Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 1 of 25

Relay and Timer Specifications, Bulletin Number 700, pages 1 to 10

Pages 1 to 10 of 250

The original document is the PDF (23 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX

Page 1

Technical Data

Relay and Timer Specifications Bulletin Number 700 Topic Topic

Page

Page

NEMA Industrial Relays

149

Summary of Changes

2

700-P Industrial Relays

151

General Information

3

700S-P and 700S-PK, Heavy-Duty Safety Control Relays

167

General Purpose Relays

9

700-N Industrial Relays

172

700-HA General-purpose Relay

12

700-R Sealed Switch Relays

176

700-HB Square Base Relay

22

700-RTC, Solid-State Timing Relay

181

700-HD Flange Mount Square Base Relay

28

IEC Control Relays

187

700-HF Square Base Relay

32

700-CF Control Relay

188

700-HC Miniature Ice Cube Relay

39

700S-CF Control Relays

207

700-HK Slim Line Relay

44

700-K Miniature Control Relays

212

700-HL Terminal Block Relay

50

Solid-state Relays

219

700-HLF Terminal Block Timing Relay

60

Solid-state Relay Glossary

221

700-HP Slim Line Relay

64

700-SC Ice Cube Relays

226

700-HJ Magnetic Latching Relay

71

700-SF Square Base Relays

231

700-HG Power Relay

75

700-SH Hockey Puck Relays

235

700-HHF Flange Mount Power Relay

80

700-SK Slim Line Relays

244

700-HTA Alternating Relay

83

General Purpose Electronic Timers and Counters

89

700-FE Economy Timing Relay

92

700-FS High Performance Timing Relay

96

700-HNC Miniature Timing Relay

103

700-HNK Ultra-Slim Timing Relay

109

700-HR Dial Timing Relays

116

700-HT Plug-in Timing Relay

128

700-HV Timing Relay

133

700-HX Multi-Function Digital Timing Relay

138

Page 2

Relay and Timer Specifications

Summary of Changes This publication contains new and updated information as indicated in the following table.

2

Topic

Page

Added Product Selection and Accessories throughout

Removed 700-RM Relays, 700-CF, 700s-CF - removed Standard and Standard diode DC coils/coil voltage codes

189, 208

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 3

General Information

General Information Contact Data Tables

IEC Relays

AC and DC Switching Capability Relay Type

Contact Arrangement

Contact Style

Contact Material

NEMA Pilot Duty(1)

700-CF

Up to 8 form X or 8 form Y cross stamped

Ag

A600 P600

Up to 8 form X or 8 form Y cross stamped

700-K

Up to 8 form X or 8 form Y bifurcated

AgCu

A300 Q300

700-P

Up to 12 form X or 8 form Y bifurcated

NiAg

A600 P600

Up to 12 form X or 8 form Y single

700S-CF

700-PK

Ag

AgCdO

A600 P600

1 mA

20 mA

50 mA

100 mA

1A

3A

5A

24V

10 A

20 A

25 A

30 A

35 A

AC DC

AC

24 V

DC

AC

17V

DC

10V

AC DC

2X A600 2X P600

10V

AC DC

(20 A Lighting Load)

NEMA Relays

AC Up to 6 form X or 4 form Y tandem

700-R

Up to 8 form A or form B sealed sw.

W

B300 C600 P300

5V

AC DC

700-RTC

Up to 4 form A or form B sealed sw.

W

B600 P300

5V

AC DC

700S-P

Up to 12 form X or 8 form Y bifurcated

NiAg

A600 P600

700-PH

AgCdO

A600 P600

10V DC

10V

(35 A Lighting Load)

AC

(1) NEMA contact rating chart is on page 19.

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

3

Page 4

General Information

Contact Data Tables

General Purpose Relays

Timing Relays

AC and DC Switching Capability

Relay Type

Contact Arrangement

Contact Style

NEMA Contact Pilot Material Duty

700-FE

1 N.O.

single

AgCdO

D300

10V

700-FS

1, 2 form C single

AgCdO

B300

10V

700-HA

2, 3 form C single

AgNi

B300

10V

700-HAX

2, 3 form C bifurcated

Au/AgNi

B300

700-HB

2, 3 form C single

AgNi

B300

700-HC14

4 form C single

Ag/Au

C300 Q300

700-HC22

2 form C single

AgNi

B300 Q300

10V

AC DC

700-HC24

4 form C single

AgNi

C300 Q300

10V

AC DC (30V Max.)

700-HD

2, 3 form C single

AgCdO

B300

10V

700-HF

2, 3, 4 form C single

AgCdO

B300

10V

700-HG

1 form X, 1 form C, 2 form A, 2 form C single

AgNi

A600

10V

AC DC (28V Max)

700HHF45

1 form X single

AgNi

A600

10V

AC DC (28V Max)

700HHF62

2 form C single

AgNi

B600

10V

700HHF73

3 form C single

AgNi

B300

700-HJ

1, 2 form C single

AgCdO, 700-HK36

1 form C single

AgNi

B300

700-

1 form C single

Au/AgNi

B300

700-HK32

2 form C single

AgNi

B300

10 mA

1 mA

50 mA

100 mA

1A

3A

4

2 form C single

Au/AgNi

10 A

20 A

25 A

30 A

35 A

AC DC (24V Max.) AC DC (24V Max.) AC DC (24V Max) AC DC (24V Max)

6V

AC DC (24VMax.)

10V AC DC (30V Max.)

10V

AC DC (24V Max) AC DC (30V Max)

AC DC (28V Max) AC DC (28V Max)

10V

10V

AC DC (24V Max.)

10V

AC DC (30V Max)

5V

700-

5A

B300

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

AC DC (30V Max)

Page 5

General Information

Contact Data Tables

General Purpose Relays (continued)

AC and DC Switching Capability Relay Type

Contact Arrangement

Contact Style

Contact Material

NEMA Pilot Duty

700-HLS

Solid-State 1 N.O., - - 700-HLT

1 Form C single

AgSnO

B300 R300

700-HLT_ _X

1 Form C single

AgSnO

B300 R300

700-HP

2 Form C single

AgNi

700-HPX

2 Form C single

700-HS

2 Form C

700-HT

2 form C

1 mA

10 mA

50 mA

100 mA

1A

3A

5A

10 A

20 A

25 A

30 A

35 A

AC/ DC

3V

6 A

AC/DC

8V

6 A

AC/DC

B300 Q300

5V (300 mW)

8 A

AC/DC

AgNi + Gold

B300 Q300

5V (50 mW)

8 A

AC/DC single

AgCdO

B300

10V single

AgNi

B300

10V

12V

AC DC

AC DC

(30V Max)

(30V Max)

NEMA Ratings and Test Values NEMA Ratings and Test Values for AC Control Circuit Contacts at 50 or 60 Hz Maximum Current [A] NEMA Contact Rating Designation

Thermal Continuous Test Current [A]

120V

240V

480V

Make

Break

Make

Break

A150

10

60

6.00, - - - - - 7200

720

A300

10

60

6.00

30

3.00, - - - 7200

720

A600

10

60

6.00

30

3.00

15

1.50

12

1.20

7200

720

B150

5

30

3.00, - - - - - 3600

360

Make

600V Break

Make

VA Break

Make

Break

B300

5

30

3.00

15

1.50, - - - 3600

360

B600

5

30

3.00

15

1.50

7.5

0.75

6

0.60

3600

360

C150

2.5

15

1.50, - - - - - 1800

180

C300

2.5

15

1.50

7.5

0.75, - - - 1800

180

C600

2.5

15

1.50

7.5

0.75

3.75

0.375

3

0.30

1800

180

D150

1.0

3.60

0.60, - - - - - 432

72

D300

1.0

3.60

0.60

1.8

0.30, - - - 432

72

D600

0.5

1.80

0.30, - - - - - 216

36

2X A300

20

120

12

60

6.00, - - - 14400

1440

2X A600

20

120

12

60

6.00

30

3.00

24

2.40

14400

1440

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

5

Page 6

General Information

NEMA Ratings and Test Values for DC Control Circuit Contacts Maximum Current [A] NEMA Contact Rating Designation

Thermal Continuous Test Current [A]

5…28V

125V

250V

301…600V

Make or Break at 300V or less [VA]

N150

10

10

2.2, - 275

N300

10

10

2.2

1.1, 275

N600

10

10

2.2

1.1

0.40

275

P150

5.0

5.0

1.1, - 138

P300

5.0

5.0

1.1

0.55, 138

P600

5.0

5.0

1.1

0.55

0.20

138

Q300

2.5

2.5

0.55

0.27

0.11

69

Q600

2.5

2.5

0.55

0.27

0.11

69

2X P600

10

10

2.2

1.1

0.40

275

NEMA Definitions for Contact Arrangements

6

Contact Arrangement

Description

Form A

A Form A contact arrangement is one that has single-pole, single-throw, normally open contacts. The function of this arrangement is to close a circuit when actuated.

Form B

A Form B contact arrangement is one that has single-pole, single-throw, normally closed contacts. The function of this arrangement is to open a circuit when actuated.

Form C

A Form C contact arrangement is one that has single-pole, double-throw contacts with three terminals - one for normally open, one for normally closed, and one common. The function of this arrangement is to transfer a circuit when actuated.

Form X

A Form X contact arrangement is one that has single-pole, single-throw, normally open double-make contacts. The function of this arrangement is to close a circuit when actuated.

or

Form Y

A Form Y contact arrangement is one that has single-pole single-throw normally closed double-break contacts. The function of this arrangement is to open a circuit when actuated.

or

Form Z

A Form Z contact arrangement is one that has single-pole, double-throw, contacts with four terminals, two for normally open and two for normally closed. The function of this arrangement is to open one circuit and close the other.

Diagram

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 7

General Information

Timing Relay Selection Criteria Single Function Timers: Timers that have only 1 timing mode (for example, ON-Delay or OFF-Delay). Multi-Function Timers: Timers that have 4…8 timing modes that are selected by turning the mode selection switch. RESET

ON-Delay or (Delay on Operate) When power is applied continuously (or when power and a start signal are applied), the timing cycle begins. The output contacts change state after the time delay is completed. The contacts will return to their normal state when a reset signal is applied or power is removed.

POWER

ON OFF

START SIGNAL

ON OFF

OUTPUT CHANGED STATE NORMAL STATE

TIME DELAY RESET

OFF-Delay or (Delay on Release) Power is applied continuously. When a start signal is applied, the output contacts change state immediately. When the start signal is removed, the timing cycle begins. The output contacts will return to their normal state once the time delay is completed. Reset will occur when a reset signal is applied or power is removed.

POWER

ON OFF

START SIGNAL

ON OFF

OUTPUT CHANGED STATE NORMAL STATE

TIME DELAY

RESET

One Shot or (Repeat Cycle) Power is applied continuously. When a start signal is applied, the output contacts change state immediately and the timing cycle begins. The output contacts will return to their normal state once the time delay is completed. Reset will occur when a reset signal is applied or power is removed.

POWER

ON OFF

START SIGNAL

ON OFF

OUTPUT CHANGED STATE NORMAL STATE

TIME DELAY RESET

Repeat Cycle or (Flicker) Power is applied continuously. When a start signal is applied, the timing cycle begins. When the time delay is completed, the output contacts change state and the next timing cycle begins. This cycle will repeat until a reset signal is applied or power is removed.

POWER

ON OFF

START SIGNAL

ON OFF

OUTPUT CHANGED STATE NORMAL STATE

OFF TIME

ON TIME

OFF TIME

ON TIME

OFF TIME

Flexibility Mounting, Timing relays are available in several different models. They can be plugged into the same socket as the relay, or use a separate plug-in socket mounting. Contacts, The contacts are of various types and ratings. See the appropriate specification pages for more details. Functionality, Timing relays with multi-range and multi-function capability are available. Allowing you to stock one relay to cover a wide variety of applications. External Trigger Switch, OFF-Delay, One-Shot, and other timer functions require an external trigger switch (from a relay or push button) to control the timing function. The external trigger switch will cause the timing function to start. In OFF-Delay, the trigger switch closes to energize the output and when the trigger switch opens the OFF-Delay starts to time out. At the end of the time delay, the output is de-energized and the output contacts return to their shelf state

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

7

Page 8

General Information

Surge Suppression Information

Photo

700-CF Relay

700-R Relay

8

Max. Transient Voltage Relative to System Voltage

Cat. No.

For use with

Suppression Technique

Max. Relay Contact Dropout Time

700-ADR

700-HA, -HB,-HK, -HP (6…220V DC)

Diode

3X, 700-ADL1

700-HC (6…24V DC)

Diode + LED

3X, 700-ADL1R

700-HB, -HA, -HK, -HP (6…24V DC)

Diode + LED

3X, 700-ADL2

700-HC (28…60V DC)

Diode + LED

3X, 700-ADL2R

700-HB, -HA, -HK, -HP (28…60V DC)

Diode + LED

3X, 700-ADL3

700-HC (110…220V DC)

Diode + LED

3X, 700-ADL3R

700-HB, -HA, -HK, -HP (110…220V DC)

Diode + LED

3X, 700-AR1

700-HB, -HA, -HC,-HK, -HP (6…24V AC/DC)

RC

No Effect

3

700-AR2

700-HB,-HA, -HC,-HK, -HP (110…240V AC/DC)

RC

No Effect, 700-AV1R

700-HB,-HA, -HC,-HK, -HP (6…24V AC)

Varistor + LED

No Effect, 700-AV3R

700-HB, -HA, -HC, -HK, -HP (110…240V AC)

Varistor + LED

No Effect, 700-CF built-in, Diode, 6…10X

100-FSC

100C, 700-CF

R-C Ckt

No Effect

3X

100-FSV

100C, 700-CF

MOV

No Effect, 100-FSD

100C, 700-CF

Diode

70…95 ms

6…10X

100-JE

100C, 700-CF

Diode

5X

6…10X

700-N5

700-P, 700-N

RC

No effect

3X

700-N24

700-P, 700-N

RC

No effect

3X

700-R built-in, Diode, 6…10X

199-FSMA1, FSMA2

700-P, 700-H, 700-CF, 700DC-R

RC

No effect

3X

199-FSMA9, 10, 11

700-P, 700-H, 700-CF, 700DC-R

MOV

No effect, 199-FSMZ

700-P, 700-H, 700-CF, 700DC-R

Diode

5X, Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 9

General Purpose Relays

General Purpose Relays Product Overview

Bulletin No.

700-HA

700-HB

700-HD

700-HF

Type

General-purpose Relay

General-purpose Relay

General-purpose Relay

General-purpose Relay

Features

• Pin-style terminals • Standard ON/OFF flag indicator • Electrical schematic on face • Clear cover for visual inspection • Optional push-to-test and manual override • Optional LED

• Blade-style quick connect terminals • Standard ON/OFF flag indicator • Electrical schematic on face • Clear cover for visual inspection • Optional push-to-test and manual override • Optional LED

• Flange-mounted • Blade-style quick connect terminals • Clear cover for visual inspection

• Square-base • Plug-in quick connect solder terminals • Optional push-to-test • Optional LED

Contact Form

DPDT, 3PDT

DPDT, 3PDT

DPDT, 3PDT

DPDT, 4 PDT

Contact Type

Single

Single

Single

Single

Contact Material

AgNi, AgNi + Gold

AgCdO

AgCdO

AgCdO

Operating Current, Under Resistant Load, Max

700-HA: 10 A 700-HAX: 6 A

15 A

15 A

10 A

Permissible Load, min

700-HA: 10V, 5 mA 700-HAX: 6V 1 mA

10V, 10 mA

10V, 10 mA

5V, 100 mA

Coil Voltage

AC: 6, 12, 24, 48, 110, 120, 230, 240, 277V DC: 6, 12, 24, 36, 48, 60, 80, 110, 125, 140, 220V

AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V

AC: 6, 12, 24, 120, 208, 240V DC: 6, 12, 24, 48, 110V

AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V

Permissible Coil Voltage Variation

80…110% of nom voltage at 50 Hz 80…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC

Contact Ratings

Coil Ratings

85…110% of nom voltage at 50 Hz 85…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC

Electrical Ratings Dielectric Withstand Voltage

Pole-to-pole: 2000V Contact-to-coil: 2000V Contact-to-frame: 2000V

Pole-to-pole: 2500V Contact-to-coil: 4000V Contact-to-frame: 2500V

Pole-to-pole: 2500V Contact-to-coil: 4000V Contact-to-frame: 2500V

Pole-to-pole: 1500V Contact-to-coil: 1500V Contact-to-frame: 1500V

Electrical Service Life (Cycles)

100 000 min

100 000 min

100 000 min

200 000 min 500 000 min (DPDT)

Certifications

CE. cULus, cURus, CSA, Lloyds

CE. cULus, cURus, CSA, Lloyds

CE. UR, CSA, Lloyds

CE., UR, CSA

Socket Catalog Numbers

700-HN100, 700-HN101, 700-HN125, 700-HN126, 700-HN204, 700-HN205

700-HN153, 700-HN154, 700-HN262, 700-HN264

Page

12

22

28

32

Reference

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

9

Page 10

General Purpose Relays

Bulletin Number

700-HC

700-HK

700-HL

700-HP

Type

Interposing/Isolation Relay

Interposing/Isolation Relay

Interposing/Isolation Relay

Interposing/Isolation Relay

Features

• Blade-style terminals • Standard ON/OFF flag indicator • Electrical schematic on face • Clear cover for visual inspection • Optional push-to-test and manual override • Optional LED

• Optional pilot light • Retainer clip (comes with socket) • Low switching capacity • Push-to-test and manual override

• Ideal for PLC Interfaces • Built-in Coil Surge Protection • Fully Assembled Relay/Sockets • Standard LED • Relay or Solid-state Output • Optional: Leakage Current • Suppression Solution

• PCB “Pin Style” mounting • 5 mm pin spacing

Contact Form

DPDT, 4PDT

SPDT, DPDT

SPDT 1 N.O. (SSR)

DPDT

Contact Type

Single

Single

Single

Single

Contact Material

AgNi, AgNi + Gold

AgNi, AgNi + Gold

AgSnO

AgNi, AgNi + Gold

Operating Current, Under Resistant Load, Max

10 A (DPDT) 7 A (4PDT)

8 A (DPDT), 16 A (SPDT)

6 A (SPDT), 2 A (SSR DC output), 2 A (SSR AC output)

8A

Permissible Load, min

10V, 10 mA (Gold), 5V, 10 mA or 25V, 2 mA (Silver)

5V 60 mA (Silver), 5V 10 mA (Gold)

12V 6 mA (72 mW) Silver 8V, 2.5 mA (20 mW) Gold

5V 5 mA (50 mW) Gold, 5V 5 mA (300 mW) Silver

Coil Voltage

AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V

AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V

AC: 12, 24, 48, 110, 120, 230, 240V DC: 12, 24, 48, 125, 230, 240V

AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V

Permissible Coil Voltage Variation

80…110% of nom voltage at 50 Hz 80…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC

80…110% of nom voltage at 50 Hz 80…110% of nom voltage at 60 Hz 73…110% of nom voltage at DC

85…110% of nom voltage at 50 Hz 85…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC

80…110% of nom voltage at 50 Hz 80…110% of nom voltage at 60 Hz 73…150% of nom voltage at DC

Dielectric Withstand Voltage

Pole-to-pole: 1000V Contact-to-coil: 2000V Contact-to-frame: 2000V

Pole-to-pole: 1500V Contact-to-coil: 1500V Contact-to-frame: 1500V

Pole-to-pole: 1000V Contact-to-coil: 4000V Contact-to-frame: 1500V

Pole-to-pole: 2000V Contact-to-coil: 5000V

Electrical Service Life (Cycles)

100 000 min

100 000 min

100 000 min

100 000 min

Certifications

CE, cULus, cURus, CSA, Lloyds

CE, UL, UR, CSA

CE, cURus, cULus, ABS

CE, cULus, cURus, CSA, Lloyds

Socket Catalog Numbers

700-HN103, 700-HN128, 700-HN104

700-HN121, 700-HN221, 700-HN122,, 700-HN222, 700-HN223, 700-HN224

700-HN123, 700-HN230

Page Number

39

44

64

Contact Ratings

Coil Ratings

Electrical Ratings

Reference

10

50