The text of a spec sheet · part 24 of 25
Relay and Timer Specifications, Bulletin Number 700, pages 231 to 240
Pages 231 to 240 of 250
The original document is the PDF (23 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX
Page 231
Solid-State Relays
Dimensions - 700-SC Relays All units in millimeters unless otherwise indicated. To convert millimeters to inches multiply by 0.0394. Dimensions are not intended to be used for manufacturing purposes. Terminal Arrangement/ Internal Connections (Bottom View)
28 max.
1
4
5
8(+) Load
9
Load
(+)
12(–) (–)
21.5 max.
13
36.5 max.
Input
14
–
42.5 max. –
Note:
Load power supply
+ Input voltage
+
The plus and minus symbols shown in parentheses are for DC loads.
Cat. No 700-SC… (1) (1)
700-SC is compatible with Cat. Nos. 700-HN103, -HN104, and -HN128 socket.
Basic Application Considerations for 700-SC High-density Mounting of Multiple Solid-state Relays (SSRs) If multiple relays are mounted side by side, the outer wall of each SSR works as a radiator. The SSR casing serves to dissipate heat. Install the relays so that they are adequately ventilated. If poor ventilation is unavoidable, reduce the load current by half.
Connection For DC Load Switching, 700-SC will operate properly if the load is connected to either the positive or negative SSR load terminal.
Protective Component When controlling AC inductive loads, connect an inrush/surge absorbing device (varistor) across the SSR load terminals. If the SSR has built- in surge suppression (s 700-SE and 700-SH) and additional surge suppression is required, connect the varistor across the terminals of the load device. Select a varistor that meets the conditions of the load voltage that is outlined in the table below. Load Voltage [V AC]
Varistor Voltage [V]
100…120
240…270
200…240
440…470
380…480
820…1000
TIP
Varistor Surge Resistance
1000 A min.
For additional details on solid-state relays, see the Solid-State Relay Application Guide, publication 700-AT001.
Load Input
230
SSR
Load power supply
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 232
Solid-State Relays
700-SF Square Base Relays • 3 A (resistive) max. continuous load (output) current • 264V AC or 52.8V DC max. load voltage options • 4…24V DC control/input voltage • Photocoupler or phototriac isolation option between control and output voltage • LED Indicator for input/logic ON/OFF status monitoring 700-HN116 socket compatible
•
Input-to-Output Isolation Method
Zero Cross Function
Photocoupler
Yes
Phototriac
No
Photocoupler
Not Applicable
Status Indicator
Yes
Output (Load) Max. Continuous Current and Rated Voltage Range
Rated Input Control Voltage
Cat. No.
3 A @ 100…240V AC (47...63 Hz)
5…24V DC
700-SFZY3Z25
24V DC
700-SFTY3Z24
3 A @ 4…48V DC
4…24V DC
700-SFNY3Z25
Accessories-700-SF Relays Photo
(1)
Description
Pkg. Quantity
Cat. No.
Screw Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket for use with DPDT HF relays.
10
700-HN116
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N41
Retainer Clip for Cat. Nos. 700-HN103, -HN104, and -HN128 Sockets with 700-HC Relays. Secures relay in socket.
10
700-HN114(1)
700-SF must use Cat. No. 700-HN114 series B retainer clip.
Specifications- 700-FS Relays Control/Input Ratings Cat. No.
Rated Control Voltage
Max. Operating Control Voltage Range [V DC]
Max. Reverse Control Voltage [V]
Impedance
700-SFZY3Z25
5…24V DC
4…28V DC
–32
700-SFTY3Z24
24V DC
19.2…28.8V DC
700-SFNY3Z25
5…24V DC
4…28V DC
Control Voltage Levels Pick-up Voltage
Drop-out Voltage
15 mA max. (1)
4V DC max.
1V DC min.
–28.8
2 kΩ ± 20%
19.2V DC max.
1V DC min.
–28.8
1.5 kΩ + 20%/– 10% (2)
4V DC max.
1V DC min.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
231
Page 233
Solid-State Relays
Load/Output Ratings Cat. No.
Rated Control Voltage
Max. Load Voltage Range
Continuous Load Current (Resistive) [A]
700-SFZY3Z25
100…240V AC
75…264V AC
4…48V DC
3…52.8V DC
700-SFTY3Z24 700-SFNY3Z25
Max. Inrush Current (4)
Min.
Max. (3)
0.1
3
0.1
3
45 A @ 50/60 Hz, 1 cycle
0.1
3
18 A (10 ms)
Characteristics Description Load Switching Method/Device
Output VDRM, VCEO (V)
Cat. No. 700-SFZY3Z25 Cat. No. 700-SFTY3Z24 Triac Transistor 1/2 cycle of load power source 1 ms max. cycle time (5) + 1 ms max. 1/2 cycle of load power source cycle time (5) + 1 ms max. 1.6V (RMS) max. 5 mA max. (@ 100V AC); 2.5 mA max. (@ 100V AC); 5 mA max. (@ 200V AC) 10 mA max. (@ 200V AC) 600 600
Output di/dt (A/uS) Output dv/dt (V/uS) Output I2t (A2S)
50 250 18
50 250 18, - - Output Tj (°C) Max. Insulation Resistance Dielectric Strength Vibration Resistance (Max.) Shock Resistance (Max.)
125 100 MΩ min. (at 500V DC) 1,500V AC, 50/60 Hz for 1 min 10…55 Hz, 1.5 mm double amplitude (10 G) 1000 m/s2 (100 G)
125
150
Ambient Temperature
Operating: –30…+80 °C (–22…+176 °F) with no icing or condensation Storage: –30…+100 °C (–22…=212 °F) with no icing or condensation
Ambient Humidity Standards Compliance Certifications Weight
45…85% (no condensation) UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -4-3, EN/IEC 60950 cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, VDE Certified Approx. 50 g
Pick-up Time Drop-out Time Output ON Voltage Drop Output Leakage Current
Cat. No. 700-SFNY3Z25 0.5 ms max. 2 ms max. 1.5V max. 5 mA max. (@ 50V DC) 80
(1) With constant current input circuit system, SSR impedance varies with a change in input voltage. (2) (3) (4) (5)
Input impedance reaches its maximum at the operating voltage. If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. See the “Inrush Current Resistivity” graphs on page 116 for more details. See “Load Current vs. Ambient Temperature Characteristics” on page 116 for additional load current details. 60 Hz full cycle time = 16.6 ms, 50 Hz full cycle time 20 ms.
IMPORTANT
232
This data is non-repetitive. Keep the inrush current to half the rated value if it occurs repetitively. Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 234
Solid-State Relays
Inrush Current Resistivity (1)
Inrush Current Resistivity (1)
700-SFZ… 700SFT…
700-SFN…
Ambient Temperature [° C]
2000
1000
500
200 300
5000
1000
10
100
80
60
40
20
-30
-20
0
0
0
500
10
50 70 100
Inrush Current [A]
20
200
1
30
100
2
40
30 50
3
30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 0 20 30
50
Inrush Current [A Peak]
Load Current [A]
4
10
Load Current vs. Ambient Temperature Characteristics 700-SF
Energizing Time [ms]
Energizing Time [ms]
(1) Inrush current resistivity is defined as the ability of an SSR to withstand a large surge current for a short period. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
EMC Directive Compliance 1. AC-switching models comply with EMC Directives under the following conditions 3 m max. Load Input
700-SF
Varistor: 470 V, 0.6 W Film capacitor: 1µ F, 250 VAC
Output
Varistor
Film capacitor
• Connect a varistor between the output terminals. • Connect a film capacitor to the load power supply. • The input cable must be less than 3 m.
2. DC-switching models comply with EMC Directives under the following conditions Less than 10 m Load Input
700-SF
Output
• The input cable must be less than 10 m.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
233
Page 235
Solid-State Relays
Dimensions - 700-SF Relays All units in millimeters unless otherwise indicated. To convert millimeters to inches multiply by 0.0394. Dimensions are not intended to be used for manufacturing purposes.
Terminal Arrangement/Input Connections (Bottom View)
28 max
1
2
3
4(+)
5
Load
6(-)
7
Input
8
Load
(+)
(-)
-
36.5 max 42.5 max
21.5 max
-
+
Input Voltage
+
Notes: 1. The plus and minus symbols shown in parentheses are for DC loads. 2. The coil has no polarity.
IMPORTANT
700-SF is compatible with Cat. No. 700-HN116 socket.
Basic Application Considerations of 700-SF High-density Mounting of Multiple Solid-state Relays (SSRs) If multiple SSRs are mounted side by side, the outer case wall of the SSR acts as a radiator. The SSR case serves to dissipate heat. Install the relays so that they are adequately ventilated. If poor ventilation is unavoidable, reduce the load current by half.
Connection For DC load switching, the Bul. 700-SF SSR will operate properly if the load is connected to either the positive or negative load terminals.
Protective Component to Extend SSR Life When controlling AC inductive loads, connect an inrush/surge absorbing device (varistor) across the SSR load terminals. If the SSR has built- in surge suppression (700-SE and 700-SH) and additional surge suppression is required, connect the varistor across the terminals of the load device. Select a varistor that meets the conditions of the load voltage that is outlined in the table. Load Voltage [V AC]
Varistor Voltage [V]
100…120
240…270
200…240
440…470
380…480
820…1000
TIP
Varistor Surge Resistance
1000 A min.
For additional details on solid-state relays, see the Solid-State Relay Application Guide, publication 700-AT001.
For a DC inductive load, a diode should be connected parallel to the load to absorb the counter electromotive force (OFF) of the load.
Load Input
234
SSR
Load power supply
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 236
Solid-State Relays
700-SH Hockey Puck Relays • 100 A max. continuous load (output) current with appropriate heat sink • 264V AC, 530V AC, or 660V AC max. load voltage options • 3…32V DC, 4…32V DC, 80…130V AC, 200…260V AC, 20…280V AC/22…48V DC control (input) voltage options • LED indicator for input/logic ON/OFF status monitoring • Protective cover for added safety
Photo
Input-toOutput Isolation Method
Zero Cross Function
Yes
Status Indicator
Yes
Output (Load) Max. Continuous Current and Rated Voltage Range (1)
Rated Input Control Voltage
Cat. No.(2)
10 A @ 42…265V AC
3…32V DC
700-SH10JZ24
10 A @ 42…265V AC
80…130V AC
700-SH10JA12
10 A @ 42…265V AC
200…260V AC
700-SH10JA22
10 A @ 42…530V AC
4…32V DC
700-SH10HZ25 (Series B)
25 A @ 42…530V AC
4…32V DC
700-SH25HZ25 (Series B)
25 A @ 24…265V AC
3…32V DC
700-SH25GZ24
25 A @ 24…265V AC
20…280V AC/ 22…48V DC
700-SH25GA24
50 A @ 24…265V AC
3…32V DC
700-SH50GZ24
50 A @ 24…265V AC
20…280V AC/ 22…48V DC
700-SH50GA24
50 A @ 42…530V AC
4…32V DC
700-SH50HZ25
25 A @ 42…660V AC
4…32V DC
700-SH25VZ25
25 A @ 42…660V AC
20…280V AC/ 22…48V DC
700-SH25VA24
50 A @ 42…660V AC
4…32V DC
700-SH50VZ25
50 A @ 42…660V AC
20…280V AC/ 22…48V DC
700-SH50VA24
75 A @ 42…530V AC
4…32V DC
700-SH75HZ25
75 A @ 42…660V AC
4…32V DC
700-SH75VZ25
75 A @ 42…530V AC
20…280V AC/ 22…48V DC
700-SH75HA24
75 A @ 42…660V AC
20…280V AC/ 22…48V DC
700-SH75VA24
100 A @ 42…530V AC
4…32V DC
700-SH100HZ25
100 A @ 42…530V AC
20…280V AC/ 22…48V DC
700-SH100HA24
100 A @ 42…660V AC
4…32V DC
700-SH100VZ25
100 A @ 42…660V AC
20…280V AC/ 22…48V DC
700-SH100VA24
5 A @ 3...60V DC
3…32V DC
700-SH5FZ24
25 A @ 90…280V AC
4…20 mA DC
700-SH25WA25
50 A @ 90…280V AC
4…20 mA DC
700-SH50WA25
Optocoupler
Yes
No
Yes
Yes
(1) When used with heat sink. (2) All catalog numbers are Series A unless noted.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
235
Page 237
Solid-State Relays
Accessories - 700-SH Relays Photo
236
Description
Pkg. Quantity
Cat. No.
Heat Sink - Panel or DIN Rail Mount
1
700-SN10
Heat Sink - Panel or DIN Rail Mount
1
700-SN25
Heat Sink - Panel or DIN Rail Mount
1
700-SN50
Heat Sink - Panel or DIN Rail Mount
1
700-SN50HC
Heat Sink - Panel or DIN Rail Mount
1
700-SN50VHC
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Thermal Conductive Pads
50
700-SHCPAD
Plastic Covers, for DC output version
25
700-SHCOV
Thermal Adapters - for 100 A Wire
10
700-SHTRMA
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 238
Solid-State Relays
Specifications- 700-SH Relays Control/Input Ratings Cat. No.
Operating Voltage
Input Current @ Max. Voltage
Voltage Level Pickup Voltage
Drop-out Voltage
3…32V DC
12 mA
2.75V DC max.
1.2V DC min.
80…130V AC
13 mA
70V AC max.
30V AC min. (1)
200...280V AC
13 mA
190V AC max.
90V AC min.
4…32V DC
12 mA
4V DC max.
1V DC min.
20…280V AC/22…48V DC
20 mA
18V AC/DC
6V AC/DC
3…32V DC
12 mA
2.5V DC
1.2V DC
20…280V AC/22…48V DC
20 mA
-32V DC
6V AC/DC
4…32V DC
12 mA
3.5V DC
1.2V DC
20…280V AC/22…48V DC
20 mA
18V AC/DC
6V AC/DC
700-SH_ _ W…
Current Control
4…20 mA, - 700-SH_ _ F…
3…32V DC
12 mA
3V DC max.
1.0V DC
700-SH10J…
700-SH_ _ H…
700-SH_ _ G…
700-SH_ _ V…
(1) When specified heatsink is used.
Output Ratings Load Voltage Range
Applicable Load Current with Heat Sink [A] (2)
700-SH5FZ24
3…60V DC
0.001…5 A DC
700-SH10J…
42…265V AC
0.15…10
700-SH10H…
42…530V AC
0.15…10
700-SH25G…
24…265V AC
0.15…25
700-SH25H…
42…530V AC
0.15…25
700-SH25V…
42…660V AC
0.15…25
700-SH25W…
90…280V AC
0.15…25
700-SH50G…
24…265V AC
0.15…50
700-SH50H…
42…530V AC
0.15…50
700-SH50V…
42…660V AC
0.15…50
700-SH50W…
90…280V AC
0.15…50
700-SH75H…
42…530V AC
0.15…75
700-SH75V…
42…660V AC
0.15…75
700-SH100H…
42…530V AC
0.15…100
700-SH100V…
42…660V AC
0.15…100
Cat. No.
(2) AC unless indicated.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
237
Page 239
Solid-State Relays
Characteristics Description
Cat. Nos. 700-SH10, 25, 50 (not including 700-SH_ _W)
Cat. Nos. 700-SH75, 100
Pick-up Time
1/2 of load power source cycle time(DC input) / 1 of load power source cycle time (AC input)
Drop-out Time
1/2 of load power source cycle time (DC input) / 2 of load power source cycle time (AC input)
Output ON Voltage Drop
1.6V (RMS) max.
Output Leakage Current
<3 mARMS 100 MΩ min (@ 500V DC)
Insulation Resistance
100 MΩ min. (at 500V DC)
Dielectric Strength
>4000V ACRMS
Vibration Resistance
Malfunction: 10…55 Hz, 1.5 mm double amplitude
Shock Resistance
Malfunction: 1000 m/s2 Operating: –20…+70 °C with no icing or condensation
Ambient Temperature Storage: –40…+100 °C with no icing or condensation Ambient Humidity
0…95% no condensing
Standards Compliance
UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -4-2, -4-3, EN 61000-6-2, EN 61000-6-4
Certifications cURus Recognized (File No. E14843, Guide NPNT2), CSA Certified (File No. 240924)
Weight
Approx. 60 g
Description
Approx. 100 g
Cat. No. 700-SH_ _W
Pick-up Current
4.2 mA
Drop-out Current
4.1 mA
Voltage Drop
<10V DC @ 20 mA
Leakage Current
<3 mA
Insulation Voltage
<4000 VRMS
Vibration Resistance
Malfunction: 10…55 Hz, 1.5 mm double amplitude
Shock Resistance
Malfunction: 1000 m/s2
Ambient Temperature
Operating: –20…+70 °C with no icing or condensation
Ambient Humidity
0…95% no condensing
Standards Compliance
UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -4-2, -4-3, EN 61000-6-2, EN 61000-6-4
Certifications cURus Recognized (File No. E14843, Guide NPNT2), CSA Certified (File No. 24024)
Weight
Approx. 60 g
Description
Cat. No. 700-SH5FZ24
Pick-up Voltage
<3V DC
Drop-out Voltage
>1V DC
Activating Frequency
<100 Hz
Input Impedance
1 kΩ
Response Time Pick-up @ Vin > 5V
<4000 uS
Response Time Drop-out
<1 mS
On-state Voltage Drop @ Rated Current
<1.5V
238
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 240
Solid-State Relays
Description
Cat. No. 700-SH5FZ24
Off-state Current Drop @ Rated Voltage
<1 mA
Insulation Voltage
<1 mA
Vibration Resistance
Malfunction: 10…55 Hz, 1.5 mm double amplitude
Shock Resistance
Malfunction: 1,000 m/s2
Ambient Temperature
Operating: –20…+70 °C with no icing or condensation
Ambient Humidity
0…95% no condensing
Standards Compliance
UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -4-2, -4-3, EN 61000-6-2, EN61000-6-4 cURus Recognized (File No. E14843, Guide NPNT2), CSA Certified (File No. 240924)
Certifications Weight
Approx. 60 g
Surge Current vs. Ambient Temperature Characteristics Surge current resistivity for 700-SH50....
Surge current resistivity for 700-SH10, 25.... 700A
300A
600A
250A
500A
Inrush current (Apk)
Inrush current (Apk)
350A
200A
150A
100A
400A
300A
200A
50A
100A
0A 10ms
100ms
1000ms
0A 10ms
10000m s
Energizing time (ms)
100ms
1000ms
10000m s
Energizing time (ms)
Surge current resistivity for 700-SH75....
Surge current resistivity for 700SH100....
1200A
2000A 1800A 1000A
1600A 1400A
Inrush current (Apk)
Inrush current (Apk)
800A
600A
400A
1200A 1000A 800A 600A
200A
400A 200A
0A 10ms
100ms
1000ms
Energizing time (ms)
10000m s
0A 10ms
100ms
1000ms
10000m s
Energizing time (ms)
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
239