Page 131

General Purpose Electronic Timers and Counters

Description

Pkg. Qty. Cat. No.

Screw Terminal Tube Base Sockets, Panel or DIN Rail Mounting; Guarded Terminal Construction. 11-pin for use with 3PDT 700-HA relays.

10

700-HN101

Screw Terminal Tube Base Sockets, Panel or DIN Rail Mounting; Open Style Terminal Construction. 11-pin for use with 3PDT 700-HA relays. No retainer clip required.

10

700-HN126

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Retainer Clip for Cat. Nos. 700-HN100 and -HN101 Sockets with 700-HT Timing Relays(1)Secures relay in socket. Order must be for 10 clips or multiples of 10.

10

700-HN110

Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N40

Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N41

(1) Refer to 700-HT Timing Relay, Socket, and Retainer Clip Reference Chart.

130

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 132

General Purpose Electronic Timers and Counters

Specifications - 700-HT Cat. No. 700-HT…

Cat. No. 700-HTF…

Electrical Ratings

Pilot Duty Rating

(1)

NEMA B300

Rated Thermal Current (Ith)

10 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA

Contacts

Inductive

Make

Break

HP

Make

Break

HP

120V AC

30 A

3A

1/2 N.O. 1/3 N.C

30 A

3A

1/3

240V AC

15 A

1.5 A

1/2 N.O. 1/3 N.C

15 A

1.5 A

1/2

Resistive 28V DC

10 A

10 A, 10 A

10 A, 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC

Permissible Coil Voltage Variation

Power Consumption ±10%

AC

24V AC

2 VA

120V AC

4 VA

240V AC

4 VA

DC

1.3 W Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole-to-Pole, same circuit (VRMS)

1000V AC

Pole-to-Pole, different circuits (VRMS)

2000V AC

Contact-to-Coil (VRMS)

2000V AC

Electrical Life Operations

100,000 minimum

Switching Frequency Operations

1800/hr

Coil Voltages

See product selection Mechanical

Degree of Protection

Open Type (Guarded Terminal Sockets)

Mechanical Life Operations

10 x 106

Switching Frequency Operations

18,000/hr

Timing

Duty Cycle

Continuous

Repeat Accuracy (constant voltage and temperature)

±2% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s)

Repeat Accuracy (variable voltage and temperature)

±10%, ±5% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s)

High End of Range

+5%, Low End of Range

-50%, Fixed Time Setting Accuracy Scale Tolerance

Reset Time

ON Delay

100 ms

OFF Delay

40 ms

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

131

Page 133

General Purpose Electronic Timers and Counters

Cat. No. 700-HT…

Cat. No. 700-HTF…

Environmental Operating

–28…+65 °C (50 °C max., 240V AC coil) (–18…+149 °F) (122 °F max., 240V AC coil)

Storage

–55…+85 °C (–67…+185 °F)

Temperature

Altitude

2000 m (6560 ft)

Construction Insulating Material

Molded High Dielectric Material

Enclosure

Impact Resistant Dust Cover

Contact Material Terminal Markings on Socket

Silver Cadmium Oxide In accordance with EN50 005 8- or 11-Pin Socket (On = 8, Off = 11) 700-HN100, -HN125 700-HN101, -HN126

Sockets

Certifications

CSA Certified, File 223833, UL Recognized, File E3125 Guide NLDX 2,UL Listed,whe used with 700-HN100, 700-HN101, 700-HN125, and 700-HN126 Sockets, File No. E3125 Guide NLDX, CE Marked

Standards

EN 61812-1, EN 60947-1,-5-1, CSA 22.2 No. 14, UL 508

(1) See NEMA Ratings and Test Values on page 5.

Trigger Signal Cat. Nos. 700-HT Contact closure provides signal to timer. A low energy signal is generated by the 700-HT timing relay. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Bul. 800F-X__V, 800T-X__V). No external voltage should be connected to the contact signal.

Timing Diagrams - 700-HT Relays

ON Delay

132

OFF Delay

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 134

General Purpose Electronic Timers and Counters

700-HV Timing Relay •Repeat Cycle Timing Relay •10 A Contact Rating •DPDT •Pin Style Terminals •0.1 s…30 min. •Repeat Cycle Adjustable Timing •Two Timing Adjustments T1 ≠ T2

Repeat Cycle Timing Relays with Pin Style Terminations with 2 Adjustments (T1 ≠ T2) Wiring Diagrams

Operating Mode

U.S./Canada

International

700-HN125 or 700-HN100

700-HN100

Repeat Cycle

700-HV Repeat Cycle Timing Relay DPDT 2-Pole, 2 Form C Contacts

700

– a

Socket

HV

3

2

A

A

A2 b c d e f g

Catalog Number Explanation - 700-HV Relays a Bulletin Number

700

- b Type of Relay

HV – Tube Base Repeat Cycle Timing Relay c Operating Mode

3 –Power ON Repeat Cycle, OFF Start (Repeat Cycle, OFF/ON Delay)

d Number of Poles

2 - 2PDT e Timing Range OFF Time f Timing Range ON Time g Coil Voltage

Code OFF Time, Type HV A – 0.1…10 s B – 1.0…100 s C – 0.1…10 min D – 1.0…100 min E –0.1…10 hr

Code ON Time, Type HV A 0.1…10 s B 1.0…100 s C 0.1…10 min D 1.0…100 min E 0.1…10 hr

U12 –12V DC U24 –24V AC/DC, 50/60 Hz U120 – 120V AC/DC, 50/60 Hz A2 –240V AC, 50/60 Hz

Socket and Retainer Clip Reference Relay Type 700-HV

Socket Cat. No.

Retainer Clip Cat. No.

700-HN100

700-HN110

700-HN125

Not Required(1)

(1) Design of these sockets holds the relays securely and does not require retainer clips.

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

133

Page 135

General Purpose Electronic Timers and Counters

Accessories - 700-HV Relays Photo

134

Description

Pkg. Qty.

Cat. No.

Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with DPDT 700-HA Relays, -HX Digital Timing Relays, -HT (On-Delay) and HRM, -NRC and -HV (Repeat Cycle) Timing Relays. Order ten or multiples of ten

10

700-HN100

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Open Style Construction. 8Pin for use with DPDT 700-HA Relays, -HT (On-Delay) and -HRM, -HRC and -HV (Repeat Cycle) Timing 10 Relays. Order must be for 10 sockets or multiples of 10. No retainer clip required.

700-HN125

Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N40

Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N41

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 136

General Purpose Electronic Timers and Counters

Specifications - 700-HV Relays Cat. No. 700-HV… Electrical Ratings Pilot Duty Rating‡

NEMA B300

Rated Thermal Current (Ith)

10 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA Make

Break

Inductive Contacts

Hp

120V AC

30 A

3A

1/2 N.O. 1/3 N.C.

240V AC

15 A

1.5 A

1/2 N.O. 1/3 N.C.

Resistive 28V DC

10 A

10 A, 85…110 of Nominal Voltage at 50 Hz 85…110 of Nominal Voltage at 60 Hz 80…110 of Nominal Voltage at DC

Permissible Coil Voltage Variation

Power Consumption ±10%

AC

24V AC

2 VA

120V AC

4 VA

240V AC

4 VA

DC

1.3 W Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole-to-Pole, same circuit (VRMS)

1000V AC

Pole-to-Pole, different circuits (VRMS)

2000V AC

Contact-to-Coil (VRMS)

2000V AC

Electrical Life Operations

100,000 minimum

Switching Frequency Operations

1800/hr

Coil Voltages

See product selection Mechanical

Degree of Protection

Open Type (Guarded Terminal Sockets)

Mechanical Life Operations

10 x 106

Switching Frequency Operations

18,000/hr

Timing

Duty Cycle

Continuous

Repeat Accuracy (constant voltage and temperature)

±2% (Time Delay: 0.1…2 s) ±1% (Time Delay: >2 s)

Repeat Accuracy (variable voltage and temperature)

±10% High End of Range

+5%

Low End of Range

-50%

Scale Tolerance Reset Time

100 ms Environmental Operating

–28…+65 °C (50 °C max., 240V AC coil) (–18…+149 °F) (122 °F max., 240V AC coil)

Storage

–55…+85 °C (–67…+185 °F)

Temperature

Altitude

2000 m (6560 ft.)

Construction Insulating Material

Molded High Dielectric Material

Enclosure

Impact Resistant Dust Cover

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

135

Page 137

General Purpose Electronic Timers and Counters

Contact Material

Silver Cadmium Oxide

Terminal Markings on Socket

In accordance with EN50 005

Sockets

8-Pin Socket Cat. No. 700-HN100, -HN125

Certifications

CSA Certified, File 223833; UL Recognized, File E3125; Guide NLDX 2; cULus Listed when used with 700-HN100 and 700HN125 sockets; CE Marked

Standards

EN 61812; EN 60947-1, -5-1; CSA 22.2 No. 14; UL 508

Timing Diagram- 700-HV Relays

Dimensions - 700-HV Relays Approximate Dimensions are shown in millimeters (inches). Approximate Dimensions are not intended to be used for manufacturing purposes.

700-HV Timing Relay

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No.

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lbs.) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lbs.) (5/pkg)

136

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 138

General Purpose Electronic Timers and Counters

Cat. No. 700-HN100 Panel Mounting Double Wire - 2 x 2.5mm2 (#2-14 AWG…#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) - Torque: 0.8 N•m (7 ib•in)

Cat. No. 700-HN125 Wire Size: 2 x 2.5 mm2 Single Wire - Up to #12 AWG Double Wire - 2 x 2.5mm2 (#2-14 AWG…#2-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) - Torque: 0.8 N•m (7 ib•in)

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

137

Page 139

General Purpose Electronic Timers and Counters

700-HX Multi-Function Digital Timing Relay • Digital timing relay with LCD display • Socket- or panel-mounted (NEMA 4X/IP66) • 5A, B300, SPDT contact ratings • 10 Functions or modes • Environmentally friendly, flash memory, no battery Photo

Operating Mode

Timing Range

A mode: Signal ON-Delay 1 A-1 mode: Signal ON-Delay 2 A-2 mode: Power ON-Delay 1 A-3 mode: Power On-Delay 2 B mode: Repeat Cycle 1 B-1 mode: Repeat Cycle 2 D mode: Signal OFF-delay E mode: One Shot F mode: Cumulative Z mode: On/Off duty adjustable repeat cycle S mode:stop watch toff: Flicker OFF start 1 ton: Flicker ON start 1 toff-1: Flicker OFF start 2 ton-1: Flicker ON start 2

0.000…9.999 s 0.000…99.99 s 0.000…999.9 s 0.000…9999 s 0.000…99 min 59 s 0.000…999.9 min 0.000…9999 min 0.000…99 hr 59 min 0.000…999.9 hr 0.000…9999 hr

Socket Type

700-HN100 700-HN125

Contact Output

SPDT

No. of Pins

8

Input Voltage

Cat. No.

100…240V AC

700-HX86SA17

24V AC 12…24V DC

700-HX86SU24

Socket and Retainer Clip Reference Timer Type

700-HX

Socket Cat. No.

Retainer Clip Cat. No.

700-HN100

700-HN131

700-HN108

Not Required (1)

700-HN125

Not Required

(1) Design of socket holds the relay securely and does not require retainer clips.

Accessories - 700-HX Relays Photo

138

Description

Pkg. Quantity

Cat. No.

Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with 700-HX Timing Relays. Order ten or multiples of ten

10

700-HN100

Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Open Style Construction. 8-Pin for use with 700-HX Timing Relays. Order must be for 10 sockets or multiples of 10. No retainer clip required.

10

700-HN125

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 140

General Purpose Electronic Timers and Counters

Photo

Description

Pkg. Quantity

Cat. No.

Specialty Socket 8-pin backwired socket with solder terminals. For use with 700-HX Timing Relays.

10

700-HN108

Retainer Clip for Cat. Nos. 700-HN100 Sockets with all 700-HX Timing Relays Secures timer in socket.

10

700-HN131

Frame Adapter For flush or door mounting of all 700-HR and -HX timers.

1

700-HN130

Protective Cover Helps prevent tampering of timing and mode settings. Provides a degree of protection against water and dirt from entering the front of the relay. For use with all 700-HR and -HX timing relays.

1

700-HN132

Note: Not required for installation

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

139