The text of a spec sheet · part 17 of 25
Relay and Timer Specifications, Bulletin Number 700, pages 161 to 170
Pages 161 to 170 of 250
The original document is the PDF (23 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX
Page 161
NEMA Heavy-Duty Industrial Relays
Pneumatic Time-Delay Unit • Timing Range, 0.1…60 s • 0, 2, or 4 instantaneous contacts • Two timed contacts, both ON Delay or both OFF Delay • Convertible from ON Delay to OFF Delay and vice versa • Standard contact cartridges rated NEMA A600 (AC) and P600 (DC) • Master contact cartridges rated 2X NEMA A600 (AC) and N150 P600 (DC) No. of Timed Contacts (1) Photo
Operating Mode N.O.
Continuous Carrying Current [A]
Arrangement
Timing Range
N.C.
Cat. No.
10 On-Delay Off-Delay
1
Open Type Without Enclosure(2)
1
700-PT 0.1…60 s
20
700-PKT
(1) In addition to instantaneous cartridges on the relay (2) Mounts on 4-pole Bulletin 700-P or -PK relay or 2-pole Bulletin 700-PH relay.
Mechanical Latch Units Photo
Description
AC-Operated Latch Units
DC-Operated Latch Units
160
Arrangement
Continuous Carrying Current [A]
Cat. No.
No cartridge
700-PLL⊗
10
700-PLL11⊗
20
700-PKLL11⊗
No cartridge
700DC-PLL⊗
10
700DC-PLL10⊗
20
700DC-PKLL10⊗
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 162
NEMA Heavy-Duty Industrial Relays
Accessories Photo
Relays per Strip
Description
Pkg. Quantity
Cat. No.
4
5
700-MP4
8
5
700-MP8
12
5
700-MP12
16
5
700-MP16
DIN Rail Adapter Can be used with the following relays: Bulletin 700-P, 700DC-P, 700S-P, 700-N, 700-R, 700-RTC
1
700-DRA
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Type 1 Enclosure, Use for all Bulletin 700-P relays except 10- and 12-pole DC relays or 6-pole DC Bulletin 700-PH relays.
1
700-N31
Type 4/4X Enclosure, For 2- and 4-pole Bulletin 700-P, -N, and -R relays and 2-pole heavy duty relays.
1
700-N39
Type 7 & 9 Enclosure, For 2- and 4-pole Bulletin 700-P, -N, and -R relays and 2-pole heavy duty relays. 1 conduit hub; top and bottom.
1
700-N33
Relay Rail Simplifies panel layout. These indexed strips are easily cut to the required length and bolted, riveted, or spot-welded in place. Relays are installed adjacent to one another on the mounting strip with the captive mounting screws provided. Rows of relays on Relay Rail form their own wiring trough. Can be used with the following relays: 700P, 700DC-P, 700S-P, 700N, 700-R, 700-RTC
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
161
Page 163
NEMA Heavy-Duty Industrial Relays
Accessories Photo
Description
700-N5
Mounting on coil terminal
1
700-N24
24…48V AC/DC
1
199-FSMA9
50…120V AC/ DC
1
199-FSMA10
130…250V AC/ DC
1
199-FSMA11
Diode Surge Suppressor, for 6…300V DC voltage coils. Used on Bulletin 700-P, -PH, -PK, -N, -F, and -R relays.
1
199-FSMZ-1
35 A Jumper Kit – CSA Approved, UL Listed This 35 A Jumper Kit can be used with any Bulletin 700-P and -PK AC or DC relay, Time-Delay relay or Latch Unit equipped with 20 A Master Cartridges. It does not require any additional panel space. Jumper Kit terminals are designed for one #8 AWG wire or two #10 AWG wires. When connecting the two 20 A Master Cartridges in parallel, it is important that they be the same configuration (Normally Open or Normally Closed). Jumpers can be added to any contact cartridge location on a relay except the two center poles because of the wide spacing. An adhesive label is included with each kit listing the contact ratings.
1
700-CPH
Surge Suppressor When the circuit to a DC operating coil is opened, the inductive energy stored in the coil can generate very high transient voltages. With the addition of the appropriate surge suppressor, the stored energy is absorbed and dissipated limiting the voltage spikes. A surge suppressor is not required with AC 700-R or RM relays because the AC operating coil transients are suppressed by a full wave rectifier connected to the coil.
Cat. No. 700-N4
Jumpers (Not applicable for Bulletin 700-PH or -PK relays) – For connection between a middle pole and an outer pole on the left or right side of the relay.
Jumper – For outer poles
Jumpers (Not applicable for Bulletin 700-PH or -PK relays) – For connection between two middle poles.
Jumper – For middle poles
700-N4
Check Out Tool, Mechanically maintains the Bulletin 700-P, -PH, or -PK relay in the energized position for troubleshooting purposes.
700-N23
Adapter Plate, Simplified relay conversion. Allows you to use the existing mounting holes when you replace a Bulletin 700-B, -BR, -BX, or -D relay with a Bulletin 700-P, -PH, or -PK relay.
162
Cat. No.
Mounting behind 1 relay
Surge Suppressors (RC Circuit), Surge suppressors reduce the high transient voltages generated when the coil circuit is opened. These suppressors can be used with Bulletin 700-P, -PH, -PK, and -N relays, and other electromechanical devices. They contain a resistor and capacitor. Maximum ratings: 150V, AC or DC, 35 VA. Cat. No. 700-N5 requires 1 in. additional depth of enclosure.
Cat. No. 700-N3
Pkg. Quantity
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
700-N3 50
1 700-N34
Page 164
NEMA Heavy-Duty Industrial Relays
IP 2X Finger-Safe Cover Accessories Photo
Description
Pkg. Quantity
Cat. No.
IP2X Top Cover for 700-P
1
700-PFSC
Timer Top Cover Kit
1
700-PFSTC
Latch Top Cover Kit (for Relays with Mechanical Latch Attachment)
1
700-PFSLCK
Timer Top Cover Kit, (for Master Cont. Relays with Pneumatic Timer)
1
700-PFSKTC
Latch Top Cover Kit (for Master Cont. Relays with Mechanical Latch)
1
700-PFSKLCK
Top Covers (Covering Top Level Contact Screws)
Deck Covers (Covering all terminals not on top deck, only for multi-deck relays) IP2X Deck Cover for all AC & DC Relays in the 700P Range
1
700-PFSDEK
IP2X Coil Cover for all AC Relays in the 700P Range
1
700-PFSACC
IP2X Coil Cover for all DC Relays in the 700P Range
1
700-PFSDCC
Coil Covers
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
163
Page 165
NEMA Heavy-Duty Industrial Relays
Specifications - 700-P Relays Type
Standard Cartridge
Master Cartridge
Heavy duty
700-P
700-PMCKIT
700-PHDKIT
10 A @ 600V AC ; 5 A @ 600V DC
20 A @ 600V AC; 10 A @ 600V DC
35 A @ 600V AC; 20 A @ 600V DC
AC
NEMA A600
2 x NEMA A600
2 x NEMA A600
DC
NEMA P600
N150 P600
N150 P600
Additional Contact Ratings for AC single-phase loads, 3 Hp @ 240V AC - N.O. 2 Hp @ 240V AC - N.O./N.C. 1 Hp @ 120V AC - N.O./N.C. 20 A Resistive Heating to 600V AC 20 A Tungsten Lighting Load to 480V AC
5 Hp @ 240V AC - N.O. 3 Hp @ 240V AC - N.O./N.C. 2 Hp @ 120V AC - N.O./N.C. 35 A General Use At 0.75 PF to 600V AC 35 A Tungsten Lighting Load to 480V AC
DC Current Ratings Make/Break
Cartridge Cat. No. 700-CP1
Cartridge Cat. No. 700-CPM
Cartridge Cat. No. 700-CPH
Bulletin No.
Electrical Contact Rating Continuous Ratings Make/Break
Volts DC Contacts in Series DC Switching Inductive Load
Coil Voltage Range
Coil Consumption
AC DC
PLL - PKLL AC Latch Unit
24
64
125
250
500
600
64
125
250
500
600
480 W
480 W
275 W
138 W
135 W
120 W
10 A
5A
2.2 A
.55 A
.24 A
.2 A
10 A
5A
2.2 A
.55 A
.24 A
.2 A
20 A
10 A
5A
2A
.7 A
.5 A
20 A
10 A
5A
2A
.7 A
.5 A
1.0 A, 15 A
7A
3A
1.5 A
1.0 A, 15 A
7A
3A
1.5 A
1.0 A
1.5 A, 20 A
10 A
5A
2.5 A
1.5 A, 20 A
10 A
5A
2.5 A
1.5 A
24
64
125
250
500
600
24
1
5A
2.2 A
1.1 A
.55 A
.24 A
.2 A
2
10 A
10 A
5A
2A
.7 A
.5 A
3, - 7A
3A
1.5 A
4, - 10 A
5A
2.5 A
AC
85…110%
85…110%
DC
80…110%
80…110%
85…110% 80…110%
Battery
85…115%
85…115%
85…115%
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
Inrush
132VA (2)
138VA (2)
132VA (2)
138VA (2)
132VA (2)
138VA (2)
Sealed
19.3VA (2)
19VA (2)
19.3 VA (2)
19VA (2)
19.3VA (2)
12.7VA (2)
Inrush
12.7VA (2)
12.7VA (2)
Sealed
19VA (2) 12.7VA (2)
12.7VA (2)
12.7VA (2)
Inrush
15VA (2)
15.6VA (2)
5VA (2)
15.6VA (2)
15VA (2)
15.6VA (2)
Sealed
(2)
(2)
(2)
(2)
(2)
5.5VA (2)
5.4VA
5.5VA
5.4VA
5.5VA
5.4VA
PLL - PKLL DC Latch Unit
Unlatch
35VA (2)
35VA (2)
Intermittent
35 W (2)
35 W (2), - Reset Time
PT – PKT
75 ms
75 ms, Minimum Pulse
PLL–PKLL
75 ms
75 ms, Mechanical Operating Time
Pickup
AC – 10…20 ms / DC – 30…50 ms
AC – 10…20 ms / DC – 30…50 ms
AC – 10…20 ms / DC – 30…50 ms
Dropout
AC – 10…20 ms / DC – 20…33 ms
AC – 10…20 ms / DC – 20…33 ms
AC – 10…20 ms / DC – 20…33 ms
Mechanical Life
10 million operations Construction
Contact Arrangement
Up to 12 Poles, Convertible to N.O. or N.C. (8 N.C. Maximum)
Contact Material
Silver Nickel
Mounting
Up to 6 Poles, Convertible to N.O. or N.C. (4 N.C. Maximum)
Silver Cadmium Oxide
Silver Cadmium Oxide
Panel, Strip Mount, or DIN Rail Horizontal Mounting Recommended Environmental
Temperature
Operating (1)
–20…+65 °C (–4…149 °F)
–20…+65 °C (–4…149 °F)
–20…+65 °C (–4…149 °F)
Storage
–40…+65 °C (–40…149 °F)
–40…+65 °C (–40…149 °F)
–40…+65 °C (–40…149 °F)
Wire Terminations
Wire size per UL/CSA Tightening Torque Standards Compliance Certifications
#18 AWG…(2) #12 AWG 8…12 lb•in (0.9…1.4 N•m) UL 508, CSA C22.2, No. 14, EN/IEC 60947-1, -5-1 cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, ABS
(1) Temperature inside the panel. (2) Average value for all coils within range. For values on a specific coil voltage, contact your local Rockwell Automation sales office or Allen-Bradley distributor.
164
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 166
NEMA Heavy-Duty Industrial Relays
International Symbol for Mechanically Linked Contacts
Dimensions - 700-P Relays with standard, master contact, or heavy-duty contact cartridge Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 103.43 (4-5/64), 171.68 (6-49/64)
1/2
2.77 (7/64)
2.77 (7/64)
2- and 4-pole 700-P Relay Approx Shipping Weight: AC – 0.68 kg (1.5 lb), DC – 1.34 kg (2.95 lb)
2- and 4-pole 700-P with Pneumatic Time Delay Attachment Approx Shipping Weight: AC – 0.85 kg (1.88 lb), DC – 1.5 kg (3.33 lb)
AC 136.75 (5-25/64) 171.68 (6-49/64)
2.77 (7/64)
2.77 (7/64)
6- and 8-pole 700-P Relay with one -PB adder deck Approx Shipping Weight: AC – 0.79 kg (1.75 lb), DC – 1.45 kg (3.20 lb)
700-P Relay with Mechanical Latch Attachment Approx Shipping Weight: AC – 0.97 kg (2.13 lb), DC – 1.62 kg (3.58 lb)
AC 136.75 (5-25/64)
Cat. No. 700
#8 Screws (Captive)
2.77 (7/64)
700-P Relay, up to 12 poles with -PB and -PC adder decks Approx Shipping Weight: AC – 1.02 kg (2.25 lb), DC – 1.68 kg (3.7 lb)
Relay Rail for 700-P, -N, -NM, -R, -RM, -RT, -RTA Relays Secure the mounting strip with two screws at each end relay position. Use a minimum of one screw at the 3rd, 5th, 7th, etc., relay positions. Alternate between upper and lower horizontal slots.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
165
Page 167
NEMA Heavy-Duty Industrial Relays
178.60 (7-1/32)
AC – 170.49 (6-23/32) DC – 187 (7-25/64)
700-PS Timer
Cat. No. 700-N31, Type 1 Enclosure for 700-P, -RTC Relays Approximate Shipping Weight: 1.26 kg (2.8 lb)
5.2 (13/64)
6.2 (15/64)
50 (1-63/64)
12.5 (1/2)
700-PS Timer Mounted on a 700-P Relay Approximate Shipping Weight: AC – 0.68 kg (1.5 lb) without 700-PS, DC – 1.34 kg (2.9 lb) without 700-PS
1.0 (0.04) 3.98 (0.16)
35.0 (1.38)
1000 (39-3/8)
27.0 (1.06)
7.5 (0.3)
0.5 (.02)
2.25 (0.09) 0.5 (.02)
Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes
166
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
DIN Rail Adapter
Page 168
NEMA Heavy-Duty Industrial Relays
700S-P and 700S-PK, Heavy-Duty Safety Control Relays • Mechanically linked contacts meet IEC 947-5-1-L • 2…12 poles – all mechanically linked • Red cover for easy identification of safety circuits • Tamper resistant cover helps prevent changes which could jeopardize safety • IEC mechanically linked contacts symbol displayed on front • Visual indication of contact state • Ideal for use in safety circuits
700S-P (10 A) Safety Control Relays, AC and DC Coil Voltages Contacts
AC Coils
24V DC Coils
Open Type Panel Mount Relay Rail Mount
Open Type Panel Mount Relay Rail Mount
Open Type DIN Rail Mount
N.O.
N.C.
3
1
700S-P310
700S-DCP310Z24
700S-DCP310DZ24
2
2
700S-P220
700S-DCP220Z24
700S-DCP220DZ24
7
1
700S-P710
700S-DCP710Z24
700S-DCP710DZ24
6
2
700S-P620
700S-DCP620Z24
700S-DCP620DZ24
5
3
700S-P530
700S-DCP530Z24
700S-DCP530DZ24
4
4
700S-P440
700S-DCP440Z24
700S-DCP440DZ24
3
5
700S-P350
700S-DCP350Z24
700S-DCP350DZ24
10
2
700S-P1020
700S-DCP1020Z24
700S-DCP1020DZ24
Cat. No.
Cat. No.
Cat. No.
⊗ AC Coil Voltage Code(1) The Cat. No. as listed is incomplete. Select a coil voltage code from the table below to complete the Cat. No. Example: Cat. No. 700S-P310 becomes Cat. No. 700S-P310A1 for a 120V AC coil. [V]
24
115-120
230-240
460-480
60 Hz
A24
A1
A2
A4
IEC 947-5-1 Annex L has 2 requirements for a relay to meet for mechanically linked contacts: 1.) If a N.O. contact welds, all the N.C. contacts will remain open and meet a 2500V impulse test. 2.) If a N.C. contact welds, all the N.O. contacts will remain open and meet a 2500V impulse test. 700S-P and 700S-DCP relays meet these requirements including the 2500V impulse test. The relays shown on this page are shipped from the factory with the 700-CPS safety cartridge installed and cannot be converted to N.O. or N.C. in the Field.
(1) For other coil voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
167
Page 169
NEMA Heavy-Duty Industrial Relays
700S-PK (20 A) Safety Control Relays Contacts N.O.
N.C.
7 6 5 4 3 10 3 7 6 5 4 3 10 3
1 2 3 4 5 2 1 1 2 3 4 5 2 1
168
Coil Voltage
Cat. No.
110V AC 110V AC 110V AC 110V AC 110V AC 110V AC 110V AC 24V DC 24V DC 24V DC 24V DC 24V DC 24V DC 24V DC
700S-PK710A1 700S-PK620A1 700S-PK530A1 700S-PK440A1 700S-PK350A1 700S-PK1020A1 700S-PK310A1 700S-DCPK710Z24 700S-DCPK620Z24 700S-DCPK530Z24 700S-DCPK440Z24 700S-DCPK350Z24 700S-DCPK1020Z24 700S-DCPK310Z24
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 170
NEMA Heavy-Duty Industrial Relays
Specifications - 700S-P Relays Type
700S-P
Electrical 10 A @ 600V AC 5 A @ 600V DC
Contact Rating Continuous AC
NEMA A600
DC
NEMA P600
Ratings Make/ Break Minimum Contact Switching Ratings
10V, 50 mA Volts DC
Contacts in Series DC Switching Inductive Load
24V
64V
125V
250V
500V
600V
1
5A
2.2 A
1.1 A
0.55 A
0.24 A
0.2 A
2
10 A
10 A
5A
2A
0.7 A
0.5 A
3, - 7A
3A
1.5 A
1.0 A
4, - 10 A
5A
2.5 A
1.5 A
1.5 million operations at 10A break at 120V AC 14 million operations at 1A break at 120V AC 6 million operations at 1A break at 24V DC
Contact Electrical Life - Resistive Loads
Coil Voltage Range (1)
AC
85…110%
DC
80…110%
Battery Charging
85…115%
Coil Consumption
50 Hz
60 Hz
Inrush
132 VA
138 VA
Sealed
19.3 VA
19 VA
AC Inrush
12.7 W
Sealed
12.7 W
DC
Mechanical Mechanically Linked Contacts
All contacts are mechanically linked per IEC 947- 5-1 annex L for 2 to 12 poles Pickup
AC – 10…20 ms DC – 30…50 ms
Dropout
AC – 10…20 ms DC – 20…33 ms
Operating Time Mechanical Life
10 million operations
Construction 2…12 Poles, Double Break Contacts N.O. or N.C. (8 N.C. Maximum)
Contact Arrangement Contact Material/Design
Silver Nickel/Bifurcated
Mounting
Panel mount or mount on 700-MP Relay or DIN Rail Horizontal Mounting Recommended
Environmental Operating Temperature (2)
-20…+65 °C (-4…+149 °F)
Storage Temperature
-40…+65 °C (-40…+149 °F)
Wire Terminations Wire size per UL/CSA
#18 AWG…(2) #12 AWG
Tightening Torque
8…12 lb•in (0.9…1.4 N•m)
Standards Compliance
UL 508, CSA C22.2, No. 14, EN/IEC 60947-1, -5-1
Certifications cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, ABS
(1) Coil voltage required for proper operation (percent of rated coil voltage). (2) Temperature inside the panel.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
169