Relays and Timers Specifications, Bulletin Number 700, pages 61 to 70

Pages 61 to 70 of 128

The original document is the PDF (10 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 700-HN122

Page 61

700-HR Timing Relays

Relays and Timer Specifications Signal Specifications Circuit Impedance

Circuit impedance can be used to calculate the maximum wiring distance from the signal switch to the timing relay, for example. Permissible signal-ON impedance: 1 kΩ max. Permissible signal-OFF impedance: 100 kΩ min.

Power-OFF Reset

Min. power-off time: 0.1 s, Reset Voltage: 10% max. of rated voltage

Signal Duration

Min. pulse width: 0.05 s

Signal Options

700-HR52

700-HRT6

700-HRV5

700-HRQR

Start

X

X

X

NA

Reset

X

X

NA

X

Gate

X

X

NA

NA

Nomenclature Timing Charts Mode A, ON-Delay a. Needs continuous input power applied. b. Timing is initiated by the leading edge of the start signal. c. Contacts change state after timing is complete. d. Additional start signals during timing don't reset timing or contacts. e. When the input power is removed contacts return to shelf state.

Basic Operation T

Power

T

Power

Start

Start

Output (N.C.)

Output

Output (N.O.) Power LED

Mode B, Repeat Cycle, Off Start a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. Additional start signals during timing do not reset timing or contacts. c. For the first time period the contacts remain in their shelf state. When that time period is complete contacts change state for the same time period (time on = time off). d. This cycle repeats itself until input power is removed or reset signal is applied. When the input power is removed or reset signal is applied contacts return to the shelf state.

Basic Operation T

T

T

Power Start Output (N.C.) Output (N.O.) Power LED

T

T

T

Power Start Output a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. Additional start signals during timing do not reset timing or contacts. c. For the first time period the contacts change state. When that time period is complete contacts return to the shelf state for the same time period (time on = time off). d. This cycle repeats itself until input power is removed or reset signal is applied. When the input power is removed or reset signal is applied contacts return to the shelf state.

Basic Operation Power Start Output (N.C.)

T

T

T

Power Start

T

T

T

Output

Output (N.O.) Power LED

Rockwell Automation Publication 700-TD552A-EN-P

61

Page 62

700-HR Timing Relays

Relay and Timer Specifications

Mode C, Watchdog monitor (Trigger = Signal On/Off) a. Need continuous input power applied. b. Contacts change state immediately when start signal is applied or when start signal is removed (only if timing cycle was complete). c. Timing is initiated at the leading edge of the start signal. After the first timing cycle is complete, timing is initiated by the trailing edge of the start signal. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to the shelf state.

Power

T

T t t<T

T

Basic Operation

Start Output (N.C.)

T

Power Start

Output (N.O.) Power LED Mode D, Off-Delay (Trigger=Signal Off)

T

Output a. Need continuous input power applied. b. Contacts change state immediately when start signal is applied. c. Timing is initiated by the trailing edge of the start signal. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to the shelf state.

Basic Operation t

T

Power t<T

Start

Power Start

Output (N.C.)

Output

T

Output (N.O.) Power LED

Mode E, One-Shot (Trigger=Signal On) 700-HR52, -HRV, and -HRT6 a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. c. Contacts change state immediately when start signal is applied. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to shelf state.

Basic Operation Power

T t

T t<T Power Start

Start Output (N.C.) Output (N.O.) Power LED

T

Output

Mode E, One-Shot (Trigger = Power On) 700-HRS, -HRP, and -HRT4 a. Need continuous input power applied. b. Timing is initiated when the input power is applied. c. At the end of the time period contacts return to the shelf state. d. Relay timing is reset when input power is removed.

Basic Operation Power Timed Output (N.C.) Timed Output (N.O.) Power LED 62

T t<T Power Output

Rockwell Automation Publication 700-TD552A-EN-P

T

Page 63

Relays and Timer Specifications

700-HNC Plug-in Timing Relay

Mode J, Delayed One-Shot (Trigger=Power On) a. Need continuous input power applied. b. No start signal applied. c. Timing is initiated when input power is applied. c. Contacts change state after the timing for a fixed time of 1s +/-0.5s d. At the end of the 1 sec period the contacts return to the shelf state. e. When the input power is removed contacts return to the shelf state.

Basic Operation T

Power

T

1s ±0.5s

Output (N.C.)

Power 1s ±0.5s

Output (N.O.)

Output (N.O.)

Power LED

Power LED Mode Star-Delta a. Need continuous input power applied. b. No start signal required. Timing is initiated when input power is applied. c. Star ouput contact changes state when input power is applied.

d. After timing is complete star output contact returns to the shelf state then both the star & delta contacts remain in shelf states until transfer time setting is complete. e. Delta output contact changes state after transfer time is complete. f. Instantaneous contact changes state when input power is applied. g. All contacts return to the shelf state when input power is removed.

Power

Basic Operation t2 t1

Output (N.C.)

Power

Output (N.O.)

Instantaneous Output

Output 8-5,

LED

Output 8-5,

LED

Output 8-6,

LED

Output 8-6,

LED t1 t2

Mode True Off-Delay (Trigger=Power Off) a. Continuous input power is NOT required. b. No start signal applied. c. Contacts change state immediately when input power is applied. d. Timing starts when input power is removed. e. At the end of the time period contacts return to the shelf state. f. Relay timing is reset when input power is reapplied while the relay is timing. Contacts remain in energized state. t<T T t

T

Basic Operation

Power

T

Output (N.C.)

Power

Output (N.O.)

Output

Relay On LED

Relay On LED

Rockwell Automation Publication 700-TD552A-EN-P

63

Page 64

700-HR Timing Relay

Relays and Timer Specifications

Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes. 81.5 (3-7/32) 52.3 (2-1/16)

15.0 (19/32)

Mode

3 2

4 hrs

6

Range

78 (3.07)

63.7 (2.51)

0.7 (0.03)

48.0 (1-57/64)

5 0

6 (.24)

Up

1

48.0 (1-57/64)

15 (.59)

Power

A

39 (1.54)

Unit

44.8 (1.76)

48.0 (1-57/64)

6.0 (1/4)

Cat. No. 700-HR, -HRM, -HRC, -HRF, -HRS, -HRV, -HRP, -HRY, -HRQ Timing Relays

Cat. No. 700-HR, -HRM, -HRC, -HRF, -HRS, HRV, HRP

Cat. No. 700-HRY, -HRQ Timing Relays

Timing Relays

Panel

35.0 (1-3/8)

45.0 (1-25/32)

57.0 (2-11/32)

32.0 (1-1/4)

45.0 (1-49/64)

24.0 (31/32)

45.0 (1-25/32) Cat. No. 700-HN129, 11-pin Cat. No. 700-HN108, 8-pin socket

Cat. No. 700-HR… Panel Cutout

30 (1-3/16) 22

Cat. No. 700-HN130 Retainer

24.6 (31/32) 20.8 (53/64)

40.1 (1-37/64)

26 (1-1/32)

12

24

14 5

2

1

8

Ø 24.9 (63/64)

7

4

6

3

65 (2-35/64) 7

Ø 4.2 (5/32)

2 8

1

21

11

A2

54.9 (2-5/32)

A1 3

38 (1-1/2)

#4_40 M3

4

5

51.1 (2-1/64)

6

33.0 (1-19/64)

14.7 (37/64)

Cat. No. 700-HN100

Cat. No. 700-HN125

Wire Size: 2x2.5 mm Single Wire, Up to #12 AWG Double Wire, 2x2.5 mm (#2-14 AWG…#2-20 AWG) (Either Solid or Stranded) Strip length: 9 mm (3/8 in), Torque: 0.8 N•m (7 lb•in)

Wire Size: 2x2.5 mm Single Wire - Up to #12 AWG Double Wire, 2x2.5 mm (#2-14…#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in), Torque: 0.8 N•m (7 lb•in)

Panel Mounting 30 (1-3/16) 24

21 22

1 12

32 6

7

9

3

65 (2-35/64) 10

11

1

54.9 (2-5/32)

9

4

8 5

7 6

Ø 4.2 (5/32)

51.1 (2-1/64)

2

14

#4_40 M3

A2 31 11 A1

38 (1-1/2)

64

26.9 (1.06)

10

3 4

24.6 (31/32) 20.8 (53/64)

11

2

5

8

34

59.2 (2-1/3) 7.9 (0.31)

26 (1-1/32)

52.3 (2.06)

Cat. No. 700-HN100

Cat. No. 700-HN126

Wire Size: 2x2.5 mm Single Wire, Up to #12 AWG Double Wire, 2x2.5 mm (#2-14 AWG…#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.), Torque: 0.8 N•m (7 lb•in.)

Wire Size: 2x2.5 mm Single Wire - Up to #12 AWG Double Wire, 2x2.5 mm (#2-14…#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in), Torque: 0.8 N•m (7 lb•in)

Rockwell Automation Publication 700-TD552A-EN-P

Page 65

Relays and Timer Specifications

700-HX Plug-in Timing Relay

General Timer Functions

Operation Key

Display Section 1. Key Protect Indicator (orange) 2. Control Output Indicator (orange) 3. Reset Indicator (orange) 4. Present Value Display (Main display) (Character height: 12 mm, red *) * Characters on models with screw terminals can be switched between red, green, and orange.

1 2 3 8

4

8. Mode Key

5

9. Reset Key

6

(Changes modes and setting items) (Resets present value and output)

7

10. Up Keys 1 to 4

10

11. Down Keys 1 to 4

11

9

Switches

5. Time Unit Indicators (Color is same as present value display.) (If the time range is 0 min, 0 h, 0.0 h, or 0 h 0 min, these indicators flash to indicate timing operation.)

Front View

12. Key-protect Switch (Default setting)

12

OFF (Disabled)

ON (Enabled)

6. Set Value Display (Sub-display) (Character height: 6 mm, green)

7. Set Value 1, 2 Indicator (green) Character Size for Present Value Display

12mm

Character Size for Set Value Display

6mm

Rockwell Automation Publication 700-TD552A-EN-P

65

Page 66

700-HX Plug-in Timing Relay

Relays and Timer Specifications

Specifications Electrical Ratings Pilot Duty Rating

NEMA B300

Rated supply voltage

100 to 240V AC, 24V AC/12 to 24V DC (50/60Hz) (permissible ripple: 20%(p-p) max.)

Operating voltage range Power consumption Inrush Current

Make Break

85…110% of rated supply voltage 100…240V AC

4.3VA

24V AC/12…24V DC

3.4VA/1.7 W

100…240V AC

3A

24V AC/12…24V DC

5A

120V AC

30 A

240V AC

15 A

120V AC

3A

240V AC

1.5 A

Hp at 120V AC

1/4 Hp

Hp at 240V AC

1/3 Hp Mechanical

Mounting Method

Flush mounting, surface mounting, DIN mounting

Display

Seven-segment, negative transmissive LCD; Present value (red, 12 mm high characters); Set value (green, 6 mm high characters)

Digits

Four digits Time ranges

Timer

Inputs

0.000…9.999 s, 0.00…99.99 s, 0.0…999.9 s, 0…9999 s, 0 min 00 s…99 min 59 s, 0.0…999.9 min, 0 hr 00 min…99 hr 59 min, 0.0 hr…999.9 hr, 0 hr…9999 hr

Timer modes

Elapsed time (Up), remaining time (Down), selectable

Output modes

A, A-1, A-2, A-3, B, B-1, D, E, F, Z, S, tOFF, tON, tOFF-1, or tON-1

Input signals

Start, reset

Input method

No-voltage input via:NPN transistor or switching of contact

Start, reset, gate

Minimum input signal width: 1 or 20 ms (selectable)

Power reset

Minimum power-opening time: 0.5 s (Except for A-3, B-1, and F mode) SPDT contact output: 5 A at 250V AC, resistive load (cosine=1) Minimum applied load: 10 mA at 5 V DC (failure level: P, reference value)

Control output External Power Supply

No

Key Protect

Yes

Memory Backup

EEP-ROM (overwritten 100 000 times min), which can store data for 10 years min.

Accuracy of Operating Time and Setting

Power-ON start: +-0.01% +-50 ms max. * to be rated against set value Signal start: +- 0.005% +-30 ms max. * to be rated against set value Signal start at transistor output model: +- 0.005% +-3 ms max.‡ If the set value is within the sensor waiting time (250 ms max.)

The values are based on the set value. ‡ The value is applied for a minimum pulse width of 1 ms.

66

Rockwell Automation Publication 700-TD552A-EN-P

Page 67

Relays and Timer Specifications

700-HX Plug-in Timing Relay

Insulation Resistance

100 mΩ min. (at 500V DC)

Dielectric Strength

2000V AC, 50/60Hz for 1 min between current-carrying terminals and non-currentcarrying metal parts (1000V AC for 24V AC/12 to 24V DC type), 1000 VAC, 50/60 Hz for 1 min between non-continuous contacts

Noise Immunity

'+-1.5 kV (between power terminals) for 100 to 240 VAC, +-480V for 24VAC/12 to 24VDC, and +-600V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)

Static Immunity

±8 kV (malfunction), ±15 kV (destruction)

Vibration Resistance

Malfunction

10…55 Hz with 0.35 mm single amplitude each in three directions for 10 min

Shock Resistance

Malfunction

98 m/s2 (approx. 10 G) each in three directions

Mechanical

10 million operations min. (under no load at 18 000 operation/hr)

Electrical

100 000 operations min. (5 A at 250V AC, resistive load at 1800 operation/hr)

Life Expectancy

EMC

(EMI)

EN61812-1

Emission Enclosure:

EN55011 Group1 class A

Emission AC mains:

EN55011 Group1 class A

(EMS)

EN61812-1

Immunity ESD:

EN61000-4-2: 4 kV contact discharge (level2) 8 kV air discharge (level3)

Immunity RF-interference:

EN61000-4-3: 10 V/m

Enclosure Ratings

Panel surface:IP66 and NEMA Type 4X (indoors)‡

Weight

Approx. 100 g

Certifications

CE Certified; cURus (File No. E14843, Guide NRNTZ/NRNT8), C-Tick Marked

Standards

EN61010-1, EN 61326, VDE0106/P 100, CSA C22.2 No. 14, UL 508

700-HX User Manual, pub. number 700-UM002_-EN-D, available at Literature Library. ‡ An attached waterproof packing is necessary to ensure IP66 waterproofing between the 700-HX and installation pan.

Rockwell Automation Publication 700-TD552A-EN-P

67

Page 68

700-HX Plug-in Timing Relay

Relays and Timer Specifications

Timing Charts One-Shot Sustained Output

One-shot outputs can be set to 0.1s, 0.5 s, 1 s, 5 s, 10 s, or 20 s.

Output Mode A Mode: Signal ON-Delay (Timer resets when power comes ON.)

Timing starts when the start signal goes ON. While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF. The control output is controlled using a sustained or one-shot time period.

Power

Start signal

Basic Operation

Gate*

Power

Reset t t t

Control output

** Start Signal Input Timing

Set value Timing diagram

UP

Output

0

Set value DOWN 0

*Output is instantaneous when setting is 0. ** Start signal input is enabled during timing. Output Mode A-1: Signal ON-Delay 2 (Timer resets when power comes ON.)

Timing starts when the reset input goes ON and is reset when the start signal goes OFF. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF. The control output is controlled using a sustained or one-shot time period.

Power

Start signal Gate*

Basic Operation

Reset

Power Control output

Start Signal Input

Set value UP Timing diagram

0

Timing

Output

Set value DOWN 0

*Output is instantaneous when setting is 0. Output Mode A-2: Power ON Delay 1 (Timer resets when power comes ON)

Power

Timing starts when the reset input goes OFF. The start signal disables the timing function (i.e., same function as the gate input). The control output is controlled using a sustained or one-shot time period.

Start signal Gate *

Basic Operation

Reset

Power

Control output

Timing Set value Timing diagram

UP

Output

0

*Output is instantaneous when setting is 0.

Set value DOWN 0

Output Mode A-3 Power ON Delay 2 (Timer does not reset when power comes ON) Power

Timing starts when the reset input goes OFF. The start signal disables the timing function (i.e., same function as the gate input). The control output is controlled using a sustained or one-shot time period.

Start signal Gate * Reset

Basic Operation Power

Control output

Timing

Set value Timing diagram

UP

Sustained Output *Output is instantaneous when setting is 0.

0

Set value DOWN 0

Gate not included on any mode of this relay.

68

Rockwell Automation Publication 700-TD552A-EN-P

Page 69

Relays and Timer Specifications

700-HX Plug-in Timing Relay

Output Mode B: Repeat Cycle (Timer resets when power comes ON.)

Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.

Sustained Output

Basic Operation

Power

Start signal

Power Gate*

** Start Signal Input

Reset

Timing

Control output

Timing diagram

UP

Timing

Timing

Timing

Output

Set value 0

* Normal output operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled diring timing.

Set value DOWN 0

Timing starts when the start signal goes ON. The control output is turned ON when time is up. While the start signal is ON, the timer starts when the power cones ON or when the reset input goes OFF.

One-Shot Output Power

Basic Operation

Start Signal

Power ** Start Signal Input

Gate* Reset

Timing

Control Output

Timing

Timing

Timing

Output

* Normal output operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during timing.

Set Value 0 Timing UP Set Value Diagram 0 DOWN

Output Mode B-1: Repeat Cycle 2 (Timer does not reset when power comes ON) Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at the start). While the start signal is ON, the timer starts when the power comes ON or when the rest input goes OFF.

Sustained Output

Basic Operation

Power

Power ** Start Signal Input

Start signal Gate*

Timing

Reset

Set value UP

Timing

Output

Control output

Timing diagram

Sustained

* Normal output operation will not be possible if the set time is too short Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during.

0

Set value DOWN 0

One-Shot Output

Timing starts when the start signal goes ON. The control output comes ON when time is up. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.

Basic Operation Power

Power Start signal Gate*

** Start Signal Input

Timing

Timing

Reset

Output Control output Set value Timing diagram

UP

0

Set value DOWN 0

Sustaining

* Normal outout operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during timing.

Gate not included on any mode of this relay.

Rockwell Automation Publication 700-TD552A-EN-P

69

Page 70

700-HX Plug-in Timing Relay

Relays and Timer Specifications Output Mode D: Signal OFF-Delay (Timer resets when power comes ON.)

The control output is ON when the start signal is ON (except when the power is OFF or the reset is ON). The timer is reset when the time is up.

Power

Start signal

Basic Operation Gate*

Power ** Start Signal Input

Reset Control output

Timing

Set value Timing diagram

UP

Output

0

* Output functions only during start signal input when setting is 0. ** Start signal input is enabled during timing.

Set value DOWN 0

Output Mode E: Interval (Timer resets when power comes ON.)

Timing starts when the start signal comes ON. The control output is reset when time is up. While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.

Basic Operation

Power

Start signal

Power ** Start Signal Input

Gate* Reset

Timing

Control output Set value Timing diagram

UP

Output

0

Set value DOWN 0

* Output is disabled when the setting is 0. ** Start signal input is enabled during timing. Output Mode F: Cumulative (Timer does not reset when power comes ON) Start signal enables timing (timing is stopped when the start signal is OFF or when the power is OFF). A sustained control output is used.

Basic Operation Power Start Signal Input Timing

Output

Timing Sustained

*Output is instantaneous when setting is 0.

Gate not included on any mode of this relay.

70