Page 121
Relays and Timer Specifications
700-SH Solid State Relays
Surge current resistivity for 700-SH75.... 1200A
Surge current resistivity for 700SH100.... 2000A 1800A
1000A
1600A
Inrush current (Apk)
1400A
600A
400A
1200A 1000A 800A 600A
200A
400A 200A
0A 10ms
100ms
1000ms
10000m s
0A 10ms
Energizing time (ms)
100ms
1000ms
10000m s
Energizing time (ms)
Load current vs. ambient temperature characteristics for 700-SH10….
Load current vs. ambient temperature characteristics for 700-SH25….
12
30 700-SN50VHC
10
700-SN50HC 700-SN10
700-SN50(V)HC
25
700-SN25
700-SN10
6
4
No heatsink
15
No heatsink
5
0 -10
0
10
20
700-SN50
10
2
-20
700-SN25
20
700-SN50
Load Current (A)
Load Current (A)
8
30
40
50
60
70
0
80
-20
Ambient temperature (ºC)
-10
0
10
20
30
40
Load current vs. ambient temperature characteristics for 700-SH75….
60
70
80
Load current vs. ambient temperature characteristics for 700-SH5….. 6 700-SN50(V) HC
700-SN50VHC
70
5
700-SN50HC
60
700-SN10
700-SN25
50
60
700-SN50
4
50 700SN10
40
700-SN25
Load Current (A)
Load Current (A)
50
Ambient temperature (ºC)
80
700-SN50
30
No heatsink
3
2 20 1
10
No heatsink
0 -20
-10
0
10
20
30
40
50
60
70
0
80
-20
-10
0
10
20
Ambient temperature (ºC)
30
40
70
80
Ambient temperature (ºC)
Load current vs. ambient temperature characteristics for 700-SH50…. 60 Load current vs. ambient temperature characteristics for 700-SH100…. 120
50 700-SN50VHC
100 700-SN50HC
40
700-SN50VHC
Load Current (A)
700-SN50
80 Load Current (A)
Inrush current (Apk)
800A
60
700-SN10
700-SN10
700-SN25
700-SN50
700-SN50HC
30
700-SN25
20
40
20
10 No heatsink
No heatsink
0 -20
-10
0
10
20
30
40
Ambient temperature (ºC)
50
60
70
80
0 -20
-10
0
10
20
30
40
50
60
70
80
Ambient temperature (ºC)
Rockwell Automation Publication 700-TD552A-EN-P
121
Page 122
700-SH Solid State Relays
Relays and Timer Specifications
Mounting All units are in mm's unless otherwise indicated. To convert to inches multiply by 0.0394. Dimensions are not intended for manufacturing purposes.
24.5
30.0
45.5
Mounting Holes (Bottom View) 5.3
2 x M5 Screws
Load Two Ø 4.4 or M4 Holes
47.5
47.5 58.2
Terminal Arrangement/ Internal Connections (Top View)
Load L1
A2
2 x M3 Screws
Input
Load Power Supply T1
A1
13.0 25 45.5
Cat. No. 700-SH5F…
44.8
28.8
Two Ø 4.4 or M4 Holes
47.5
12.3 2 X M5 Screws
8.6
47.5
58.2
Operating Indicator
APPLY HEATSINK COMPOUND
2 X M3 Screws
5.2 5.25 25 45.5 Cat. No. 700-SH10, -SH25, -SH50, -SH75, -SH100 The proper mounting orientation of the heat sink is so the heat fins run perpendicular to the floor (vertical) to maximize ventilation flow. If the fins do not run perpendicular to the floor, a 30% current derating is required. § When attaching a heat sink to Bulletin 700-SH, apply a thin layer of heat conductive grease (approximately 0.002 in. thick) on the heat sink to maximize heat transfer between the SSR and the heat sink. Recommended types: Silicon based, Dow Corning 340, Toshiba YG6240; Non-silicon based, AOS company type 53300 (Cat. No. 46801-010-01). ♣ Tighten the SSR panel/heat sink mounting screws to a torque of 0.78…0.98 N•m (6.9…8.7 lb•in). Δ Tighten the SSR terminal wiring screws as follows M4: 0.98…1.37 N•m (8.67…12.12 lb•in), M5: 1.57…2.35 N•m (13.89…20.8 lb•in).
122
Rockwell Automation Publication 700-TD552A-EN-P
Page 123
Relays and Timer Specifications
700-SH Solid State Relays 700-SN10
700-SN25
700-SN50
700-SN50HC
700-SN50VHC
♦ Tighten the heat sink mounting screws (M4) to a torque of 0.98…1.37 N•m (8.67…12.12 lb•in). ♠ Heat sink weight: Cat. Nos. 700-S10 = 200 g, 700-S20 = 400 g, 700-S30 = 560 g.
Rockwell Automation Publication 700-TD552A-EN-P
123
Page 124
700-SH Solid State Relays
Relays and Timer Specifications
12
47
27
45
67
27,5
Cat. No. 700-SHCOV
Cat. No.700-SHTRMA 28,5
Load Connection For an AC load, use a power supply rated at 50 or 60 Hz. The maximum operating frequency is 10 Hz. The Bulletin 700-SH has a built-in varistor for surge/inrush protection of AC loads. If additional suppression is required, connect an external varistor across the load device terminals. Select a varistor which meets the load voltage condition outlined in the table below. Load Voltage [V AC]
Varistor Voltage [V]
100…120
240…270
200…240
440…470
380…480
820…1000
Varistor Surge Resistance 1000 A min.
Zero Cross Function A SSR with a zero cross function operates when an AC load voltage reaches the zero point or its vicinity. This reduces clicking noises when the load is switched and minimizes the influence of an inductive load, (e.g., lamp, heater, or motor) on the power supply because the inrush current of the load is reduced. This can also minimize the scale of the inrush current protection circuit.
Output (load voltage)
Input
ON OFF
At a low applied voltage (e.g., 24V AC) the load current is not fully supplied. When the unit is switched ON, the voltage required to power the unit deprives the output signal of the necessary voltage level and thus creates loss time. The lower the load voltage is, the greater the loss time is. This condition, however, will not create any serious problems.
Loss time
For a DC inductive load, a diode should be connected parallel to the load to absorb the counter electromotive force (OFF) of the load.
Load Input
SSR
Load power supply
Note: For additional details when using Solid-State Relays, refer to pub. 700-AT001*, Solid-State Relay Application Guide.
124
Rockwell Automation Publication 700-TD552A-EN-P
Page 125
Relays and Timer Specifications
700-SK Solid State Relays
Input Sensor Module Input Sensor Ratings Cat. No.
Rated Input Voltage
Max. Operating Input Voltage Range
Input Current
Pick-up Voltage
Drop-out Voltage
700-SKICZ24
12…24V DC
6.6…32V DC
8 mA max.
6.6V DC max.
3.6V DC min.
700-SKICA18
100…240V AC
60…264V AC
15 mA max.
60V AC max.
20V AC min.
Output Logic Ratings Cat. No.
Logic Level Supply Voltage
Logic Level Supply Current Draw
4…32V DC
0.1…100 mA
Cat. No. 700-SKICA18
Cat. No. 700-SKICZ24
700-SKICZ24 700-SKICA18
Characteristics Description Pick-up time
20 ms max.
0.1 ms max.
Drop-out time
20 ms max.
0.1 ms max.
Response frequency
10 Hz
1 kHz
Output ON voltage drop
1.6V max. 5 μA max.
Leakage current Output VDRM, VCEO (V)
80 (ref. value)
80 (ref. value)
Output di/dt (A/uS), - Output dv/dt (V/uS), - 2
Output I t (A S), - Output Tj (°C) Max.
150
2
150
Insulation Resistance
100 MΩ min. between input and output
Dielectric Strength
4000V AC, 50/60 Hz for 1 min between input and output
Vibration Resistance (Max.)
10…55 Hz, 1.5 mm double amplitude (10 G)
Shock Resistance (Max.)
1000 m/s2 (100 G)
Ambient Temperature
Operating
–30…+80 °C (–22…+176 °F) with no icing or condensation
Storage
–30…+100 °C (–22…+212 °F) with no icing or condensation
Standards Compliance
UL 508, CSA C22.2 No. 14, EN/IEC 60950
Certifications cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified
Ambient humidity
Operating
45…85% (no condensation)
Weight
Approx. 18 g
Output SSR Module Control/Input Ratings Cat. No.
Rated Control Voltage
Max. Operating Control Voltage Range
Max. Reverse Control Voltage
-32V DC
15 mA max. at 25 °C (77 °F)
700-SKOZ2Z25 700-SKON2Z25
5…24V DC
4…32V DC
700-SKOC2Z25
Pick-up Voltage
Drop-out Voltage
4V DC max.
1V DC min.
8 mA max.
700-SKOC1Z25
Load/Output Ratings Cat. No. 700-SKOZ2Z25 700-SKON2Z25
Rated Load Voltage
Maximum Load Voltage Range
100…240V AC
Continuous Load Current (Resistive) [A] Min.
Max.§
Max. Inrush Current‡
75…264V AC
0.05
2
30 A (@50/60 Hz, 1 cycle)
700-SKOC2Z25
5…48V DC
4…60V DC
0.1
2
8 A (10 ms)
700-SKOC1Z25
48…200V DC
40…200V DC
0.1
1.5
8 A (10 ms)
With a constant current input system. SSR impedance varies with a change in input voltage. ‡ If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the “Inrush Current Resistivity” graphs on page 9-193 for more details. § Refer to "Load Current vs. Ambient Temperature Characteristics" graphs on page 9-193 for additional details.
Rockwell Automation Publication 700-TD552A-EN-P
125
Page 126
700-SK Solid State Relays
Relays and Timer Specifications
Output Module, Continued Characteristics Description
Cat. No. 700-SKOZ2Z25
Load Switching Method/Device
Cat. No. 700-SKON2Z25
Cat. No. 700-SKOC2Z25
Cat. No. 700-SKOC1Z25
Triac
Transistor
Pick-up Time
1/2 cycle of load power source cycle + 1 ms max.
1 ms max.
Drop-out Time
1/2 of load power source cycle + 1 ms max.
2 ms max.
20 Hz
100 kHz
Response Frequency Output ON Voltage Drop
1.6V max.
Leakage Current
2.5V max.
1.5 mA max.
Output VDRM, VCEO (V)
1 mA max.
600 (ref.value)
600 (ref.value)
80 (ref.value)
Output di/dt (A/uS)
30
30, 400 (ref.value), Output dv/dt (V/uS)
300
300, - Output I2t (A2S)
10.4
10.4, - Output Tj (°C) Max.
125
125
150
150
Insulation Resistance
100 MΩ min. between input and output
Dielectric Strength
4000V AC, 50/60 Hz for 1 min between input and output
Vibration Resistance (Max.)
10…55 Hz, 1.5 mm double amplitude (10 G) 1000 m/s2 (100 G)
Shock Resistance (Max.) Ambient Temperature
Operating
–30…+80 °C (–22…+176 °F) with no icing or condensation
Storage
–30…+100 °C (–22…+212 °F) with no icing or condensation
Standards Compliance
UL 508, CSA C22.2 No. 14, EN/IEC 60950
Certifications cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, TÜV Certified
Ambient Humidity
Operating
45…85% (no condensation)
Weight
Approx. 18 g
60 Hz cycle time = 16.6 ms, 50 Hz cycle time = 20 ms.
Load Current vs. Ambient Temperature Characteristics
10
9
9
8
8
3 2
100
5 4 3
2
Energizing Time (ms)
10
2000
1000
0
300 500
1
0
100
1
2000
4
6
1000
5
7
300 500
6
700-SKOZ/SKOC1
100
Inrush Current (A)
7
10
Inrush Current (A) Energizing Time (ms)
5000
1000
500
100
200
30 50
10
Inrush Current (A)
30
700-SKOC2
30 50
10
30 50
Inrush Current Resistivity‡ 700-SKOZ/SKON
10
80
Ambient Temperature [° C]
Ambient Temperature [° C]
20
60
-20
0.5
100
80
60
40
20
0
0.5
1
40
1
1.5
20
1.5
2
0
Maximum Load Current (A)
2
-20
Maximum Load Current (A)
For 2 A Versions
Energizing Time (ms)
‡ Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period of time. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
126
Rockwell Automation Publication 700-TD552A-EN-P
Page 127
Relays and Timer Specifications
700-SK Solid State Relays
All units are in millimeters unless otherwise indicated. To convert to inches multiply by 0.0394. Dimensions are not to be used for manufacturing purposes. Note: The input module ( Bul. 700-SKI) and output module (Bul. 700-SKO) are compatible with the Cat. No. 700-HN121 socket. 1 5.2
Terminal Arrangement/ Internal Connections (Bottom View)
3 0.5 29 max.
17.4
4.75 1
13 max.
28 max.
5
(+)
4 9.6
(–)
4.7
Input
0.5 4.75
4
4
Load
5
7.5
3
10
1
5
(–)
(+)
2 20
Application Considerations of Bulletin 700-SK Connection For DC load switching, Bulletin 700-SK SSR will operate properly if the load is connected to either the positive or negative SSR load terminal. The load can be connected to either positive or negative output terminals of the SSR.
Protective Element (to extend SSR life) Since the SSR does not incorporate a surge absorption component, be sure to connect a surge absorption component when using the SSR to control an inductive load. For additional details applying solid-state relays, refer to pub. 700-AT001A*, Solid-State Relay Application Guide.
Rockwell Automation Publication 700-TD552A-EN-P
127
Page 128
Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Allen-Bradley, Rockwell Software, Rockwell Automation, and LISTEN. THINK. SOLVE are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Publication 700-TD552A-EN-P - September 2014 Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.