Page 151

NEMA Heavy-Duty Industrial Relays

Product Overview

Bulletin No.

700-R

700-RTC

Type

Sealed Switch

Solid-state Timing Relay

Features

• Hazardous location ratings • Long life in dirty environment • Timer and latch options • Switch 600V AC, 300V DC

• Timed and instantaneous contacts. • Sealed contacts for harsh environments and hazardous locations.

Contact Form

2...8 Poles, Contact Type

Sealed Switch, Contact Material

Sealed Switch, Electrical, Max. Current AC Resistive

5A, Min. load

1 mA, 5V, Coil Voltage

24...240V AC 24...250V DC, Coil Voltage Pickup

85...110% AC Coils 80...110% DC Coils, Dielectric Withstand

2640V, Electric Service Life (cycles)

1.5 million at 5 A 120V AC, Certifications

UL, CSA, CE, Sockets

Panel or rail mount, Control Outputs: Time Limit Instantaneous, Four output contacts

Timing Operation Modes:, On-Delay Off-Delay

Time Range, 0.05 s…64 min

Supply Voltage, 24V AC 110…120V AC 220…240V AC 24V DC 120V DC 240V DC

Product Selection

176

181

Reference

Timing Relay Information

150

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 152

NEMA Heavy-Duty Industrial Relays

700-P Industrial Relays 700-P, Direct Drive™ Convertible Contact Cartridge Relays • NEMA and IEC ratings • 600V maximum AC/DC • Accessories for field installation: contact cartridges, adder decks, time delay, latching, surge suppressors, mounting strip • Contact Ratings: (10 A) 700-CP1, (20 A) 700-CPM, (35 A) 700-CPH, (Low Power) 700-CPR • For machine tool and other heavy-duty applications • Can accommodate ring tongue terminals • Integral DIN Rail mount on AC relays • Finger-safe protection standard • Factory supplied standard at 120V AC and 24V DC - user configurable for field assembly • Blank relays are available in all coil voltages for field custom configuration • Contact cartridge is convertible from N.O. to N.C. by simply turning cartridge over. The 700/700DC-P family of Direct Drive Industrial Relays offers switching solutions ranging from 200 mA in Low Energy Circuits to 35 A in Heavy Duty Circuits. All of the contacts can easily be changed from the standard N.O. to N.C. configuration. The relays can be accessorized to meet the application needs with the use of time delayed contacts, mechanical latches and NEMA enclosures. All devices are available in the most popular AC and DC control voltages. Combining different cartridges into one relay can yield a custom-tailored application solution. Relays are available without contact cartridges in all of the available AC and DC coil voltages for maximum flexibility. 700/700DC-P relays use standard (10 A) contact cartridges with a double-break and bifurcated design. Bifurcation provides excellent contact reliability and low-contact bounce, while the double-break contact design reduces the possibility of contacts welding and enhances the relay’s ability to break DC circuits. These relays can be configured with a maximum of 12 contacts (only 8 may be N.C.).

A Modular Approach to Control Circuit Solutions The 700-P AC control relay is factory assembled with a standard 10 A contact cartridges with all contacts as N.O.in either 2, 4, 8, or 12 pole configurations with a 120 volt operating coil. Four pole relays are also available at 240 and 480 VAC and can have up to eight contacts added by using adder decks. The 700DC-P control relay is factory assembled with a standard 10 A contact cartridges with all contacts as N.O. in either 4 or 8 poles with a 24 volt operating coil. The 4 pole is also available with a 120 VDC operating coil. For control relays that require different contact ratings or control voltages we offer a modular design that are easily field configurable. A base blank relay (either AC or DC control), a variety of contact kits, adder decks, and operating coils can be used to make an infinite number of custom control relay solutions. • Master Control 700-PMCKIT master control cartridges provide (20 A) switching capability with large single-contact pads on each side of the spanner for twice the current rating to control heavy loads and provide for master control of a system. The cartridge also has the same double-break design as the standard 700-P relay contact cartridge. Relays can be configured with up to a maximum of 12 contacts (only 8 may be N.C.). Time delay and latching attachments are compatible with master cartridges. • Heavy Duty Control 700-PHDKIT contact cartridges provide (35 A) switching capability through tandem contact cartridges. A jumper allows two (20 A) master contact cartridges to be connected in parallel. A maximum of six poles can be configured in a relay, only four of which can be normally closed. Time delay and latch attachments are available. • Low Energy Control Logic Reed 700-PLRKIT contact cartridges provide switching to 200 mA @ 30 VDC. These contacts are matched with standard control (10 A) contact cartridges for low energy switching applications. • Overlapping Contact 700-POLKIT contact cartridges provide (10 A) switching capabilities with the same rating as the standard contact. These cartridge used in pairs operate with the N.O. contact closing before the N.C. contact opens on pick-up and vice versa on the dropout.

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

151

Page 153

NEMA Heavy-Duty Industrial Relays

AC-Operated Relays - In-stock Contact Configurations Contacts Photo N.O.

Open Type, DIN Rail, or Relay Rail Mount (700-MP)

Contact Arrangement and Markings

(1)

120V AC

240V AC

480V AC

0

4-Pole Relay

700-P000A1, - 2

4-Pole Relay

700-P200A1, - 4

4-Pole Relay

700-P400A1

700-P400A2

700-P400A4

8

8-Pole Relay

700-P800A1, - 12

12-Pole Relay

700-P1200A1, - (1) Factory assembled N.O. contacts can be easily to N.C. in the field.

DC-Operated Relays - In-stock Contact Configurations Open Type Relay Rail Mount (2)

Contacts Photo

Contact Arrangement and Markings

N.O. (1)

120V DC

Cat. No.

Cat. No.

0

4-Pole Relay

700DC-P000Z24, 4

4-Pole Relay

700DC-P400Z24

700DC-P400Z1

700DC-P800Z24, 8

8-Pole Relay

(1) Factory assembled N.O. contacts can be easily to N.C. in the field. (2) For DIN Rail mounting, order Cat. No. 700-DRA.

152

24V DC

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 154

NEMA Heavy-Duty Industrial Relays

Base Blank Relay - Factory Assembled Photo

Type of Control Circuit

Cat. No.

AC

700-P000⊗

DC

700DC-P000⊗

⊗ AC Coil Voltage Code Hz

24

110

115-120

200-208

230-240

277

460-480

575-600

50, A1, - - - - - 60

A24, A1

A20

A2

A27

A4

A6

⊗ DC Coil Voltage Code 24

48

72

115-125

230-250

575-600

Z24

Z48

Z72

Z1

Z2

Z6

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

153

Page 155

NEMA Heavy-Duty Industrial Relays

Master (20 A) and Heavy Duty (35 A) Contact Cartridge Options Follow this process to order a relay that utilizes: 20 A master contact cartridges or 35 A heavy duty contact cartridges.

Base Blank Relay

+

Cartridge Kit

+

Base Blank Relay

Adder Decks

+

Coil

Type of Control Circuit

Cat. No.

AC

700-P000A1

DC

700DC-P000Z24

+ Contact Cartridge Kits Photo

Description

Contents

Continuous Carrying Current [A]

Cat. No.

Master Contact Cartridge AC Rating Twice NEMA A600 DC Rating NEMA N150 P600

4 Master Cartridges (Cat. No. 700-CPM)

20

700-PMCKIT

Heavy Duty Contact Kit

4 Master Cartridges and two sets of jumper terminals, rating label (makes two 35 A poles)

35

700-PHDKIT

+ Adder Decks Do you have more than four circuits or more than two 35 A circuits in the relay?

EXAMPLE

154

Adder Decks Required Cat. No.

Additional Cartridge Kits Required

8 Pole Device

700-PB00

1 additional kit

12 Pole Device

700-PB00 700-PC00 (Qty 1 of each)

2 additional kits

Heavy Duty circuit (35 A) application that requires 4 circuits and 240 AC control circuit: • • • •

IMPORTANT

Device Description

Base Unit: Cat. No. 700-P000A1 Cartridge Kits: Cat. No. 700-PHDKIT - Qty 2 (Each kit makes two circuits) Adder Deck: Cat. No. 700-PB00 Coil: Cat. No. PA254

If required, see Operating Coils for coil selection.

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 156

NEMA Heavy-Duty Industrial Relays

Logic Reed and Overlapping Contact Cartridge Option Follow this process to order a relay that utilizes: low energy contact cartridges or overlapping late make or late break cartridges.

Base Blank Relay

+

Cartridge Kit

+

Base Blank Relay

Adder Decks

+

Coil

Type of Control Circuit

Cat. No.

AC

700-P000A1

DC

700DC-P000Z24

+ Contact Cartridge Kits Photo

Continuous Carrying Current [A]

Description

Contents

Logic Reed Cartridge for Low Energy Circuits 150V AC 500 mA 25 VA Max. 30V DC 200 mA 6W Max.

2 Logic Reed Cartridges (Cat. No. 700-CPR)

500 mA 150V AC 200 mA 30V DC

2 Standard Cartridges (Cat. No. 700-CP1)

10

4 Overlapping Cartridges (Cat. No. 700-CP11Z)

10

Overlap Contact Cartridges Overlapping Used in pairs. N.O. contact closes before N.C. contact opens on pick-up and vice versa on drop-out.

Cat. No.

700-PLRKIT

700-POLKIT

+ Adder Decks Do you have more than four circuits or more than two 35 A circuits in the relay?

EXAMPLE

Adder Decks Required Cat. No.

Additional Cartridge Kits Required

8 Pole Device

700-PB00

1 additional kit

12 Pole Device

700-PB00 700-PC00 (Qty 1 of each)

2 additional kits

Logic Reed and Overlapping Contact Cartridge Option: • • • •

IMPORTANT

Device Description

Low Voltage Circuit 24V DC less than 200 mA Base Unit: Cat. No. 700-P000A1 Cartridge Kits: Cat. No. 700-PLRKIT - Qty 1 Coil: Cat. No. PA254

If required, see Operating Coils for coil selection.

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

155

Page 157

NEMA Heavy-Duty Industrial Relays

Accessories - 700-P Relays Adder Decks Photo

156

Description

No. of N.O. Contacts

Continuous Carrying Current [A]

Second Deck (0-pole)

0, 700-PB00

Second Deck (4-pole)

4

10

700-PB40

Third Deck (0-pole)

0

0

700-PC00

Third Deck (4-pole)

4

10

700-PC40

Arrangement

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Cat. No.

Page 158

NEMA Heavy-Duty Industrial Relays

Operating Coils Bulletin 700-P Relays, Bulletin 700-PLL-PKLL Mechanical Latch Attachments Bulletin 700-P, 2…12-pole, AC control

24

PA013

PA407

PL013

PL407

PM714

PD714

48, - - - PM724

PD724

60 Hz

72

110…115 Bulletin 700-P Operating Coil

Bulletin 700-PL Unlatch Coil and Magnet Assembly

50 Hz

60 Hz

50 Hz

DC, - - - - PM730

PD730

(3), PA236, PL236, PD733 (100…110)

115…120(3)

PA236, PL236, - - - PA322, PL322, - 115…125, - - - PM735

120§

PA322, PL322, - - 130…140, - - - - PD738

200…208

PA249, PL249, - - 220…230

PA251

PA339, PL339, - 230…240

PA254

PA342

PL254

PL342, - 230…250, - - - PM748

PD748

277

PA260, - - - - 380, PA354, PL354

PL354, 415, PA357, PL357

PL357, 440…460, PA360, PL360

PL360, 460…480

PA273, PL273, - - 500, PA364, PL364

PL364, 575…600

PA278, PL278, - PD758

110

(1)

Bulletin 700-PLL–PKLL AC Mechanical Latch Attachment

Bulletin 700DC-P 2…12-pole, DC control

Coil Volts(2)

PD735

(1) This coil is optimized for 110…115V, 50 Hz applications and will operate satisfactorily at 120V, 60 Hz. (2) Coils for AC relays cannot be used in DC relays and vice versa. (3) This coil is optimized for 115…120V, 60 Hz applications and will operate satisfactorily at 110V, 50 Hz.

⊗ AC Coil Voltage Code The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700-PLL⊗ becomes Cat. No. 700-PLLA1. Hz

24

110

50

B24

A1

60

A24, (1)

110-115 B11, (2)

115-120

120

200-208

220-230

230-240

277

347

380

415

440-480

460-480

500

575-600, - - B22

B2, - B3

B41

B44, B50, A1 (1)

B11(2)

A20

A22

A2

A27

A35, - - A4, A6

(1) Optimized for 115…120V, 60 Hz. Operates satisfactorily at 110V, 50 Hz. (2) Optimized for 110…115V, 50 Hz. Operates satisfactorily at 120V, 60 Hz.

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

157

Page 159

NEMA Heavy-Duty Industrial Relays

⊗ DC Coil Voltage Code The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700DC-PLL⊗ becomes Cat. No. 700DC-PLLZ24. 24

48

64

72

115-125

230-250

575-600

Z24

Z48

Z64

Z72

Z1

Z2

Z6

Contact Cartridges (Convertible from N.O. to N.C. and N.C. to N.O.) Photo

Description

Continuous Carrying Current [A]

Standard Contact Cartridge AC Rating NEMA A600 DC Rating NEMA P600

10

Overlap Contact Cartridges Overlapping Used in pairs. N.O. contact closes before N.C. contact opens on pickup and vice versa on drop-out. (1)

Pkg. Quantity

Cat. No.

1

700-CP1

DC Rating NEMA P150 125V DC, 138 VA 5 Make and Break

2

700-CP11Z

20

1

700-CPM

1

700-CPR

AC Rating NEMA A600

Master Contact Cartridge AC Rating Twice NEMA A600 DC Rating NEMA N150 P600

Logic Reed Cartridge for Low Energy Circuits 150V AC 500 mA 25 VA Max. 30V DC 200 mA 6W Max. (2)

Arrangement

10

Maximum 150V AC

500 mA

Maximum 30V DC

200 mA

(1) Not Direct Drive (2) The 700-CPR Logic Reed cartridge must be installed only in the 2nd deck (B1X - B4X, B1Y - B4Y position) or 3rd deck (C1X - C4X, C1Y - C4Y position) of the Bulletin 700 Type P relay. It is not recommended that the 700-CPR cartridge be installed in the single deck (A1X - A4X, A1Y - A4Y position) because this may lead to improper operation.

158

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 160

NEMA Heavy-Duty Industrial Relays

Electrically Held Relays, Typical Wiring Diagrams

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

159