
Repeat Cycle Off-start
No
Repeat Cycle On-start
No
Note: The right two DIP switch pins are used to select the operating modes.
56
Factory-set
Rockwell Automation Publication 700-TD552A-EN-P
Page 57
700-HNK - Ultra Slim Timing Relay
Relays and Timer Specifications Approximate Dimensions
Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes. 47.4 (1.86) 46.0 (1.81)
12.8 (0.50)
31.2 (1.22)
6 (0.23)
2.03 (5/64)
Five M3.5 x 0.315 Screws
21 6 4.06 (5/32)
12 2 3.0 Ø (1/8) Use M3 Screws
84.1 5 (+) (3-5/16) (A1)
39.5 (1-17/32)
35.5 (1-13/32)
1 (-) (A2) 4.06 (5/32) 15.6 (5/8)
6.0 (0.23)
Bulletin 700-HNK42 DPST-NO Contact Approximate Dimensions
Bulletin 700-HNK41 SPDT Contact Approximate Dimensions
11 4 14 3
46.0 (1.81)
31.2 (1.22) 28.8 (1.13)
28.8 (1.30)
7.11 (9/32)
47.0 (1.86)
12.8 (0.50)
29.9 (1-3/16) 54.1 (2-1/8)
7.11 (9/32)
22 7 24 5
2.03 (5/64)
Eight M3.5 x 0.315 Screws
14 4
84.1 (3-5/16) 8 (+) (A1) 4.06 (5/32)
11 3
12 2
4.06 (5/32) 39.5 (1-17/32)
3.0 Ø (1/8) Use M3 Screws
15.6 (5/8)
35.5 (1-13/32)
1 (-) (A2) 29.9 (1-3/16) 54.1 (2-1/8)
Cat No. 700-HN121
Cat No. 700-HN122
Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in) Total height: 700-HN121 + 700-HNK41 is 78.0 mm. Holes required for mounting [3 mm (1/8 in.) diameter].
Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in) Total height: 700-HN122 + 700-HNK42 is 78.0 mm. Holes required for mounting [3 mm (1/8 in.) diameter].
Rockwell Automation Publication 700-TD552A-EN-P
57
Page 58
Relays and Timer Specifications
700-HR Timing Relay
700-HR, HRS, -HRV
70-HRP
700-HRC
700-HRM
700-HRF
700-HRY
700-HRQ
700-HRT (Transistor Outputs)
Electrical Ratings Pilot Duty Rating
NEMA B300, Thermal Current (Ith)
5A
100 mA @ 30V DC max.
120V AC
30 A, 240V AC
15 A, 120V AC
3A, 240V AC
1.5 A
Make Break Hp at 120V
1/6 Hp (0.12 kW), 1/4 Hp (0.18 kW)
1/6 Hp (0.12 kW)
Hp at 240V
1/3 Hp (0.25 kW)
Resistive Load
5 A at 250V AC/30V DC
Inductive Load
AC-15 @ 250V AC, 3 A/DC-13 @ 30V DC, 0.5 A
1/4 Hp (0.18 kW)
1/6 Hp (0.12 kW), - Accuracy of Operating Time
±0.2 % FS max. (±0.2 % ±10 ms max. in a range of 1.2 s)
Setting Error
±5 % FS ±50 ms (The value is ±5 % FS +100 ms to -0 ms max. when the C or D mode signal of the 700-HRVs are OFF.)
Influence of Voltage
±0.2 % FS max. (±0.2 % ±10 ms max. in a range of 1.2 s)
Influence of Temperature
±1 % FS max. (±1 % ±10 ms max. in a range of 1.2 s)
Permissible Leakage Current Power Consumption
-HR52, -HRS
-HRV
-HRP, -HRC
-HRM
-HRF
-HRY
-HRQ
-HRT
240V AC, Output ON
2.1 VA
2.5 VA
2.0 VA
2.1 VA
10 VA
12 VA
0.4 VA, 240V AC, Output OFF
1.3 VA
1.8 VA
2.0 VA
1.3 VA
10 VA
12 VA
0.4 VA, 24V DC, Output ON
0.8 W
0.9 W
0.9 W
0.8 W
1.0 W, 0.2 W
0.3 W
24V DC, Output OFF
0.2 W
0.3 W
0.9 W
0.2 W
1.0 W, 0.2 W
0.2 W
Dielectric Strength
2000V AC (1000V AC for 700-HRT), 50/60 Hz for 1 min (contact to frame) 2000V AC (1000V AC for 700-HRT), 50/60 Hz for 1 min (between control output terminals and operating circuit) 2000V AC, 50/60 Hz for 1 min (pole-to-pole) 1000V AC, 50/60 Hz for 1 min (between contacts not located next to each other) 2000V AC, 50/60 Hz for 1 min (contact to coil)
Vibration Resistance
Malfunction: 10…55 Hz with 0.5 mm double amplitude each in three directions for ten minutes each
Shock Resistance
Malfunction: 100 m/s2 (10 G)
Design Specifications
Mechanical 98 m/s2 (10 G)
294 m/s2 (10 G)
98 m/s2 (10 G)
100 m/s2 (10 G)
±1kV for 48V DC
±1.5 kV for ±600V DC
Environmental Noise Immunity
±1.5 kV for ±600V DC
±400V for 12V DC
Static Immunity
Malfunction: 8 kV
Ambient Temperature
Operating: -10…55 °C (with no icing) Storage: -25…65 °C (with no icing)
Ambient Humidity
Operating: 35…85 %
Life Rxpectancy (Min. Operations)
Mechanical:20 000 000. (under no load at 1800 operations/h) Electrical: 100 000 (5 A at 250V AC, resistive load at 1800 operations/h)
EMC
(EMI) EN50081-2 Emission Enclosure:EN55011 Group 1 class A Emission AC Mains: EN55011 Group 1 class A (EMS) EN50082-2 Immunity ESD:EN61000-4-2:4 kV contact discharge (level 2) 8 kV air discharge (level 3) Immunity RF-interference from AM Radio Waves: ENV50140:10 V/m (80 MHz…1 GHz) (level 3) Immunity RF-interference from Pulse-modulated Radio Waves:ENV50204:10 V/m (900 ±5 MHz) (level 3) Immunity Conducted Disturbance:ENV50141:10 V (0.15…80 MHz) (level 3) Immunity Burst:EN61000-4-4:2 kV power-line (level 3) Immunity Surge:EN61000-4-52 kV I/O signal-line (level 4) 1 kV line to line 2 kV line to ground (level 3)
Degree of Protection
IP40 (panel surface)
Construction Mech: 107 Electrical: 104
Weight
Approx. 90 g
Certifications
CSA Certified (File No. 70751), UL Recognized (File No. E14843 Guide No. NRNT2), CE Marked, C-Tick Marked
Standards
UL 508, CSA C22.2 No. 14, EN 61812-1, EN 61000-6-2, -6-4
58
Rockwell Automation Publication 700-TD552A-EN-P
Page 59
700-HR Timing Relays
Relays and Timer Specifications Timer Functions 700-HR Multifunction Timer Power indicator (green) (Flashes when Timer operates; lit when Timer stops operating) Operating mode display window
Operating mode selector Select a mode from: A, B, B2, C, D, E, J, and G (700-HR52, -HRV, and HRT 6) A, E, B2, J, and B (800-HRS, -HRP, and -HRT4)
Output indicator (orange) (Lit when energized)
Scale range display windows Time unit display window
Time Range selector (select one from 1.2, 3, 12, and 30 at full scale.)
Time setting knob (set time)
Time unit selector (select one from sec, 10 s, min, 10 m, hrs, and 10 h)
700-HRC -HRM On-Delay Timer Power indicator (green) (Flashes when Timer operates; lit when Timer stops operating)
Output indicator (orange) (Lit when energized)
Scale range display windows Time unit display window Time Range selector (select one from 1.2, 3, 12, and 30 at full scale.)
Time setting knob (set time)
Time unit selector (select one from sec, 10 s, min, 10 m, hrs, and 10 h)
700-HRF Twin Timer OFF indicator (green) Lit when the output is OFF. OFF-time unit display ON indicator (orange) Lit when the output is ON.
OFF-time unit selector (select one from sec, 10 s, min., 10 m, hrs, and 10 h) ON-time setting knob (with orange pointer) For ON-time setting
Scale range display windows
OFF-time setting knob (with green pointer) For OFF-time setting Time range selector (select one from 1.2, 3, 12, and 30 at full scale.)
ON-time unit display ON-time unit selector (select one from sec, 10 s, min., 10 m, hrs, and 10 h)
700-HRY Star-Delta Timer Star operation indicator (green) Delta operation indicator (orange)
Time unit display (sec. is fixed)
Scale range display windows Time setting knob (for setting star operation time) Star operation time range selector (select one from 6, 12, 60 and 120 at full scale.)
Star-delta transfer time selector (select one from 0.05 s, 0.1 s, 0.25 s, 0.5 s, 0.75 s and 1.0 s) Star-delta transfer time unit display
700-HRQ True Off-Delay Timer Scale range display windows
Output indicator (red) Time setting knob (for setting OFF-delay time)
Time range selector (select one from 0.6, 1.2, 6, and 12 at full scale.) True OFF-Delay time unit display
Rockwell Automation Publication 700-TD552A-EN-P
59
Page 60
700-HR Timing Relays
Relays and Timer Specifications
Specifications for Start, Gate, Reset Signal (Cat. Nos. 700-HR52, -HRT6, -HRV, -HRQR) Start, Reset, and Gate signals are typically contact closures or signals from a solid-state sensor.
(R) Reset Signal The reset signal is not required for normal operation. Reset can be accomplished by removing power from the timing relay. To reset the timer without removing power, a signal must be applied which resets the timing cycle and returns the output contacts to their shelf state. The reset signal will override both the start signal and gate signal. The reset signal can be either momentary or maintained.
Power to Timing Relay t1< T t1
T t1 t2
Reset Signal Timing Cycle Timing Relay Output
(G) Gate Signal The gate signal is not required for normal operation. The gate signal provides a pause or retentive timing function. When the gate signal is applied the timing cycle is momentarily interrupted. When the signal is removed, the timing cycle resumes timing at the point the cycle was interrupted and will continue timing until the time delay is completed or the gate signal is re-applied.
Power to Timing Relay t1+t2 = T
Gate (pause) Timing Cycle Timing Relay Output
Contact Signal, Cat. Nos. 700-HR52, -HRT6, -HRQR Contact closure provides signal to timer. A low energy signal is generated by the 700-HR timing relay. For optimum reliability, use contacts designed for low energy switching (5V, 1 mA) (Bul. 800F-X__V, 800T-X__V). No external voltage should be connected to the contact signal.
R S G
5v, 1mA
Contact Signal, Cat. No. 700-HRV For use in applications where it is not possible to use contacts designed for low energy switching. Contact closure provides signal to timer. A signal is generated by the 700-HR timing relay, and is the same potential as the supply voltage of the timing relay. No external voltage should be connected to contact signal. 700-HRV52TU24 supply voltage: 24...48V AC, 12...48V DC / 700-HRV52TA17 supply voltage: 100...240V AC, 100...125V DC.
S
U
U
(+)
( )
Solid-State Signal, Cat. Nos. 700-HR52, -HRT6 Timing relay is suitable for use with a 3-wire NPN 12...24V DC sensor. Supply voltage potential of sensor must be the same as the supply voltage potential of the timing relay. Permissible off-state leakage current from sensor: 0.01 mA max.
+ 12...24V DC COM
0.1mA
R S G
COM ( )
(+) 12...24V DC
Solid-State Signal, Cat. No. 700-HRV Timing relay is suitable for use with a 3-wire NPN or PNP 12...24V DC sensor. Supply voltage potential of sensor must be the same as the supply voltage potential of the timing relay. Permissible off-state leakage current from sensor: 0.01 mA max.
S
S
PNP Wiring Diagram
60
+ 12...24 V DC COM
+ 12...24V DC COM
COM ( ) (+) 12...24V DC
Rockwell Automation Publication 700-TD552A-EN-P
NPN Wiring Diagram
COM ( ) (+) 12...24V DC