The text of a spec sheet · part 1 of 25
Relay and Timer Specifications, Bulletin Number 700, pages 1 to 10
Pages 1 to 10 of 250
The original document is the PDF (23 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX
Page 1
Technical Data
Relay and Timer Specifications Bulletin Number 700 Topic Topic
Page
Page
NEMA Industrial Relays
149
Summary of Changes
2
700-P Industrial Relays
151
General Information
3
700S-P and 700S-PK, Heavy-Duty Safety Control Relays
167
General Purpose Relays
9
700-N Industrial Relays
172
700-HA General-purpose Relay
12
700-R Sealed Switch Relays
176
700-HB Square Base Relay
22
700-RTC, Solid-State Timing Relay
181
700-HD Flange Mount Square Base Relay
28
IEC Control Relays
187
700-HF Square Base Relay
32
700-CF Control Relay
188
700-HC Miniature Ice Cube Relay
39
700S-CF Control Relays
207
700-HK Slim Line Relay
44
700-K Miniature Control Relays
212
700-HL Terminal Block Relay
50
Solid-state Relays
219
700-HLF Terminal Block Timing Relay
60
Solid-state Relay Glossary
221
700-HP Slim Line Relay
64
700-SC Ice Cube Relays
226
700-HJ Magnetic Latching Relay
71
700-SF Square Base Relays
231
700-HG Power Relay
75
700-SH Hockey Puck Relays
235
700-HHF Flange Mount Power Relay
80
700-SK Slim Line Relays
244
700-HTA Alternating Relay
83
General Purpose Electronic Timers and Counters
89
700-FE Economy Timing Relay
92
700-FS High Performance Timing Relay
96
700-HNC Miniature Timing Relay
103
700-HNK Ultra-Slim Timing Relay
109
700-HR Dial Timing Relays
116
700-HT Plug-in Timing Relay
128
700-HV Timing Relay
133
700-HX Multi-Function Digital Timing Relay
138
Page 2
Relay and Timer Specifications
Summary of Changes This publication contains new and updated information as indicated in the following table.
2
Topic
Page
Added Product Selection and Accessories throughout
Removed 700-RM Relays, 700-CF, 700s-CF - removed Standard and Standard diode DC coils/coil voltage codes
189, 208
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 3
General Information
General Information Contact Data Tables
IEC Relays
AC and DC Switching Capability Relay Type
Contact Arrangement
Contact Style
Contact Material
NEMA Pilot Duty(1)
700-CF
Up to 8 form X or 8 form Y cross stamped
Ag
A600 P600
Up to 8 form X or 8 form Y cross stamped
700-K
Up to 8 form X or 8 form Y bifurcated
AgCu
A300 Q300
700-P
Up to 12 form X or 8 form Y bifurcated
NiAg
A600 P600
Up to 12 form X or 8 form Y single
700S-CF
700-PK
Ag
AgCdO
A600 P600
1 mA
20 mA
50 mA
100 mA
1A
3A
5A
24V
10 A
20 A
25 A
30 A
35 A
AC DC
AC
24 V
DC
AC
17V
DC
10V
AC DC
2X A600 2X P600
10V
AC DC
(20 A Lighting Load)
NEMA Relays
AC Up to 6 form X or 4 form Y tandem
700-R
Up to 8 form A or form B sealed sw.
W
B300 C600 P300
5V
AC DC
700-RTC
Up to 4 form A or form B sealed sw.
W
B600 P300
5V
AC DC
700S-P
Up to 12 form X or 8 form Y bifurcated
NiAg
A600 P600
700-PH
AgCdO
A600 P600
10V DC
10V
(35 A Lighting Load)
AC
(1) NEMA contact rating chart is on page 19.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
3
Page 4
General Information
Contact Data Tables
General Purpose Relays
Timing Relays
AC and DC Switching Capability
Relay Type
Contact Arrangement
Contact Style
NEMA Contact Pilot Material Duty
700-FE
1 N.O.
single
AgCdO
D300
10V
700-FS
1, 2 form C single
AgCdO
B300
10V
700-HA
2, 3 form C single
AgNi
B300
10V
700-HAX
2, 3 form C bifurcated
Au/AgNi
B300
700-HB
2, 3 form C single
AgNi
B300
700-HC14
4 form C single
Ag/Au
C300 Q300
700-HC22
2 form C single
AgNi
B300 Q300
10V
AC DC
700-HC24
4 form C single
AgNi
C300 Q300
10V
AC DC (30V Max.)
700-HD
2, 3 form C single
AgCdO
B300
10V
700-HF
2, 3, 4 form C single
AgCdO
B300
10V
700-HG
1 form X, 1 form C, 2 form A, 2 form C single
AgNi
A600
10V
AC DC (28V Max)
700HHF45
1 form X single
AgNi
A600
10V
AC DC (28V Max)
700HHF62
2 form C single
AgNi
B600
10V
700HHF73
3 form C single
AgNi
B300
700-HJ
1, 2 form C single
AgCdO, 700-HK36
1 form C single
AgNi
B300
700-
1 form C single
Au/AgNi
B300
700-HK32
2 form C single
AgNi
B300
10 mA
1 mA
50 mA
100 mA
1A
3A
4
2 form C single
Au/AgNi
10 A
20 A
25 A
30 A
35 A
AC DC (24V Max.) AC DC (24V Max.) AC DC (24V Max) AC DC (24V Max)
6V
AC DC (24VMax.)
10V AC DC (30V Max.)
10V
AC DC (24V Max) AC DC (30V Max)
AC DC (28V Max) AC DC (28V Max)
10V
10V
AC DC (24V Max.)
10V
AC DC (30V Max)
5V
700-
5A
B300
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
AC DC (30V Max)
Page 5
General Information
Contact Data Tables
General Purpose Relays (continued)
AC and DC Switching Capability Relay Type
Contact Arrangement
Contact Style
Contact Material
NEMA Pilot Duty
700-HLS
Solid-State 1 N.O., - - 700-HLT
1 Form C single
AgSnO
B300 R300
700-HLT_ _X
1 Form C single
AgSnO
B300 R300
700-HP
2 Form C single
AgNi
700-HPX
2 Form C single
700-HS
2 Form C
700-HT
2 form C
1 mA
10 mA
50 mA
100 mA
1A
3A
5A
10 A
20 A
25 A
30 A
35 A
AC/ DC
3V
6 A
AC/DC
8V
6 A
AC/DC
B300 Q300
5V (300 mW)
8 A
AC/DC
AgNi + Gold
B300 Q300
5V (50 mW)
8 A
AC/DC single
AgCdO
B300
10V single
AgNi
B300
10V
12V
AC DC
AC DC
(30V Max)
(30V Max)
NEMA Ratings and Test Values NEMA Ratings and Test Values for AC Control Circuit Contacts at 50 or 60 Hz Maximum Current [A] NEMA Contact Rating Designation
Thermal Continuous Test Current [A]
120V
240V
480V
Make
Break
Make
Break
A150
10
60
6.00, - - - - - 7200
720
A300
10
60
6.00
30
3.00, - - - 7200
720
A600
10
60
6.00
30
3.00
15
1.50
12
1.20
7200
720
B150
5
30
3.00, - - - - - 3600
360
Make
600V Break
Make
VA Break
Make
Break
B300
5
30
3.00
15
1.50, - - - 3600
360
B600
5
30
3.00
15
1.50
7.5
0.75
6
0.60
3600
360
C150
2.5
15
1.50, - - - - - 1800
180
C300
2.5
15
1.50
7.5
0.75, - - - 1800
180
C600
2.5
15
1.50
7.5
0.75
3.75
0.375
3
0.30
1800
180
D150
1.0
3.60
0.60, - - - - - 432
72
D300
1.0
3.60
0.60
1.8
0.30, - - - 432
72
D600
0.5
1.80
0.30, - - - - - 216
36
2X A300
20
120
12
60
6.00, - - - 14400
1440
2X A600
20
120
12
60
6.00
30
3.00
24
2.40
14400
1440
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
5
Page 6
General Information
NEMA Ratings and Test Values for DC Control Circuit Contacts Maximum Current [A] NEMA Contact Rating Designation
Thermal Continuous Test Current [A]
5…28V
125V
250V
301…600V
Make or Break at 300V or less [VA]
N150
10
10
2.2, - 275
N300
10
10
2.2
1.1, 275
N600
10
10
2.2
1.1
0.40
275
P150
5.0
5.0
1.1, - 138
P300
5.0
5.0
1.1
0.55, 138
P600
5.0
5.0
1.1
0.55
0.20
138
Q300
2.5
2.5
0.55
0.27
0.11
69
Q600
2.5
2.5
0.55
0.27
0.11
69
2X P600
10
10
2.2
1.1
0.40
275
NEMA Definitions for Contact Arrangements
6
Contact Arrangement
Description
Form A
A Form A contact arrangement is one that has single-pole, single-throw, normally open contacts. The function of this arrangement is to close a circuit when actuated.
Form B
A Form B contact arrangement is one that has single-pole, single-throw, normally closed contacts. The function of this arrangement is to open a circuit when actuated.
Form C
A Form C contact arrangement is one that has single-pole, double-throw contacts with three terminals - one for normally open, one for normally closed, and one common. The function of this arrangement is to transfer a circuit when actuated.
Form X
A Form X contact arrangement is one that has single-pole, single-throw, normally open double-make contacts. The function of this arrangement is to close a circuit when actuated.
or
Form Y
A Form Y contact arrangement is one that has single-pole single-throw normally closed double-break contacts. The function of this arrangement is to open a circuit when actuated.
or
Form Z
A Form Z contact arrangement is one that has single-pole, double-throw, contacts with four terminals, two for normally open and two for normally closed. The function of this arrangement is to open one circuit and close the other.
Diagram
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 7
General Information
Timing Relay Selection Criteria Single Function Timers: Timers that have only 1 timing mode (for example, ON-Delay or OFF-Delay). Multi-Function Timers: Timers that have 4…8 timing modes that are selected by turning the mode selection switch. RESET
ON-Delay or (Delay on Operate) When power is applied continuously (or when power and a start signal are applied), the timing cycle begins. The output contacts change state after the time delay is completed. The contacts will return to their normal state when a reset signal is applied or power is removed.
POWER
ON OFF
START SIGNAL
ON OFF
OUTPUT CHANGED STATE NORMAL STATE
TIME DELAY RESET
OFF-Delay or (Delay on Release) Power is applied continuously. When a start signal is applied, the output contacts change state immediately. When the start signal is removed, the timing cycle begins. The output contacts will return to their normal state once the time delay is completed. Reset will occur when a reset signal is applied or power is removed.
POWER
ON OFF
START SIGNAL
ON OFF
OUTPUT CHANGED STATE NORMAL STATE
TIME DELAY
RESET
One Shot or (Repeat Cycle) Power is applied continuously. When a start signal is applied, the output contacts change state immediately and the timing cycle begins. The output contacts will return to their normal state once the time delay is completed. Reset will occur when a reset signal is applied or power is removed.
POWER
ON OFF
START SIGNAL
ON OFF
OUTPUT CHANGED STATE NORMAL STATE
TIME DELAY RESET
Repeat Cycle or (Flicker) Power is applied continuously. When a start signal is applied, the timing cycle begins. When the time delay is completed, the output contacts change state and the next timing cycle begins. This cycle will repeat until a reset signal is applied or power is removed.
POWER
ON OFF
START SIGNAL
ON OFF
OUTPUT CHANGED STATE NORMAL STATE
OFF TIME
ON TIME
OFF TIME
ON TIME
OFF TIME
Flexibility Mounting, Timing relays are available in several different models. They can be plugged into the same socket as the relay, or use a separate plug-in socket mounting. Contacts, The contacts are of various types and ratings. See the appropriate specification pages for more details. Functionality, Timing relays with multi-range and multi-function capability are available. Allowing you to stock one relay to cover a wide variety of applications. External Trigger Switch, OFF-Delay, One-Shot, and other timer functions require an external trigger switch (from a relay or push button) to control the timing function. The external trigger switch will cause the timing function to start. In OFF-Delay, the trigger switch closes to energize the output and when the trigger switch opens the OFF-Delay starts to time out. At the end of the time delay, the output is de-energized and the output contacts return to their shelf state
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
7
Page 8
General Information
Surge Suppression Information
Photo
700-CF Relay
700-R Relay
8
Max. Transient Voltage Relative to System Voltage
Cat. No.
For use with
Suppression Technique
Max. Relay Contact Dropout Time
700-ADR
700-HA, -HB,-HK, -HP (6…220V DC)
Diode
3X, 700-ADL1
700-HC (6…24V DC)
Diode + LED
3X, 700-ADL1R
700-HB, -HA, -HK, -HP (6…24V DC)
Diode + LED
3X, 700-ADL2
700-HC (28…60V DC)
Diode + LED
3X, 700-ADL2R
700-HB, -HA, -HK, -HP (28…60V DC)
Diode + LED
3X, 700-ADL3
700-HC (110…220V DC)
Diode + LED
3X, 700-ADL3R
700-HB, -HA, -HK, -HP (110…220V DC)
Diode + LED
3X, 700-AR1
700-HB, -HA, -HC,-HK, -HP (6…24V AC/DC)
RC
No Effect
3
700-AR2
700-HB,-HA, -HC,-HK, -HP (110…240V AC/DC)
RC
No Effect, 700-AV1R
700-HB,-HA, -HC,-HK, -HP (6…24V AC)
Varistor + LED
No Effect, 700-AV3R
700-HB, -HA, -HC, -HK, -HP (110…240V AC)
Varistor + LED
No Effect, 700-CF built-in, Diode, 6…10X
100-FSC
100C, 700-CF
R-C Ckt
No Effect
3X
100-FSV
100C, 700-CF
MOV
No Effect, 100-FSD
100C, 700-CF
Diode
70…95 ms
6…10X
100-JE
100C, 700-CF
Diode
5X
6…10X
700-N5
700-P, 700-N
RC
No effect
3X
700-N24
700-P, 700-N
RC
No effect
3X
700-R built-in, Diode, 6…10X
199-FSMA1, FSMA2
700-P, 700-H, 700-CF, 700DC-R
RC
No effect
3X
199-FSMA9, 10, 11
700-P, 700-H, 700-CF, 700DC-R
MOV
No effect, 199-FSMZ
700-P, 700-H, 700-CF, 700DC-R
Diode
5X, Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 9
General Purpose Relays
General Purpose Relays Product Overview
Bulletin No.
700-HA
700-HB
700-HD
700-HF
Type
General-purpose Relay
General-purpose Relay
General-purpose Relay
General-purpose Relay
Features
• Pin-style terminals • Standard ON/OFF flag indicator • Electrical schematic on face • Clear cover for visual inspection • Optional push-to-test and manual override • Optional LED
• Blade-style quick connect terminals • Standard ON/OFF flag indicator • Electrical schematic on face • Clear cover for visual inspection • Optional push-to-test and manual override • Optional LED
• Flange-mounted • Blade-style quick connect terminals • Clear cover for visual inspection
• Square-base • Plug-in quick connect solder terminals • Optional push-to-test • Optional LED
Contact Form
DPDT, 3PDT
DPDT, 3PDT
DPDT, 3PDT
DPDT, 4 PDT
Contact Type
Single
Single
Single
Single
Contact Material
AgNi, AgNi + Gold
AgCdO
AgCdO
AgCdO
Operating Current, Under Resistant Load, Max
700-HA: 10 A 700-HAX: 6 A
15 A
15 A
10 A
Permissible Load, min
700-HA: 10V, 5 mA 700-HAX: 6V 1 mA
10V, 10 mA
10V, 10 mA
5V, 100 mA
Coil Voltage
AC: 6, 12, 24, 48, 110, 120, 230, 240, 277V DC: 6, 12, 24, 36, 48, 60, 80, 110, 125, 140, 220V
AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V
AC: 6, 12, 24, 120, 208, 240V DC: 6, 12, 24, 48, 110V
AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V
Permissible Coil Voltage Variation
80…110% of nom voltage at 50 Hz 80…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC
Contact Ratings
Coil Ratings
85…110% of nom voltage at 50 Hz 85…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC
Electrical Ratings Dielectric Withstand Voltage
Pole-to-pole: 2000V Contact-to-coil: 2000V Contact-to-frame: 2000V
Pole-to-pole: 2500V Contact-to-coil: 4000V Contact-to-frame: 2500V
Pole-to-pole: 2500V Contact-to-coil: 4000V Contact-to-frame: 2500V
Pole-to-pole: 1500V Contact-to-coil: 1500V Contact-to-frame: 1500V
Electrical Service Life (Cycles)
100 000 min
100 000 min
100 000 min
200 000 min 500 000 min (DPDT)
Certifications
CE. cULus, cURus, CSA, Lloyds
CE. cULus, cURus, CSA, Lloyds
CE. UR, CSA, Lloyds
CE., UR, CSA
Socket Catalog Numbers
700-HN100, 700-HN101, 700-HN125, 700-HN126, 700-HN204, 700-HN205
700-HN153, 700-HN154, 700-HN262, 700-HN264
Page
12
22
28
32
Reference
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
9
Page 10
General Purpose Relays
Bulletin Number
700-HC
700-HK
700-HL
700-HP
Type
Interposing/Isolation Relay
Interposing/Isolation Relay
Interposing/Isolation Relay
Interposing/Isolation Relay
Features
• Blade-style terminals • Standard ON/OFF flag indicator • Electrical schematic on face • Clear cover for visual inspection • Optional push-to-test and manual override • Optional LED
• Optional pilot light • Retainer clip (comes with socket) • Low switching capacity • Push-to-test and manual override
• Ideal for PLC Interfaces • Built-in Coil Surge Protection • Fully Assembled Relay/Sockets • Standard LED • Relay or Solid-state Output • Optional: Leakage Current • Suppression Solution
• PCB “Pin Style” mounting • 5 mm pin spacing
Contact Form
DPDT, 4PDT
SPDT, DPDT
SPDT 1 N.O. (SSR)
DPDT
Contact Type
Single
Single
Single
Single
Contact Material
AgNi, AgNi + Gold
AgNi, AgNi + Gold
AgSnO
AgNi, AgNi + Gold
Operating Current, Under Resistant Load, Max
10 A (DPDT) 7 A (4PDT)
8 A (DPDT), 16 A (SPDT)
6 A (SPDT), 2 A (SSR DC output), 2 A (SSR AC output)
8A
Permissible Load, min
10V, 10 mA (Gold), 5V, 10 mA or 25V, 2 mA (Silver)
5V 60 mA (Silver), 5V 10 mA (Gold)
12V 6 mA (72 mW) Silver 8V, 2.5 mA (20 mW) Gold
5V 5 mA (50 mW) Gold, 5V 5 mA (300 mW) Silver
Coil Voltage
AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V
AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V
AC: 12, 24, 48, 110, 120, 230, 240V DC: 12, 24, 48, 125, 230, 240V
AC: 6, 12, 24, 120, 240V DC: 6, 12, 24, 48, 110V
Permissible Coil Voltage Variation
80…110% of nom voltage at 50 Hz 80…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC
80…110% of nom voltage at 50 Hz 80…110% of nom voltage at 60 Hz 73…110% of nom voltage at DC
85…110% of nom voltage at 50 Hz 85…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC
80…110% of nom voltage at 50 Hz 80…110% of nom voltage at 60 Hz 73…150% of nom voltage at DC
Dielectric Withstand Voltage
Pole-to-pole: 1000V Contact-to-coil: 2000V Contact-to-frame: 2000V
Pole-to-pole: 1500V Contact-to-coil: 1500V Contact-to-frame: 1500V
Pole-to-pole: 1000V Contact-to-coil: 4000V Contact-to-frame: 1500V
Pole-to-pole: 2000V Contact-to-coil: 5000V
Electrical Service Life (Cycles)
100 000 min
100 000 min
100 000 min
100 000 min
Certifications
CE, cULus, cURus, CSA, Lloyds
CE, UL, UR, CSA
CE, cURus, cULus, ABS
CE, cULus, cURus, CSA, Lloyds
Socket Catalog Numbers
700-HN103, 700-HN128, 700-HN104
700-HN121, 700-HN221, 700-HN122,, 700-HN222, 700-HN223, 700-HN224
700-HN123, 700-HN230
Page Number
39
44
64
Contact Ratings
Coil Ratings
Electrical Ratings
Reference
10
50
Rockwell Automation Publication 700-TD552B-EN-P - August 2018