The text of a spec sheet · part 19 of 25
Relay and Timer Specifications, Bulletin Number 700, pages 181 to 190
Pages 181 to 190 of 250
The original document is the PDF (23 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX
Page 181
NEMA Heavy-Duty Industrial Relays
Dimensions - 700-R Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 700-R Relays Type of Relay
No. of Poles
Open Type Without Enclosures
A Wide
B High
C Deep
D
E
B High
C Deep
D
2…4
1
55.56 (2-3/ 16)
88.90 (3-1/2)
92.25 (3-3/8)
79.38 (3-1/8)
0.91 (2)
104.78 (4-1/8)
185.74 (7-5/ 16)
103.19 (4-1/ 16)
146.05 (5-3/4)
85.73 (3-3/8)
1.81 (4)
5…8
2
55.56 (2-3/ 16)
88.90 (3-1/2)
111.13 (4-3/8)
79.38 (3-1/8)
1.02 (2-1/4)
112.71 (4-7/ 16)
228.60 (9)
120.65 (4-3/4)
206.38 (8-1/8)
92.08 (3-5/8)
2.49 (5)
C
B
A
B
D
700-R400…
D
700-R800…
160.6 max (6-21/64)
A
C 3.98 (0.16)
700 Type R
700-PS Timer
B
D
0.5 (.02)
2.25 (0.09)
E
700-N26
0.5 (.02)
Type 1 Enclosure
DIN Rail Adapter
Cat. No. 700
Secure the mounting strip with 2 screws at each end relay position. Use a minimum of one screw at the 3rd, 5th, 7th, etc., relay positions. Alternate between upper and lower horizontal slots. #8 Screws (Captive)
Relay Rail 5.2 (13/64)
6.2 (15/64)
50 (1-63/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38)
1000 (39-3/8)
7.5 (0.3)
Cat. No. 199-DR1 DIN Mounting Rail Series B
180
Approx . Ship Wt. [kg (lb)]
A Wide
A
C
Type 1 General Purpose Enclosure
Drawing Number
700 and 700DC
R
Approx . Ship Wt. [kg (lb)]
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
27.0 (1.06)
Page 182
NEMA Heavy-Duty Industrial Relays
700-RTC, Solid-State Timing Relay • • • • • • • • • • • • •
Timing functions 8 ON-delay 8 OFF-delay Timing ranges Seconds: 0.05…2, 0.2…8, 0.4…30, 2…120 Minutes: 0.015…1, 0.06…4, 0.25…16 and 1…64 AC, 50/60 Hz or DC 600V AC maximum 300V DC maximum Relays with fixed time delay Sealed contacts Harsh environments Hazardous locations Class I, Div. 2, Groups A, B, C and D
700-RTC Relay with Adjustable Time Delay – Relays with Provision for Instantaneous Contacts Relays listed below have slots for two timed contacts and two instantaneous contacts. Unused slots are equipped with removable dummy cartridges. Number of Contact Cartridges Total 0 1
2
3
Open Type Without Enclosure
Instantaneous
Timed
Cat. No.
N.O.
N.C.
N.O.
N.C.
0
0
0
0
700-RTC00000⊗
0 0 0 1 0 0 1 0 0 1 2 0 1 1 2 0 0 1 1 0 0
0 0 0 0 1 0 0 1 0 0 0 1 1 0 0 2 1 1 0 2 1
1 0 2 1 1 1 0 0 0 2 1 2 1 1 0 1 1 0 0 0 0
0 1 0 0 0 1 1 1 2 0 0 0 0 1 1 0 1 1 2 1 2
700-RTC00100⊗ 700-RTC00010⊗ 700-RTC00200⊗ 700-RTC10100⊗ 700-RTC01100⊗ 700-RTC00110⊗ 700-RTC10010⊗ 700-RTC01010⊗ 700-RTC00020⊗ 700-RTC10200⊗ 700-RTC20100⊗ 700-RTC01200⊗ 700-RTC11100⊗ 700-RTC10110⊗ 700-RTC20010⊗ 700-RTC02100⊗ 700-RTC01110⊗ 700-RTC11010⊗ 700-RTC10020⊗ 700-RTC02010⊗ 700-RTC01020⊗
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
181
Page 183
NEMA Heavy-Duty Industrial Relays
Number of Contact Cartridges
Open Type Without Enclosure
Instantaneous
Total
4
Timed
N.O.
N.C.
N.O.
N.C.
2 1 2 0 1 2 1 0 0
0 1 0 2 1 0 1 2 2
2 2 1 2 1 0 0 1 0
0 0 1 0 1 2 2 1 2
Cat. No. 700-RTC20200⊗ 700-RTC11200⊗ 700-RTC20110⊗ 700-RTC02200⊗ 700-RTC11110⊗ 700-RTC20020⊗ 700-RTC11020⊗ 700-RTC02110⊗ 700-RTC02020⊗
⊗ Coil Voltage Code The Cat. No. as listed is not complete. Select a voltage code from the table below to complete the Cat. No. Example: Cat. No. 700-RTC00100⊗ becomes Cat. No. 700-RTC00100U24. For other voltages consult your local Rockwell Automation sales office or Allen-Bradley distributor. [V]
24V DC, 24V AC
120V DC, 110/120V AC
50/60 Hz
U24
U1
700-RTC Relays with Fixed Time Delay - Relays with Provision for Instantaneous Contacts Relays listed below have slots for two timed and two instantaneous contacts. Unused slots are equipped with removable dummy cartridges. Number of Contact Cartridges Total 0 1
2
3
182
Timed
Open Type Without Enclosure Instantaneous
N.O.
N.C.
N.O.
N.C.
0 1 0 2 1 1 1 0 0 0 2 1 2 1 1 0 1 1 0 0 0 0
0 0 1 0 0 0 1 1 1 2 0 0 0 0 1 1 0 1 1 2 1 2
0 0 0 0 1 0 0 1 0 0 1 2 0 1 1 2 0 0 1 1 0 0
0 0 0 0 0 1 0 0 1 0 0 0 1 1 0 0 2 1 1 0 2 1
Cat. No. 700-RTC00#0⊗ 700-RTC10#0⊗ 700-RTC20#0⊗ 700-RTC40#0⊗ 700-RTC11#0⊗ 700-RTC12#0⊗ 700-RTC30#0⊗ 700-RTC21#0⊗ 700-RTC22#0⊗ 700-RTC50#0⊗ 700-RTC41#0⊗ 700-RTC14#0⊗ 700-RTC42#0⊗ 700-RTC13#0⊗ 700-RTC31#0⊗ 700-RTC24#0⊗ 700-RTC15#0⊗ 700-RTC32#0⊗ 700-RTC23#0⊗ 700-RTC51#0⊗ 700-RTC25#0⊗ 700-RTC52#0⊗
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 184
NEMA Heavy-Duty Industrial Relays
Number of Contact Cartridges
Open Type Without Enclosure
Timed
Total
4
Instantaneous
N.O.
N.C.
N.O.
N.C.
2 2 1 2 1 0 1 0 0
0 0 1 0 1 2 1 2 2
2 1 2 0 1 2 0 1 0
0 1 0 2 1 0 2 1 2
Cat. No. 700-RTC44#0⊗ 700-RTC43#0⊗ 700-RTC34#0⊗ 700-RTC45#0⊗ 700-RTC33#0⊗ 700-RTC54#0⊗ 700-RTC35#0⊗ 700-RTC53#0⊗ 700-RTC55#0⊗
# Operating Mode Replace the # in the cat. no. with the appropriate letter and numbers to indicate the operating mode and the fixed time delay value. Refer to operating mode table below. Digit
Operating Mode
Fixed Time Delay
S
On-Delay – s
Z
Off-Delay – s
Seconds –Two digits indicating the fixed time delay in seconds. Three digits indicating the fixed time delay (first digit indicates seconds, next two digits indicate 1/100 seconds).
Y
On-Delay – Min.
I
Off-Delay – Min.
EXAMPLE
Minutes –Two digits indicating the fixed time delay in minutes. Three digits indicating the fixed time delay (first digit indicates minutes, next two digits indicate 1/100 minutes).
Cat. No. 700-RTC00Y200U1 is for a relay without contact cartridges. “Y20” indicates an On-Delay timer with a 20 minute fixed time delay. This is a “standard relay.” Order the contact cartridges separately. Cat. No. 700-RTC42S020U1 is for a relay with 2 N.O. cartridges in the timed position and 1 N.C. cartridge in the instantaneous position. “S02” indicates an On-Delay timer with a 2 second fixed time delay.
⊗ Coil Voltage Code The cat. no. as listed is not complete. To complete the cat. no., add a coil code selected from the table below. [V]
24V DC, 24V AC
120V DC, 110/120V AC
50/60 Hz
U24
U1
Accessories - 700-RTC Relays Description
Photo
Contact Cartridges – These cartridges are used to add contacts to timing relays having unused slots. The N.O., N.C., and Dummy cartridges are interchangeable and can be used in timed or instantaneous contact slots. Dummy cartridges should be placed in unused cartridge slots to guard against entrance of foreign material. Cat. No. 700-CRT5
Cat. No. 700-CRT6
Cat. No. 700-CR9
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Cartridge Type
Color
Cat. No.
N.O.
Grey
700-CRT5
N.C.
Orange
700-CRT6
Dummy Cartridge
Black
700-CR9
183
Page 185
NEMA Heavy-Duty Industrial Relays
Description
Photo
Cartridge Type
Cat. No.
Color
Type 1 Enclosure, Use for all 700-P relays except 10- and 12-pole DC relays or 6-pole DC 700-PH relays.
700-N31
Relays per Strip
Pkg. Quantity
4
5
8
5
700-MP8
12
5
700-MP12
16
5
700-MP16
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
DIN Rail Adapter Can be used with the following relays: 700-P, 700DC-P, 700S-P, 700-N, 700-R, 700-RTC
1
700-DRA
Relay Rail Simplifies panel layout. These indexed strips are easily cut to the required length and bolted, riveted, or spot-welded in place. Relays are installed adjacent to one another on the mounting strip with the captive mounting screws provided. Rows of relays on Relay Rail form their own wiring trough. Can be used with the following relays: 700P, 700DC-P, 700S-P, 700N, 700-R, 700-RTC
700-MP4
Specifications - 700-RTC Relays Voltage and Power Requirements
184
AC Voltage +10% –15% 50/60 Hz
Total Power Required
Initiate Terminal Power
Maximum Allowable Leakage Current
Coil Code
24V AC
8 VA
4 VA
10 mA
U24
110/120V AC
9 VA
4 VA
2.4 mA
U1
DC Voltage +10% –20%
Total Power Required
Initiate Terminal Power
Maximum Allowable Leakage Current
24V DC
10 W
5W
10 mA
U24
120V DC
11 W
5W
2.4 mA
U1
Coil Code
Type
700-RTC
Contact Rating
NEMA B600 600V AC, 5 A NEMA P300 300V DC, 5 A
Contact Arrangement
1…4 poles. Max. of 2 timed and 2 instantaneous. Available in any combination of N.O. and N.C. contacts
Contact Material
W (tungsten in a controlled gas atmosphere)
Operating Mode
Convertible to ON-Delay or OFF-Delay
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 186
NEMA Heavy-Duty Industrial Relays
Type
700-RTC
Timing Range
0.015…64 minutes; 0.05...120 seconds
Reset Time
25 ms
Repeat Accuracy
±1% (or ±50 ms) at constant voltage and temperature
Mounting
Panel or strip mount
Surge Suppression
Not required. Timers have internal suppression
Haz. Loc. Ratings
Class I, Division 2, Groups A, B, C, and D
Maximum Allowable Leakage Current
24V AC/DC
10 mA
110/120V AC, 120V DC
2.4 mA
Ambient Temperature (1) Operating:
–20…+60 °C (–4…+140 °F)
Storage:
–20…+60 °C (–4…+140 °F)
Standards Compliance
ISA 12.12, CSA C22.2, No. 213
Certifications cULus Listed (File No. E10314, Guide NOIV/NOIV7)
(1) Continuous duty units placed close to each other (3 in a row) have a temperature range of –20…+45 °C (–4…+113 °F) or should have air circulated around the units. Approximate space of 3/4 in (mm) on all sides is needed.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
185
Page 187
NEMA Heavy-Duty Industrial Relays
Typical Wiring Diagram - 700-RTC Relays L1 External Initiating Contact (N.O. or N.C.) Timed Contacts Any Combination of N.O. and N.C.
Instantaneous Contacts Any Combination of N.O. and N.C.
L2
P TIMED
L1 +
INST
L2
Dimensions - 700-RTC Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
5.2 (2-13/64) Dia. Mounting Holes
Approximate Shipping Weight 0.92 kg (2.1 lb.)
186
NEMA Type 1 Enclosure for RTC Relays Approximate Shipping Weight 1.26 kg (2.8 lb.)
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 188
IEC Industrial Relays
IEC Control Relays Product Overview
Bulletin No.
700-CF and 700S-CF
700-K
Type
Control Relay
Miniature Control Relay
Features
• Mechanically linked contacts • Timer and latch operations • Switch up to 690V AC and DC • 700S-CF for safety circuits
• Smallest size • Long life • Low power consumption • Switch up to 690V AC and DC
Contact Form
4…12 poles, double break
4...8 Poles Double Break
Contact Type
Cross stamp or bifurcated
Bifurcated
Contact Material
Silver, gold
Silver
Max. Current AC Resistive
20 A (relay) 10 A (adder deck)
10 A
Min. load
17V, 10 mA (Silver) 5V, 3 mA (Gold)
15V, 2 mA (700-K)
Coil Voltage
12…600V AC 9…250V DC
12…600V AC 9…250V DC
Coil Voltage Pickup
85…110% AC coils, 80…110% DC coils
85…110% AC Coils, 80…110% DC Coils
Dielectric Withstand
2.5 kV
2640V
Electric Service Life (cycles)
1.2 million at 10 A
800K at 10 A 120V AC
Certifications
CE, cULus, CCC
CE, cULus, CCC
Sockets
DIN Rail or panel mount
DIN Rail or panel mount
Page
188
212
Electrical
Reference
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
187
Page 189
IEC Industrial Relays
700-CF Control Relay • IEC industrial relays • Mechanically linked contact performance per IEC 60947-5-1 • Gold plated, bifurcated version for low level switching applications • Master control relay version rated 15 A (AC-15) • Solid-state and pneumatic timing modules • 4-…10 Poles
4-Pole AC Coil Voltage (Ratings for 700-CF Only) AC-12
AC-15
Ith [A] 40 °C
20
Contacts
Ie [A] 60 °C
24/48V
20
Gold Plated Bifurcated Contacts(2)
Master Contacts(2)
N.O. N.C. Cat. No.
Cat. No.
Cat. No.
2
2
700-CF220⊗
700-CFB220⊗
700-CFM220⊗
3
1
700-CF310⊗
700-CFB310⊗
700-CFM310⊗
4
0
700-CF400⊗
700-CFB400⊗
700-CFM400⊗
0
4
700-CF040⊗
700-CFB040⊗, Standard Contacts(1)
Connection Diagrams 120V
10
240V
10
10
400V
500V
6
2.5
600V
690V
1
1
(1) For spring clamp terminals, insert R after 700-C. Example: Cat. No. 700-CRF220D. (2) All Cat. Nos. are factory-stocked.
⊗ AC Coil Voltage Code The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700-CF220⊗ becomes Cat. No. 700-CF220D for 120V, 60 Hz. [V]
12
24
32
36
42
48
100
100... 110
110
120
127
200
200... 220
208
208... 240
220... 230
230
230... 240
240
50 Hz
R
K
V
W
X
Y
KP, D
P
S
KG
L, - F, VA
T
60 Hz
Q
J, V, X, KP, D, - KG
H
L, - - A
50/60 Hz, KJ, - - KY
KP, KD, - KG
KL, - KL
KF, KA
[V]
277
347
380
380... 400
400
400... 415
440
480
500
550
600
50 Hz, - - N, G
B, M
C, 60 Hz
T
I
E, - - N
B, - C
50/60 Hz, - - - KN, KB, - - - 188
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 190
IEC Industrial Relays
4-Pole DC Coil Voltage (Ratings for 700-CF Only) AC-12
AC-15
Ith[A] 40 °C
Contacts Connection Diagrams
Ie [A] 60 °C
24/48V
120V
240V
400V
500V
600V
690V
Standard Contacts(1)
Gold Plated Bifurcated Contacts(2)
Master Contacts(2) Cat. No.
N.O.
N.C.
Cat. No.
Cat. No.
2
2
700-CF220
700-CFB220⊗ 700-CFM220⊗
⊗
20
20
10
10
10
6
2.5
1
1
3
1
700-CF310⊗ 700-CFB310⊗ 700-CFM310⊗
4
0
700-CF400⊗ 700-CFB400⊗ 700-CFM400⊗
(1) For spring clamp terminals, insert R after 700-C. Example: Cat. No. 700-CRF220D. (2) All Cat. Nos. are factory-stocked.
⊗ DC Coil Voltage Code The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. example: Cat. No. 700-CF220⊗ becomes Cat. No. 700-CF220EJ for 24V DC, electronic with diode. [V]
9
12
24
36
48
48... 72
60
64
72
80
110
110... 115 125
125
220
220... 250
230
250
Electronic with diode, EQ
EJ
EW, EY, - - - - ED, - - EA, - Electronic with diode/ Quick Pick-up, - QJ, - - - - - - - - - - - - - - Rockwell Automation Publication 700-TD552B-EN-P - August 2018
189