For the Allen-Bradley 700-HN122
Page 61
700-HR Timing Relays
Relays and Timer Specifications Signal Specifications Circuit Impedance
Circuit impedance can be used to calculate the maximum wiring distance from the signal switch to the timing relay, for example. Permissible signal-ON impedance: 1 kΩ max. Permissible signal-OFF impedance: 100 kΩ min.
Power-OFF Reset
Min. power-off time: 0.1 s, Reset Voltage: 10% max. of rated voltage
Signal Duration
Min. pulse width: 0.05 s
Signal Options
700-HR52
700-HRT6
700-HRV5
700-HRQR
Start
X
X
X
NA
Reset
X
X
NA
X
Gate
X
X
NA
NA
Nomenclature Timing Charts Mode A, ON-Delay a. Needs continuous input power applied. b. Timing is initiated by the leading edge of the start signal. c. Contacts change state after timing is complete. d. Additional start signals during timing don't reset timing or contacts. e. When the input power is removed contacts return to shelf state.
Basic Operation T
Power
T
Power
Start
Start
Output (N.C.)
Output
Output (N.O.) Power LED
Mode B, Repeat Cycle, Off Start a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. Additional start signals during timing do not reset timing or contacts. c. For the first time period the contacts remain in their shelf state. When that time period is complete contacts change state for the same time period (time on = time off). d. This cycle repeats itself until input power is removed or reset signal is applied. When the input power is removed or reset signal is applied contacts return to the shelf state.
Basic Operation T
T
T
Power Start Output (N.C.) Output (N.O.) Power LED
T
T
T
Power Start Output a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. Additional start signals during timing do not reset timing or contacts. c. For the first time period the contacts change state. When that time period is complete contacts return to the shelf state for the same time period (time on = time off). d. This cycle repeats itself until input power is removed or reset signal is applied. When the input power is removed or reset signal is applied contacts return to the shelf state.
Basic Operation Power Start Output (N.C.)
T
T
T
Power Start
T
T
T
Output
Output (N.O.) Power LED
Rockwell Automation Publication 700-TD552A-EN-P
61
Page 62
700-HR Timing Relays
Relay and Timer Specifications
Mode C, Watchdog monitor (Trigger = Signal On/Off) a. Need continuous input power applied. b. Contacts change state immediately when start signal is applied or when start signal is removed (only if timing cycle was complete). c. Timing is initiated at the leading edge of the start signal. After the first timing cycle is complete, timing is initiated by the trailing edge of the start signal. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to the shelf state.
Power
T
T t t<T
T
Basic Operation
Start Output (N.C.)
T
Power Start
Output (N.O.) Power LED Mode D, Off-Delay (Trigger=Signal Off)
T
Output a. Need continuous input power applied. b. Contacts change state immediately when start signal is applied. c. Timing is initiated by the trailing edge of the start signal. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to the shelf state.
Basic Operation t
T
Power t<T
Start
Power Start
Output (N.C.)
Output
T
Output (N.O.) Power LED
Mode E, One-Shot (Trigger=Signal On) 700-HR52, -HRV, and -HRT6 a. Need continuous input power applied. b. Timing is initiated by the leading edge of the start signal. c. Contacts change state immediately when start signal is applied. d. At the end of the time period contacts return to the shelf state. e. Relay timing is reset when additional start signals are applied while the relay is timing. Contacts remain in energized state. f. When the input power is removed contacts return to shelf state.
Basic Operation Power
T t
T t<T Power Start
Start Output (N.C.) Output (N.O.) Power LED
T
Output
Mode E, One-Shot (Trigger = Power On) 700-HRS, -HRP, and -HRT4 a. Need continuous input power applied. b. Timing is initiated when the input power is applied. c. At the end of the time period contacts return to the shelf state. d. Relay timing is reset when input power is removed.
Basic Operation Power Timed Output (N.C.) Timed Output (N.O.) Power LED 62
T t<T Power Output
Rockwell Automation Publication 700-TD552A-EN-P
T
Page 63
Relays and Timer Specifications
700-HNC Plug-in Timing Relay
Mode J, Delayed One-Shot (Trigger=Power On) a. Need continuous input power applied. b. No start signal applied. c. Timing is initiated when input power is applied. c. Contacts change state after the timing for a fixed time of 1s +/-0.5s d. At the end of the 1 sec period the contacts return to the shelf state. e. When the input power is removed contacts return to the shelf state.
Basic Operation T
Power
T
1s ±0.5s
Output (N.C.)
Power 1s ±0.5s
Output (N.O.)
Output (N.O.)
Power LED
Power LED Mode Star-Delta a. Need continuous input power applied. b. No start signal required. Timing is initiated when input power is applied. c. Star ouput contact changes state when input power is applied.
d. After timing is complete star output contact returns to the shelf state then both the star & delta contacts remain in shelf states until transfer time setting is complete. e. Delta output contact changes state after transfer time is complete. f. Instantaneous contact changes state when input power is applied. g. All contacts return to the shelf state when input power is removed.
Power
Basic Operation t2 t1
Output (N.C.)
Power
Output (N.O.)
Instantaneous Output
Output 8-5,
LED
Output 8-5,
LED
Output 8-6,
LED
Output 8-6,
LED t1 t2
Mode True Off-Delay (Trigger=Power Off) a. Continuous input power is NOT required. b. No start signal applied. c. Contacts change state immediately when input power is applied. d. Timing starts when input power is removed. e. At the end of the time period contacts return to the shelf state. f. Relay timing is reset when input power is reapplied while the relay is timing. Contacts remain in energized state. t<T T t
T
Basic Operation
Power
T
Output (N.C.)
Power
Output (N.O.)
Output
Relay On LED
Relay On LED
Rockwell Automation Publication 700-TD552A-EN-P
63
Page 64
700-HR Timing Relay
Relays and Timer Specifications
Approximate Dimensions Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes. 81.5 (3-7/32) 52.3 (2-1/16)
15.0 (19/32)
Mode
3 2
4 hrs
6
Range
78 (3.07)
63.7 (2.51)
0.7 (0.03)
48.0 (1-57/64)
5 0
6 (.24)
Up
1
48.0 (1-57/64)
15 (.59)
Power
A
39 (1.54)
Unit
44.8 (1.76)
48.0 (1-57/64)
6.0 (1/4)
Cat. No. 700-HR, -HRM, -HRC, -HRF, -HRS, -HRV, -HRP, -HRY, -HRQ Timing Relays
Cat. No. 700-HR, -HRM, -HRC, -HRF, -HRS, HRV, HRP
Cat. No. 700-HRY, -HRQ Timing Relays
Timing Relays
Panel
35.0 (1-3/8)
45.0 (1-25/32)
57.0 (2-11/32)
32.0 (1-1/4)
45.0 (1-49/64)
24.0 (31/32)
45.0 (1-25/32) Cat. No. 700-HN129, 11-pin Cat. No. 700-HN108, 8-pin socket
Cat. No. 700-HR… Panel Cutout
30 (1-3/16) 22
Cat. No. 700-HN130 Retainer
24.6 (31/32) 20.8 (53/64)
40.1 (1-37/64)
26 (1-1/32)
12
24
14 5
2
1
8
Ø 24.9 (63/64)
7
4
6
3
65 (2-35/64) 7
Ø 4.2 (5/32)
2 8
1
21
11
A2
54.9 (2-5/32)
A1 3
38 (1-1/2)
#4_40 M3
4
5
51.1 (2-1/64)
6
33.0 (1-19/64)
14.7 (37/64)
Cat. No. 700-HN100
Cat. No. 700-HN125
Wire Size: 2x2.5 mm Single Wire, Up to #12 AWG Double Wire, 2x2.5 mm (#2-14 AWG…#2-20 AWG) (Either Solid or Stranded) Strip length: 9 mm (3/8 in), Torque: 0.8 N•m (7 lb•in)
Wire Size: 2x2.5 mm Single Wire - Up to #12 AWG Double Wire, 2x2.5 mm (#2-14…#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in), Torque: 0.8 N•m (7 lb•in)
Panel Mounting 30 (1-3/16) 24
21 22
1 12
32 6
7
9
3
65 (2-35/64) 10
11
1
54.9 (2-5/32)
9
4
8 5
7 6
Ø 4.2 (5/32)
51.1 (2-1/64)
2
14
#4_40 M3
A2 31 11 A1
38 (1-1/2)
64
26.9 (1.06)
10
3 4
24.6 (31/32) 20.8 (53/64)
11
2
5
8
34
59.2 (2-1/3) 7.9 (0.31)
26 (1-1/32)
52.3 (2.06)
Cat. No. 700-HN100
Cat. No. 700-HN126
Wire Size: 2x2.5 mm Single Wire, Up to #12 AWG Double Wire, 2x2.5 mm (#2-14 AWG…#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.), Torque: 0.8 N•m (7 lb•in.)
Wire Size: 2x2.5 mm Single Wire - Up to #12 AWG Double Wire, 2x2.5 mm (#2-14…#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in), Torque: 0.8 N•m (7 lb•in)
Rockwell Automation Publication 700-TD552A-EN-P
Page 65
Relays and Timer Specifications
700-HX Plug-in Timing Relay
General Timer Functions
Operation Key
Display Section 1. Key Protect Indicator (orange) 2. Control Output Indicator (orange) 3. Reset Indicator (orange) 4. Present Value Display (Main display) (Character height: 12 mm, red *) * Characters on models with screw terminals can be switched between red, green, and orange.
1 2 3 8
4
8. Mode Key
5
9. Reset Key
6
(Changes modes and setting items) (Resets present value and output)
7
10. Up Keys 1 to 4
10
11. Down Keys 1 to 4
11
9
Switches
5. Time Unit Indicators (Color is same as present value display.) (If the time range is 0 min, 0 h, 0.0 h, or 0 h 0 min, these indicators flash to indicate timing operation.)
Front View
12. Key-protect Switch (Default setting)
12
OFF (Disabled)
ON (Enabled)
6. Set Value Display (Sub-display) (Character height: 6 mm, green)
7. Set Value 1, 2 Indicator (green) Character Size for Present Value Display
12mm
Character Size for Set Value Display
6mm
Rockwell Automation Publication 700-TD552A-EN-P
65
Page 66
700-HX Plug-in Timing Relay
Relays and Timer Specifications
Specifications Electrical Ratings Pilot Duty Rating
NEMA B300
Rated supply voltage
100 to 240V AC, 24V AC/12 to 24V DC (50/60Hz) (permissible ripple: 20%(p-p) max.)
Operating voltage range Power consumption Inrush Current
Make Break
85…110% of rated supply voltage 100…240V AC
4.3VA
24V AC/12…24V DC
3.4VA/1.7 W
100…240V AC
3A
24V AC/12…24V DC
5A
120V AC
30 A
240V AC
15 A
120V AC
3A
240V AC
1.5 A
Hp at 120V AC
1/4 Hp
Hp at 240V AC
1/3 Hp Mechanical
Mounting Method
Flush mounting, surface mounting, DIN mounting
Display
Seven-segment, negative transmissive LCD; Present value (red, 12 mm high characters); Set value (green, 6 mm high characters)
Digits
Four digits Time ranges
Timer
Inputs
0.000…9.999 s, 0.00…99.99 s, 0.0…999.9 s, 0…9999 s, 0 min 00 s…99 min 59 s, 0.0…999.9 min, 0 hr 00 min…99 hr 59 min, 0.0 hr…999.9 hr, 0 hr…9999 hr
Timer modes
Elapsed time (Up), remaining time (Down), selectable
Output modes
A, A-1, A-2, A-3, B, B-1, D, E, F, Z, S, tOFF, tON, tOFF-1, or tON-1
Input signals
Start, reset
Input method
No-voltage input via:NPN transistor or switching of contact
Start, reset, gate
Minimum input signal width: 1 or 20 ms (selectable)
Power reset
Minimum power-opening time: 0.5 s (Except for A-3, B-1, and F mode) SPDT contact output: 5 A at 250V AC, resistive load (cosine=1) Minimum applied load: 10 mA at 5 V DC (failure level: P, reference value)
Control output External Power Supply
No
Key Protect
Yes
Memory Backup
EEP-ROM (overwritten 100 000 times min), which can store data for 10 years min.
Accuracy of Operating Time and Setting
Power-ON start: +-0.01% +-50 ms max. * to be rated against set value Signal start: +- 0.005% +-30 ms max. * to be rated against set value Signal start at transistor output model: +- 0.005% +-3 ms max.‡ If the set value is within the sensor waiting time (250 ms max.)
The values are based on the set value. ‡ The value is applied for a minimum pulse width of 1 ms.
66
Rockwell Automation Publication 700-TD552A-EN-P
Page 67
Relays and Timer Specifications
700-HX Plug-in Timing Relay
Insulation Resistance
100 mΩ min. (at 500V DC)
Dielectric Strength
2000V AC, 50/60Hz for 1 min between current-carrying terminals and non-currentcarrying metal parts (1000V AC for 24V AC/12 to 24V DC type), 1000 VAC, 50/60 Hz for 1 min between non-continuous contacts
Noise Immunity
'+-1.5 kV (between power terminals) for 100 to 240 VAC, +-480V for 24VAC/12 to 24VDC, and +-600V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static Immunity
±8 kV (malfunction), ±15 kV (destruction)
Vibration Resistance
Malfunction
10…55 Hz with 0.35 mm single amplitude each in three directions for 10 min
Shock Resistance
Malfunction
98 m/s2 (approx. 10 G) each in three directions
Mechanical
10 million operations min. (under no load at 18 000 operation/hr)
Electrical
100 000 operations min. (5 A at 250V AC, resistive load at 1800 operation/hr)
Life Expectancy
EMC
(EMI)
EN61812-1
Emission Enclosure:
EN55011 Group1 class A
Emission AC mains:
EN55011 Group1 class A
(EMS)
EN61812-1
Immunity ESD:
EN61000-4-2: 4 kV contact discharge (level2) 8 kV air discharge (level3)
Immunity RF-interference:
EN61000-4-3: 10 V/m
Enclosure Ratings
Panel surface:IP66 and NEMA Type 4X (indoors)‡
Weight
Approx. 100 g
Certifications
CE Certified; cURus (File No. E14843, Guide NRNTZ/NRNT8), C-Tick Marked
Standards
EN61010-1, EN 61326, VDE0106/P 100, CSA C22.2 No. 14, UL 508
700-HX User Manual, pub. number 700-UM002_-EN-D, available at Literature Library. ‡ An attached waterproof packing is necessary to ensure IP66 waterproofing between the 700-HX and installation pan.
Rockwell Automation Publication 700-TD552A-EN-P
67
Page 68
700-HX Plug-in Timing Relay
Relays and Timer Specifications
Timing Charts One-Shot Sustained Output
One-shot outputs can be set to 0.1s, 0.5 s, 1 s, 5 s, 10 s, or 20 s.
Output Mode A Mode: Signal ON-Delay (Timer resets when power comes ON.)
Timing starts when the start signal goes ON. While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF. The control output is controlled using a sustained or one-shot time period.
Power
Start signal
Basic Operation
Gate*
Power
Reset t t t
Control output
** Start Signal Input Timing
Set value Timing diagram
UP
Output
0
Set value DOWN 0
*Output is instantaneous when setting is 0. ** Start signal input is enabled during timing. Output Mode A-1: Signal ON-Delay 2 (Timer resets when power comes ON.)
Timing starts when the reset input goes ON and is reset when the start signal goes OFF. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF. The control output is controlled using a sustained or one-shot time period.
Power
Start signal Gate*
Basic Operation
Reset
Power Control output
Start Signal Input
Set value UP Timing diagram
0
Timing
Output
Set value DOWN 0
*Output is instantaneous when setting is 0. Output Mode A-2: Power ON Delay 1 (Timer resets when power comes ON)
Power
Timing starts when the reset input goes OFF. The start signal disables the timing function (i.e., same function as the gate input). The control output is controlled using a sustained or one-shot time period.
Start signal Gate *
Basic Operation
Reset
Power
Control output
Timing Set value Timing diagram
UP
Output
0
*Output is instantaneous when setting is 0.
Set value DOWN 0
Output Mode A-3 Power ON Delay 2 (Timer does not reset when power comes ON) Power
Timing starts when the reset input goes OFF. The start signal disables the timing function (i.e., same function as the gate input). The control output is controlled using a sustained or one-shot time period.
Start signal Gate * Reset
Basic Operation Power
Control output
Timing
Set value Timing diagram
UP
Sustained Output *Output is instantaneous when setting is 0.
0
Set value DOWN 0
Gate not included on any mode of this relay.
68
Rockwell Automation Publication 700-TD552A-EN-P
Page 69
Relays and Timer Specifications
700-HX Plug-in Timing Relay
Output Mode B: Repeat Cycle (Timer resets when power comes ON.)
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Sustained Output
Basic Operation
Power
Start signal
Power Gate*
** Start Signal Input
Reset
Timing
Control output
Timing diagram
UP
Timing
Timing
Timing
Output
Set value 0
* Normal output operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled diring timing.
Set value DOWN 0
Timing starts when the start signal goes ON. The control output is turned ON when time is up. While the start signal is ON, the timer starts when the power cones ON or when the reset input goes OFF.
One-Shot Output Power
Basic Operation
Start Signal
Power ** Start Signal Input
Gate* Reset
Timing
Control Output
Timing
Timing
Timing
Output
* Normal output operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during timing.
Set Value 0 Timing UP Set Value Diagram 0 DOWN
Output Mode B-1: Repeat Cycle 2 (Timer does not reset when power comes ON) Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at the start). While the start signal is ON, the timer starts when the power comes ON or when the rest input goes OFF.
Sustained Output
Basic Operation
Power
Power ** Start Signal Input
Start signal Gate*
Timing
Reset
Set value UP
Timing
Output
Control output
Timing diagram
Sustained
* Normal output operation will not be possible if the set time is too short Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during.
0
Set value DOWN 0
One-Shot Output
Timing starts when the start signal goes ON. The control output comes ON when time is up. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Basic Operation Power
Power Start signal Gate*
** Start Signal Input
Timing
Timing
Reset
Output Control output Set value Timing diagram
UP
0
Set value DOWN 0
Sustaining
* Normal outout operation will not be possible if the set time is too short. Set the value to at least 100 ms (contact output type). ** Start signal input is disabled during timing.
Gate not included on any mode of this relay.
Rockwell Automation Publication 700-TD552A-EN-P
69
Page 70
700-HX Plug-in Timing Relay
Relays and Timer Specifications Output Mode D: Signal OFF-Delay (Timer resets when power comes ON.)
The control output is ON when the start signal is ON (except when the power is OFF or the reset is ON). The timer is reset when the time is up.
Power
Start signal
Basic Operation Gate*
Power ** Start Signal Input
Reset Control output
Timing
Set value Timing diagram
UP
Output
0
* Output functions only during start signal input when setting is 0. ** Start signal input is enabled during timing.
Set value DOWN 0
Output Mode E: Interval (Timer resets when power comes ON.)
Timing starts when the start signal comes ON. The control output is reset when time is up. While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.
Basic Operation
Power
Start signal
Power ** Start Signal Input
Gate* Reset
Timing
Control output Set value Timing diagram
UP
Output
0
Set value DOWN 0
* Output is disabled when the setting is 0. ** Start signal input is enabled during timing. Output Mode F: Cumulative (Timer does not reset when power comes ON) Start signal enables timing (timing is stopped when the start signal is OFF or when the power is OFF). A sustained control output is used.
Basic Operation Power Start Signal Input Timing
Output
Timing Sustained
*Output is instantaneous when setting is 0.
Gate not included on any mode of this relay.
70
Rockwell Automation Publication 700-TD552A-EN-P