Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 2 of 25

Relay and Timer Specifications, Bulletin Number 700, pages 11 to 20

Pages 11 to 20 of 250

The original document is the PDF (23 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX

Page 11

General Purpose Relays

Bulletin Number

700-HJ

700-HG

700-HHF

Type

Magnetic Latching Relay

Power Relay

Power Relay

Features

• Socket mounted • Ideal for lighting applications

• Panel mount with screw terminals • Optional magnetic blowouts for switching DC loads • Optional snap action switch

• Flange mounted • Optional LED

Contact Form

SPDT, DPDT (Single or Dual Coil)

SPST-N.O.-DM, SPDT, DPST-N.O., DPDT

SPST-NO-DM, DPDT, 3PDT

Contact Type

Single

Single

Single

Contact Material

AgCdO

AgNi

AgNi

Operating Current, Under Resistant Load, Max

10 A

40 A

20 A (3PDT), 25 A (DPDT), 30 A (SPDT)

Permissible Load, min

10V 50 mA

10V 50 mA

10V 50 mA 10V 100 mA (3PDT)

Coil Voltage

AC: 24V, 120V, 240V DC: 12V, 24V

AC: 24V, 120V, 240V, 277V, 480V DC: 12V, 24V, 48V, 110V, 220V, 250V

AC: 24V, 120V, 240V DC: 6V,12V, 24V

Permissible Coil Voltage Variation

85…110% of nom voltage at 50 Hz 85…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC

85…110% of nom voltage at 50 Hz 85…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC

85…110% of nom voltage at 50 Hz 85…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC

Dielectric Withstand Voltage

Pole-to-pole: 1500V AC Contact-to-coil: 1500V AC Contact-to-frame: 1500V AC

Pole-to-pole: 2200V AC Contact-to-coil: 2200V AC Contact-to-frame: 2200V AC

Pole-to-pole: 2200V AC Contact-to-coil: 2200V AC Contact-to-frame: 2200V AC

Electrical Service Life (Cycles)

100 000 minimum

100 000 minimum

100 000 minimum

Certifications

CE, UR, CSA

CE, UL, CSA

CE, UR, CSA

Socket Catalog Numbers

700-HN153, 700-HN154, - Page Number

71

75

80

Contact Ratings

Coil Ratings

Electrical Ratings

Reference

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

11

Page 12

General Purpose Relays

700-HA General-purpose Relay •

10 A contact rating

•

DPDT, 3PDT

•

Pin-style terminals

•

Standard ON/OFF flag indicator

•

Options: LED, push-to-test and manual override, socket-mounted surge suppressor module, or multi-function timer

•

Contact choices: standard silver nickel, or bifurcated silver nickel with gold plating

Tube Base Relay with PIN Terminals (Single Contact), Mechanical ON/OFF Indicator Included(1) Description

Wiring Diagrams

Contact Rating

U.S./Canada

DPDT 2-pole 2 Form C Single AgNi Contact

10 A B300

Sockets

3PDT 3-pole 3 Form C Single AgNi Contact

700-HN125

700-HN100 700-HN204

700-HN126

700-HN101 700-HN205

10 A B300

Sockets (1)

Coil Voltage

6V AC 12V AC 24V AC 120V AC 240V AC 277V AC 6V DC 12V DC 24V DC 36V DC 48V DC 60V DC 80V DC 110V DC 125V DC 140V DC 220V DC 6V AC 12V AC 24V AC 120V AC 240V AC 6V DC 12V DC 24V DC 48V DC 60V DC 80V DC 110V DC 125V DC 140V DC 220V DC

700-HA32A06 700-HA32A12 700-HA32A24 700-HA32A1 700-HA32A2 700-HA32A27 700-HA32Z06 700-HA32Z12 700-HA32Z24 700-HA32Z36 700-HA32Z48 700-HA32Z60 700-HA32Z80 700-HA32Z1 700-HA32Z01 700-HA32Z3 700-HA32Z2 700-HA33A06 700-HA33A12 700-HA33A24 700-HA33A1 700-HA33A2 700-HA33Z06 700-HA33Z12 700-HA33Z24 700-HA33Z48 700-HA33Z60 700-HA33Z80 700-HA33Z1 700-HA33Z01 700-HA33Z3 700-HA33Z2

LED Option: Add suffix (-4) to the selected 700-HA Relay Cat. No., except for the 240V AC Units, add (-4L). Push-to-test, Manual Override, and LED Option: Add suffix (-3-4) to the selected 700-HA Relay Cat. No., except for the 240V AC units, add (-3-4L). Push-to-test and Manual Override option: Add suffix (-3) to the selected 700-HA relay. LED not available for 220V DC and 277V AC coils.

(1) For Time Modules and Surge Suppressor Modules, see Accessories.

12

Cat. No.(1)

International

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 13

General Purpose Relays

Tube Base Relay with PIN Terminals (Bifurcated Contacts with Gold Overlay), Mechanical ON/OFF Indicator Included Description

DPDT 2-Pole 2 Form C Bifurcated AgNi Contacts with Gold Plating

Contact Rating

Sockets

U.S./Canada

International

6A

Sockets

3PDT 3-Pole 3 Form C Bifurcated AgNi Contacts with Gold Plating

Wiring Diagrams

700-HN125

700-HN100 700-HN204

6A

700-HN126

700-HN101 700-HN205

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Coil Voltage

Cat. No

6V AC

700-HAX2A06

12V AC

700-HAX2A12

24V AC

700-HAX2A24

120V AC

700-HAX2A1

240V AC

700-HAX2A2

277V AC

700-HAX2A27Δ

6V DC

700-HAX2Z06

12V DC

700-HAX2Z12

24V DC

700-HAX2Z24

36V DC

700-HAX2Z36

48V DC

700-HAX2Z48

110V DC

700-HAX2Z1

125V DC

700-HAX2Z01

140V DC

700-HAX2Z3

6V AC

700-HAX3A06

12V AC

700-HAX3A12

24V AC

700-HAX3A24

120V AC

700-HAX3A1

240V AC

700-HAX3A2

6V DC

700-HAX3Z06

12V DC

700-HAX3Z12

24V DC

700-HAX3Z24

48V DC

700-HAX3Z48

110V DC

700-HAX3Z1

125V DC

700-HAX3Z01

140V DC

700-HAX3Z3

13

Page 14

General Purpose Relays

Accessories - 700-HA Relays Photo

Photo

14

Description

Pkg. Qty.

Cat. No.

Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with DPDT 700-HA Relays, -HX Timing Relays, -HT (On-Delay), and -HRM, HRC and -HV (Repeat Cycle) Timing Relays.

10

700-HN100

Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Open Style Construction. 8Pin for use with DPDT 700-HA Relays, -HT (On-Delay) and -HRM, -HRC, and -HV (Repeat Cycle) Timing Relays. No retainer clip required.

10

700-HN125

Screw Terminal Tube Base Sockets, Panel or DIN Rail Mounting; Guarded Terminal Construction. 11-pin for use with 3PDT 700-HA relays.

10

700-HN101

Screw Terminal Tube Base Sockets, Panel or DIN Rail Mounting; Open Style Terminal Construction. 11-pin for use with 3PDT 700-HA relays. No retainer clip required.

10

700-HN126

8-Pin Socket, Can Be Used With or Without Timing Attachment or Surge Suppressor Screw Terminal Tube Base Sockets, panel or DIN Rail mounting. Guarded terminal construction. Used with DPDT 700-HA Relays.

10

700-HN204

11-Pin Socket, Can Be Used With or Without Timing Module or Surge Suppressor. Screw Terminal Tube Base Sockets, panel or DIN Rail mounting. Guarded terminal construction. Used with 3PDT 700-HA relays.

10

700-HN205

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Description

Pkg. Qty. Cat. No.

Diode Surge Suppressor Voltage Range: 6…220V DC used with 700-HN204 and 700-HN205 socket

10

700-ADR

Diode with LED Surge Suppressor Voltage Range: 6…24V DC used with 700-HN204 and 700-HN205 socket 10

700-ADL1R

Diode with LED Surge Suppressor Voltage Range: 28…60V DC used with 700-HN204 and 700-HN205 socket

10

700-ADL2R

Diode with LED Surge Suppressor Voltage Range: 110…220V DC used with 700-HN204 and 700-HN205 socket

10

700-ADL3R

Varistor with LED Surge Suppressor Voltage Range: 6…24V AC used with 700-HN204 and 700-HN205 socket

10

700-AV1R

Varistor with LED Surge Suppressor Voltage Range: 110…240V AC used with 700-HN204 and 700-HN205 socket

10

700-AV3R

RC Surge Suppressor Voltage Range: 6…24V AC/DC used with 700-HN204 and 700-HN205 socket

10

700-AR1

RC Surge Suppressor Voltage Range: 110…240V AC/DC used with 700-HN204 and 700-HN205 socket

10

700-AR2

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 15

General Purpose Relays

Photo

Pkg. Qty. Cat. No.

Description Timing Module On-Delay or One-Shot selectable voltage range: 12…24V AC/DC used with sockets that accept plug-in accessory modules. Timing Module On-Delay or One-Shot selectable voltage range: 110…125V AC used with sockets that accept plug-in accessory modules. Timing Module On-Delay or One-Shot selectable voltage range: 230…240V AC used with sockets that accept plug-in accessory modules.

1

700-AT3

1

700-AT3A1

1

700-AT3A2

1

700-HT3

On-Delay U (A1/A2) LED & R t

One-Shot U (A1/A2) LED & R

1. 1 s

0.05 s…1 s

2. 10 s

0.5 s…10 s

3. 100 s

5 s…100 s

4. 10 min

0.5 min…10 min

5. 100 min

5 min…100 min

6. 10 hours

0.5 h…10 h

7. 100 hours

5 h…100 h t

8. LED Indicator

Socket and Retainer Clip Reference Relay Type

Socket

Retainer Clip

700-HA32 700-HAX2

700-HN100 700-HN125 700-HN204

700-HN157 Not Required 700-HN157

700-HA33 700-HAX3

700-HN101 700-HN126 700-HN205

700-HN157 Not Required 700-HN157

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

15

Page 16

General Purpose Relays

Specifications - 700-HA Relays Attribute

700-HA

Electrical Ratings Pilot Duty Rating (1)

NEMA B300

Rated Thermal Current (Ith)

HA = 10 A – 120V, 240V; HAX = 6 A – 120V, 240V

Rated Insulation Voltage (Ui)

250V IEC – 300V UL/CSA Make

Break

Hp

120V AC

30 A

3A

1/3

240V AC

15 A

1.5 A

1

Inductive Contacts

General-purpose

10 A, 240V AC

Resistive

10 A, 30V DC

Min. Low Energy Permissible Load

HA = 10V, 5 mA HAX = 5V, 2 mA

Permissible Coil Voltage Variation

Coil Consumption ±10%

Pickup:80…110% of nom voltage at 50 Hz, 80…110% of nom voltage at 60 Hz, 80…110% of nom voltage at DC AC Coils

50 Hz

60 Hz

Inrush

3.3VA

2.85VA

Sealed

2.2VA

1.9VA

DC Coils

1.3 W

Must Dropout Voltage

20% of nom V AC; 10% of nom V DC

Max. Contact Resistance

50 MΩ (700-HA), 30 MΩ (700-HAX)

Design Specification/Test Requirements Electrical Pole-to-Pole

2000V

Contact to Coil

2000V

Electrical Life (Operating)

100 000 min. Mechanical

Degree of Protection (Open Type) IEC 529

IP 40

Mechanical Lifecycles (AC/DC)

> 20 x 106/ 50 x 106

Switching Frequency Operations

3600/HR

Coil Voltages Operating Time

See Product Selection Max. Pickup

10 ms

Max. Dropout

10 ms

Maximum Operating Rate Vibration Shock

4 Ops/s Endurance

5G

Operational

2.5 G

Endurance

50 G

Operational

9G Environmental

Temperature

Operating

AC/DC

–40…+70 °C

Storage

AC/DC

–40…+100 °C

Altitude

2000 m (6560 ft) Construction

Insulating Material

Molded High-Dielectric Material

Enclosure Contact Material Terminal Markings on Socket Sockets

Transparent Dust Cover 700-HA:

10 A – AgNi

700-HAX:

6 A – Bifurcated/Gold Plating AgNi In accordance with EN50 0005

8-Pin Socket, 700-HN100, -HN125, -HN204, 11-Pin Socket, 700-HN101, -HN126, -HN205

Certifications cURus Recognized (File No. E3125, Guide NLDX2/NLDX8), cULus Listed when used with 700-HN sockets noted (File No. E3125, Guide NLDX/NLDX7), CE Marked, CSA Certified, UR Certified (File 229473)

Standards

UL508, CSA C22.2 No. 14, EN 61810-1

(1) See NEMA Ratings and Test Values on page 5

16

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 17

General Purpose Relays

Load (kVA) Contact life vs. AC1 load at 1,800 cycles/h k Reduction Factor

Cycles

Max. Switching Current (A)

Relay Performance Graphs

Voltage DC (V)

COS φ

Breaking capacity for DC1 load at 1,800 cycles/h

Load reduction factor vs. cos φ

A = load applied to one contact B = load applied to two contacts in series C = load applied to three contacts in series

Specifications - 700-HT3 Time Module Attribute

700-HT3 Electrical Ratings

Operating Voltage Range

12…240V AC (50/60 Hz) 12…240V DC 0.1 W (12V) 1.0 W (230V)

Power Consumption Mechanical Degree of Protection of Input (B1) Terminal

IP 20 (Guarded Terminal)

Input Terminal Wire Range

1.0 x 0.2 mm2…2.5 mm2 (24 AWG…14 AWG) 2.0 x 0.2 mm2…1.5 mm2 (24 AWG…16 AWG)

Input Terminal Torque Range

0.45…0.8 Nm (4…7 lb-in.)

Status Indicator Repeat Accuracy

Red (1)

±1%

Recovery Time

<50 ms Three DIP switches, seven ranges (set from 5…100% of range): 1 s, 10 s, 100 s, 10 min, 100 min, 10 h, 100 h

Selectable Timing Ranges

Three DIP switches, eight modes: 1. Power On–Delay 2. Power On One-Shot 3. Power On Repeat Cycle, On Start 4. Signal On-Delay and Signal Off-Delay

Selectable Timing Modes

Adjustable Trimmer Scale Accuracy

5. Signal Off-Delay 6. Signal On-One-Shot 7. Signal Off-One-Shot 8. Signal On and Signal Off Watchdog Monitor

±5% of Time Range

Environmental Operating

–20 °C…+50 °C (–4 °F…+122 °F)

Storage

–55 °C…+85 °C (–67…+185 °F)

Temperature Altitude

2000 m (6560 ft)

Construction Enclosure Mounting with Socket Only Sockets

Gray Plastic Housing 8- or 11-Pin Socket with Module Plug 700-HN204 (8-Pin with Plug), 700-HN205 (11-Pin with Plug)

Certifications cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), CE Marked

Standards

UL508, CSA C22.2 No. 14, EN 61810-1

(1) At constant voltage and temperature.

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

17

Page 18

General Purpose Relays

Timing Charts - 700-HT3 Multi-function Time Module (t = Time Range 0.05 s…100 h) Terms: U is Power Input R is Relay Output S Signal, +A1 Socket, B1 Timer t is the resulting Time Delay (Red light-emitting diode) 1. Power On-delay Apply power (U) to timer. Relay contacts (R) change state after time delay (t) is complete. Contacts return to their shelf state when power is removed. Terminal B1 is not used in this mode.

3. Power On Repeat Cycle, On Start Apply power (U) to timer. Relay contacts (R) change state immediately and the time delay (t) begins. When the time delay is complete, the contacts return to their shelf state for time delay (t) (time on = time-off). This cycle repeats until the power is removed. Terminal B1 is not used in this mode.

2. Power On One-shot Apply power (U) to timer. Relay contacts (R) change state immediately and the time delay begins. When the time delay (t) is complete, contacts return to their shelf state. Contacts return to their shelf state when power is removed. Terminal B1 is not used in this mode.

4. Signal On-delay and Signal Off-delay Apply power (U) to timer. When the signal (S) is closed the time delay (t) begins, after the time delay is completed the relay contacts (R) change state. Opening the signal starts the time delay, after the time delay is completed the contacts return to their shelf state. If the signal is closed or opened before the time delay is complete, the time delay is reset. Contacts return to their shelf state when power is removed.

Timing Charts -Cat. No. 700-HT3 Timing Modes, Time Description, Timing Charts, and DIP Switch Selections Terms: U is Power Input R is Relay Output S Signal, +A1 Socket, B1 Timer t is the resulting Time Delay (Red light-emitting diode) 5. Signal Off-delay Apply power (U) to timer. When the signal (S) is closed, the relay contacts (R) change state immediately. When the signal is opened, the time delay (t) begins. If the signal is closed before the time delay is complete, the time delay is reset and the relay remains energized. When the time delay is complete, the contacts return to their shelf state. Contacts return to their shelf state when power is removed.

7. Signal Off One-shot Apply power (U) to timer. When the signal (S) is closed and then opened, the relay contacts (R) change state immediately and the time delay (t) begins. After the time delay begins, opening or closing the signal will not reset the time delay. When the time delay is complete, the contacts return to their shelf state. Contacts return to their shelf state when power is removed.

6. Signal On One-shot Apply power (U) to timer. When the signal (S) is closed, the relay contacts (R) change state immediately and the time delay (t) begins. After the time delay begins, opening or closing the signal will not reset the time delay. When the time delay is complete, the contacts return to their shelf state. Contacts return to their shelf state when power is removed.

8. Signal On and Signal Off Watchdog Monitor Apply power (U) to timer. When the signal (S) is closed, the relay contacts (R) energize immediately and the time delay (t) begins. If the signal is opened before the time delay is complete, the relay remains energized and the time delay is reset. When the time delay is completed, the contacts return to their shelf state. If the signal is opened after the time delay is complete, the relay contacts energize immediately and the same time delay begins. Continuous cycling of the signal at a rate that is faster than the time delay causes the relay contacts to remain energized. Contacts return to their shelf state when power is removed.

18

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 19

General Purpose Relays

Dimensions -700-HA Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

54.1 (2-1/8)

32.8 (1-3/10)

36.5 (1-9/20)

700-HA Relay

6.2 (15/64)

50 (1-63/64)

5.2 (13/64)

12.5 (1/2)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

7.5 (0.3)

1000 (39-3/8)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No.

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lb) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lb) (5/pkg)

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

19

Page 20

General Purpose Relays

Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

24.6 (31/32)

40.1 (1-37/64)

20.8 (53/64) 30.0 (1-3/16) 26 (1-1/32)

24.9 (63/64)

65.0 (2-35/64)

54.9 (2-5/32) 51.1 (2-1/64)

4.2 (5/32) 38.0 (1-1/2) #4–40 M3

Cat. No. 700-HN100

33.0 (1-19/64)

Panel Mounting

14.7 (37/64)

Cat. No. 700-HN125

Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2-14 AWG… #2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)

Wire Size: 2 x 2.5 mm2 Single Wire – Up to 12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG…#2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)

26 (1-1/32)

30 (1-3/16)

65.0 (2-35/64)

38.0 (1-1/2) #4-40 M3

Cat. No. 700-HN101

Panel Mounting

Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG…#2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)

20

Cat. No. 700-HN126

Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG…#2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)

Rockwell Automation Publication 700-TD552B-EN-P - August 2018