The text of a spec sheet · part 14 of 25
Relay and Timer Specifications, Bulletin Number 700, pages 131 to 140
Pages 131 to 140 of 250
The original document is the PDF (23 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX
Page 131
General Purpose Electronic Timers and Counters
Description
Pkg. Qty. Cat. No.
Screw Terminal Tube Base Sockets, Panel or DIN Rail Mounting; Guarded Terminal Construction. 11-pin for use with 3PDT 700-HA relays.
10
700-HN101
Screw Terminal Tube Base Sockets, Panel or DIN Rail Mounting; Open Style Terminal Construction. 11-pin for use with 3PDT 700-HA relays. No retainer clip required.
10
700-HN126
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Retainer Clip for Cat. Nos. 700-HN100 and -HN101 Sockets with 700-HT Timing Relays(1)Secures relay in socket. Order must be for 10 clips or multiples of 10.
10
700-HN110
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N41
(1) Refer to 700-HT Timing Relay, Socket, and Retainer Clip Reference Chart.
130
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 132
General Purpose Electronic Timers and Counters
Specifications - 700-HT Cat. No. 700-HT…
Cat. No. 700-HTF…
Electrical Ratings
Pilot Duty Rating
(1)
NEMA B300
Rated Thermal Current (Ith)
10 A
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA
Contacts
Inductive
Make
Break
HP
Make
Break
HP
120V AC
30 A
3A
1/2 N.O. 1/3 N.C
30 A
3A
1/3
240V AC
15 A
1.5 A
1/2 N.O. 1/3 N.C
15 A
1.5 A
1/2
Resistive 28V DC
10 A
10 A, 10 A
10 A, 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC
Permissible Coil Voltage Variation
Power Consumption ±10%
AC
24V AC
2 VA
120V AC
4 VA
240V AC
4 VA
DC
1.3 W Design Specification/Test Requirements
Dielectric Withstand Voltage
Pole-to-Pole, same circuit (VRMS)
1000V AC
Pole-to-Pole, different circuits (VRMS)
2000V AC
Contact-to-Coil (VRMS)
2000V AC
Electrical Life Operations
100,000 minimum
Switching Frequency Operations
1800/hr
Coil Voltages
See product selection Mechanical
Degree of Protection
Open Type (Guarded Terminal Sockets)
Mechanical Life Operations
10 x 106
Switching Frequency Operations
18,000/hr
Timing
Duty Cycle
Continuous
Repeat Accuracy (constant voltage and temperature)
±2% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s)
Repeat Accuracy (variable voltage and temperature)
±10%, ±5% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s)
High End of Range
+5%, Low End of Range
-50%, Fixed Time Setting Accuracy Scale Tolerance
Reset Time
ON Delay
100 ms
OFF Delay
40 ms
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
131
Page 133
General Purpose Electronic Timers and Counters
Cat. No. 700-HT…
Cat. No. 700-HTF…
Environmental Operating
–28…+65 °C (50 °C max., 240V AC coil) (–18…+149 °F) (122 °F max., 240V AC coil)
Storage
–55…+85 °C (–67…+185 °F)
Temperature
Altitude
2000 m (6560 ft)
Construction Insulating Material
Molded High Dielectric Material
Enclosure
Impact Resistant Dust Cover
Contact Material Terminal Markings on Socket
Silver Cadmium Oxide In accordance with EN50 005 8- or 11-Pin Socket (On = 8, Off = 11) 700-HN100, -HN125 700-HN101, -HN126
Sockets
Certifications
CSA Certified, File 223833, UL Recognized, File E3125 Guide NLDX 2,UL Listed,whe used with 700-HN100, 700-HN101, 700-HN125, and 700-HN126 Sockets, File No. E3125 Guide NLDX, CE Marked
Standards
EN 61812-1, EN 60947-1,-5-1, CSA 22.2 No. 14, UL 508
(1) See NEMA Ratings and Test Values on page 5.
Trigger Signal Cat. Nos. 700-HT Contact closure provides signal to timer. A low energy signal is generated by the 700-HT timing relay. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Bul. 800F-X__V, 800T-X__V). No external voltage should be connected to the contact signal.
Timing Diagrams - 700-HT Relays
ON Delay
132
OFF Delay
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 134
General Purpose Electronic Timers and Counters
700-HV Timing Relay •Repeat Cycle Timing Relay •10 A Contact Rating •DPDT •Pin Style Terminals •0.1 s…30 min. •Repeat Cycle Adjustable Timing •Two Timing Adjustments T1 ≠ T2
Repeat Cycle Timing Relays with Pin Style Terminations with 2 Adjustments (T1 ≠ T2) Wiring Diagrams
Operating Mode
U.S./Canada
International
700-HN125 or 700-HN100
700-HN100
Repeat Cycle
700-HV Repeat Cycle Timing Relay DPDT 2-Pole, 2 Form C Contacts
700
– a
Socket
HV
3
2
A
A
A2 b c d e f g
Catalog Number Explanation - 700-HV Relays a Bulletin Number
700
- b Type of Relay
HV – Tube Base Repeat Cycle Timing Relay c Operating Mode
3 –Power ON Repeat Cycle, OFF Start (Repeat Cycle, OFF/ON Delay)
d Number of Poles
2 - 2PDT e Timing Range OFF Time f Timing Range ON Time g Coil Voltage
Code OFF Time, Type HV A – 0.1…10 s B – 1.0…100 s C – 0.1…10 min D – 1.0…100 min E –0.1…10 hr
Code ON Time, Type HV A 0.1…10 s B 1.0…100 s C 0.1…10 min D 1.0…100 min E 0.1…10 hr
U12 –12V DC U24 –24V AC/DC, 50/60 Hz U120 – 120V AC/DC, 50/60 Hz A2 –240V AC, 50/60 Hz
Socket and Retainer Clip Reference Relay Type 700-HV
Socket Cat. No.
Retainer Clip Cat. No.
700-HN100
700-HN110
700-HN125
Not Required(1)
(1) Design of these sockets holds the relays securely and does not require retainer clips.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
133
Page 135
General Purpose Electronic Timers and Counters
Accessories - 700-HV Relays Photo
134
Description
Pkg. Qty.
Cat. No.
Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with DPDT 700-HA Relays, -HX Digital Timing Relays, -HT (On-Delay) and HRM, -NRC and -HV (Repeat Cycle) Timing Relays. Order ten or multiples of ten
10
700-HN100
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Open Style Construction. 8Pin for use with DPDT 700-HA Relays, -HT (On-Delay) and -HRM, -HRC and -HV (Repeat Cycle) Timing 10 Relays. Order must be for 10 sockets or multiples of 10. No retainer clip required.
700-HN125
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N41
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 136
General Purpose Electronic Timers and Counters
Specifications - 700-HV Relays Cat. No. 700-HV… Electrical Ratings Pilot Duty Rating‡
NEMA B300
Rated Thermal Current (Ith)
10 A
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA Make
Break
Inductive Contacts
Hp
120V AC
30 A
3A
1/2 N.O. 1/3 N.C.
240V AC
15 A
1.5 A
1/2 N.O. 1/3 N.C.
Resistive 28V DC
10 A
10 A, 85…110 of Nominal Voltage at 50 Hz 85…110 of Nominal Voltage at 60 Hz 80…110 of Nominal Voltage at DC
Permissible Coil Voltage Variation
Power Consumption ±10%
AC
24V AC
2 VA
120V AC
4 VA
240V AC
4 VA
DC
1.3 W Design Specification/Test Requirements
Dielectric Withstand Voltage
Pole-to-Pole, same circuit (VRMS)
1000V AC
Pole-to-Pole, different circuits (VRMS)
2000V AC
Contact-to-Coil (VRMS)
2000V AC
Electrical Life Operations
100,000 minimum
Switching Frequency Operations
1800/hr
Coil Voltages
See product selection Mechanical
Degree of Protection
Open Type (Guarded Terminal Sockets)
Mechanical Life Operations
10 x 106
Switching Frequency Operations
18,000/hr
Timing
Duty Cycle
Continuous
Repeat Accuracy (constant voltage and temperature)
±2% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s)
Repeat Accuracy (variable voltage and temperature)
±10% High End of Range
+5%
Low End of Range
-50%
Scale Tolerance Reset Time
100 ms Environmental Operating
–28…+65 °C (50 °C max., 240V AC coil) (–18…+149 °F) (122 °F max., 240V AC coil)
Storage
–55…+85 °C (–67…+185 °F)
Temperature
Altitude
2000 m (6560 ft.)
Construction Insulating Material
Molded High Dielectric Material
Enclosure
Impact Resistant Dust Cover
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
135
Page 137
General Purpose Electronic Timers and Counters
Contact Material
Silver Cadmium Oxide
Terminal Markings on Socket
In accordance with EN50 005
Sockets
8-Pin Socket Cat. No. 700-HN100, -HN125
Certifications
CSA Certified, File 223833; UL Recognized, File E3125; Guide NLDX 2; cULus Listed when used with 700-HN100 and 700HN125 sockets; CE Marked
Standards
EN 61812; EN 60947-1, -5-1; CSA 22.2 No. 14; UL 508
Timing Diagram- 700-HV Relays
Dimensions - 700-HV Relays Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.
700-HV Timing Relay
Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes
Cat. No.
A
B
C
D
Approx. Shipping Wt.
199-DR1
35 (1-3/8)
27 (1-1/16)
7.5 (19/64)
1.02 (1/64)
1.85 kg (4.07 lbs.) (10/pkg)
199-DR4
35 (1-3/8)
27 (1-1/16)
15 (19/32)
2.3 (3/32)
3.68 kg (8 lbs.) (5/pkg)
136
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 138
General Purpose Electronic Timers and Counters
Cat. No. 700-HN100 Panel Mounting Double Wire - 2 x 2.5mm2 (#2-14 AWG…#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) - Torque: 0.8 N•m (7 ib•in)
Cat. No. 700-HN125 Wire Size: 2 x 2.5 mm2 Single Wire - Up to #12 AWG Double Wire - 2 x 2.5mm2 (#2-14 AWG…#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) - Torque: 0.8 N•m (7 ib•in)
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
137
Page 139
General Purpose Electronic Timers and Counters
700-HX Multi-Function Digital Timing Relay • Digital timing relay with LCD display • Socket- or panel-mounted (NEMA 4X/IP66) • 5A, B300, SPDT contact ratings • 10 Functions or modes • Environmentally friendly, flash memory, no battery Photo
Operating Mode
Timing Range
A mode: Signal ON-Delay 1 A-1 mode: Signal ON-Delay 2 A-2 mode: Power ON-Delay 1 A-3 mode: Power On-Delay 2 B mode: Repeat Cycle 1 B-1 mode: Repeat Cycle 2 D mode: Signal OFF-delay E mode: One Shot F mode: Cumulative Z mode: On/Off duty adjustable repeat cycle S mode:stop watch toff: Flicker OFF start 1 ton: Flicker ON start 1 toff-1: Flicker OFF start 2 ton-1: Flicker ON start 2
0.000…9.999 s 0.000…99.99 s 0.000…999.9 s 0.000…9999 s 0.000…99 min 59 s 0.000…999.9 min 0.000…9999 min 0.000…99 hr 59 min 0.000…999.9 hr 0.000…9999 hr
Socket Type
700-HN100 700-HN125
Contact Output
SPDT
No. of Pins
8
Input Voltage
Cat. No.
100…240V AC
700-HX86SA17
24V AC 12…24V DC
700-HX86SU24
Socket and Retainer Clip Reference Timer Type
700-HX
Socket Cat. No.
Retainer Clip Cat. No.
700-HN100
700-HN131
700-HN108
Not Required (1)
700-HN125
Not Required
(1) Design of socket holds the relay securely and does not require retainer clips.
Accessories - 700-HX Relays Photo
138
Description
Pkg. Quantity
Cat. No.
Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with 700-HX Timing Relays. Order ten or multiples of ten
10
700-HN100
Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Open Style Construction. 8-Pin for use with 700-HX Timing Relays. Order must be for 10 sockets or multiples of 10. No retainer clip required.
10
700-HN125
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 140
General Purpose Electronic Timers and Counters
Photo
Description
Pkg. Quantity
Cat. No.
Specialty Socket 8-pin backwired socket with solder terminals. For use with 700-HX Timing Relays.
10
700-HN108
Retainer Clip for Cat. Nos. 700-HN100 Sockets with all 700-HX Timing Relays Secures timer in socket.
10
700-HN131
Frame Adapter For flush or door mounting of all 700-HR and -HX timers.
1
700-HN130
Protective Cover Helps prevent tampering of timing and mode settings. Provides a degree of protection against water and dirt from entering the front of the relay. For use with all 700-HR and -HX timing relays.
1
700-HN132
Note: Not required for installation
Rockwell Automation Publication 700-TD552B-EN-P - August 2018