For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX
Page 221
Solid-State Relays
Product Overview
Bulletin No.
700-SF
700-SH
700-SK
Type
Square Base, Socketed
Hockey Puck
Slim Line, Socketed
Features (1)
Compatible with 700-HN116 socket, LED status, zero-cross AC switching
Panel/DIN Mount, High Current, Protective Cover, LED Status
Compatible with 700-HN121 socket. Supports Input (sensor) module or Output (SSR) module
Load Type
AC (47…63 Hz)
DC
AC (47…63 Hz) 3…60V DC
Load Voltage Range
75…264V AC
3 … 52.8V DC
Load Current Max. (Continuous)
3A
Max. Leakage Current to Load
5 mA @ 100V AC, 10 mA @ 200V AC
Zero Cross Load Switching
Yes
Equivalent Electromecha nical Relay Contact Arrangement
Output Module
Input Module
AC (47…63 Hz)
DC
AC (47…63 Hz)
DC
3…50V DC, 24…265V AC 42…530V AC, 42…265V AC, 42…660V AC
75 … 264V AC
4 … 60V DC, 40 … 200V DC
Field Input: 60… 264V AC
Field Input: 6.6… 32V DC
10 A/100 A‡
2A
2 A @ 60V, 1.5 A @ 200V
Supply Current: 0.1…100 mA
Supply Current: 0.1…100 mA
5 mA @ 50V DC
<3 mA
1.5 mA
1 mA
5 μA
5 μA
Not Applicable
Yes
Yes (optional)
N/A
No
N/A
Form A
Form A
Form A
Rated Control (Input) Voltage
4V DC or 24V DC
3…32V DC, 4…32V DC, 80…130V AC, 20…260V AC 20…280V AC/22…48V DC
5… 24 V DC
LED Indicator
Yes
Yes
Yes
Mounting Method
Panel or DIN with socket
Panel without heat sink, Panel, or DIN with heat sink
Panel or DIN with socket
Dielectric Strength
1500V AC, 50/60 Hz, 1 min.
>4000V AC RMS
4000V AC, 50/60 Hz, 1 min.
Certification cURus, CE, VDE cURus, CE, CSA cURus, CE, TÜV
Max. Ambient Operating Temperature
-30…80 °C (no condensation)
-20…70 °C (no condensation)
-30…80 °C (no condensation)
Page
231
235
244
(1) See Solid-state Relay Glossary on page 221 for term definitions.
220
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 222
Solid-State Relays
Solid-state Relay Glossary Terms
Insulation
Circuit functions
Input
Meaning Basic insulation
Insulation for basic protection from electric shock (IEC950 1.2.9.2)
Supplemental insulation
Independent insulation that is provided outside of basic insulation to protect from electric shock when the basic insulation breaks down (IEC950 1.2.9.3)
Reinforced insulation
A single-layer of insulation (IEC950 1.2.9.5) that provides the same protection from electric shock as double insulation (insulation including both basic and supplemental insulation) according to conditions stipulated in IEC950 standards
Zero cross circuit
A circuit that starts operation with the AC load voltage at close to zero-phase.
Trigger circuit
A circuit for controlling the triac or thyristor trigger signal, which turns the load current ON and OFF.
Isolated input circuit
If the external circuit is prone to generating noise, or if wires from external sources are prone to the influence of inductive noise, in order to prevent malfunctions due to noise, it is necessary to electrically isolate internal circuits and external circuits (output circuits). An isolated input circuit is a circuit that isolates inputs and outputs by using components that are not connected electrically but that can transmit signals, such as contact relays or photocouplers.
Photocoupler
A component that runs the electric signal into a light emitter (for example, LED), changes it to a light signal, and then returns it to an electric signal using a photoelectric conversion element, such as a photo transistor. The space that is used for transferring the light signal is isolated thus providing good insulation and a high propagation speed.
Rated voltage
The voltage that serves as the standard value of an input signal voltage
Pickup (must-operate) voltage Minimum input voltage when the output status changes from OFF to ON.
Output
Input impedance
The impedance of the input circuit and the resistance of current-limiting resistors used. Impedance varies with the input signal voltage in case of the constant current input method.
Operating voltage
The permissible voltage range within which the voltage of an input signal voltage may fluctuate.
Dropout (Reset) voltage
Maximum input voltage when the output status changes from ON to OFF.
Input current
The current value when the rated voltage is applied.
Load voltage
This is the effective value for the power supply voltage that can be used for load switching or in the continuous-OFF state.
Maximum load current (continuous)
The effective value of the maximum current that can continuously flow into the output terminals under specified cooling conditions (i.e., the size, materials, thickness of the heat sink, and an ambient temperature radiating condition).
Leakage current
The effective value of the current that can flow into the output terminals when a specified load voltage is applied to the SSR with the output turned OFF.
Output ON voltage drop
The effective value of the AC voltage that appears across the output terminals when the maximum load current flows through the SSR under specified cooling conditions (such as the size, material, and thickness of heat sink, ambient temperature radiation conditions, etc.).
Minimum load current (continuous)
The minimum load current at which the SSR can operate normally.
Snubber circuit
A circuit consisting of a resistor R and capacitor C, which prevents faulty ignition from occurring in the SSR triac by suppressing a sudden rise in the voltage that is applied to the triac.
Semiconductor output element (switching element)
This is a generic name for semiconductors such as the thyristor, triac, power transistor, and power MOS FET. In particular, triacs are often used in SSRs because they allow switching to be performed with one element.
Repetitive peak OFF-state voltage (VDRM)
This is a rating for an output semiconductor that used in an SSR for AC loads.
Collector-emitter voltage (VCEO)
This is a rating for an output semiconductor that used in an SSR for DC loads.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
221
Page 223
Solid-State Relays
Terms
Meaning Operating (pick-up) time
A time lag between the moment a specified signal voltage is imposed to the input terminals and the output is turned ON.
Release (drop-out) time
A time lag between the moment the imposed signal input is turned OFF and the output is turned OFF.
Insulation resistance
The resistance between the input and output terminals or I/O terminals and metal housing (heat sink) when DC voltage is imposed.
Dielectric strength
The effective AC voltage that the SSR can withstand when it is applied between the input terminals and output terminals or I/O terminals and metal housing (heat sink) for more than 1 minute.
Ambient temperature and humidity (operating)
The ranges of temperature and humidity in which the SSR can operate normally under specified cooling, input/output voltage, and current conditions.
Storage temperature
The temperature range in which the SSR can be stored without voltage imposition.
Inrush current resistance
A current, which can be applied for short periods of time to the electrical element.
Counter-electromotive force
Extremely steep voltage rise which occurs when the load switched or turned OFF.
Characteristics
The recommended load capacity which takes into account the safety factors of ambient temperature and inrush Recommended applicable load current.
Others
The resistance connected in parallel to the load in order to increase apparently small load currents, so that the ON/OFF of minute currents functions normally. (It is also used to shunt leakage currents.)
Bleeder resistance
Solid-state Relay Switching Capacity
Relay Type
Equivalent EM Relay Contact Configuration
700-SA
Form A
700-SC Solid-State
700-SF
Form A
700-SH *
Form A
700-S KO
IMPORTANT
222
Form A
Form A
Load Voltage
Maximum AC an d DC Switching Capability Load Zero-Cross Switching 1 mA 10 mA 50 mA 100 mA 1 A 3A 5A 10 A 2 0 A 25 A Device
AC
Yes
Triac
DC
N/A
Transistor
AC
Yes
Triac
DC
N/A
Transistor
AC
Yes
Triac
DC
N/A
Transistor Thyristor or Triac Transistor
AC
Yes
DC
N/A
AC
Yes
Triac
DC
N/A
Transistor
(2 A)
(2 A)
* Requires a heat sink to reach maximum current value.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
30 A
35 A
100 A
Page 224
Solid-State Relays
700-SA Tube Base Relays • 5 A (resistive) max. continuous load (output) current • 264V AC or 125V DC max. load voltage options • Photocoupler isolation between control and load voltage • LED indicator (standard) for input/logic ON/OFF status monitoring • 700-HN100, -HN125, -HN 202, or -HN108 specialty socket compatible • 700-HT2 timing module Input-to-Output Isolation Method Photocoupler
Zero Cross Function Yes
Status Indicator
Yes
Not Applicable
Output (Load) Max. Continuous Current and Rated Voltage Range
Rated Input (Control) Voltage
5 A @ 100…240V AC (47…63 Hz)
5…24V DC
Cat. No. 700-SAZY5Z25
3 A @ 5…110V DC
700-SANY3Z25
Accessories - 700-SA Relays Photo
Description
Pkg. Quantity
Cat. No.
10
700-HN100
10
700-HN108
10
700-HN125
10
199-DR1
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N41
10
700-HN158
10
700-HN204
Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction. 8 Pin for use with DPDT 700-HA Relays.
Specialty Socket 8 Pin back wired socket with solder terminals
Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Open Style Construction. 8 Pin for use with DPDT 700-HA Relays. No retainer clip required.
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
Retainer Clip for Sockets with 700-SA AND 700-HB Relays. Secures relay in socket.
8-Pin Socket, Can Be Used With or Without Timing Module or Surge Suppressor. Screw Terminal Tube Base Sockets, panel or DIN Rail mounting. Guarded terminal construction. Used with DPDT 700-HA Relays.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
223
Page 225
Solid-State Relays
Specifications - 700-SA Relays Control/Input Ratings Cat. No.
700-SAZY5Z25 700-SANY3Z25
Rated Control Voltage
Max. Operating Control Voltage Range
Max. Reverse Control Voltage
Impedance
4…32V DC
-32V DC
15 mA max. (1)
4…30V DC
-30V DC
1.5 kΩ (+20% -10%)
5…24V DC
Control Voltage Levels Pick-up Voltage Drop-out Voltage 4V DC max.
1V DC min.
Load/Output Ratings Cat. No.
Rated Load Voltage
Maximum Load Voltage Range
Continuous Load Current (Resistive) [A] Min. Max. (2)
700-SAZY5Z25
100…240V AC
75…264V AC
0.1
5.0
700-SANY3Z25
5…110V DC
3…125V DC
0.1
3.0
Max. Inrush Current (3) 80 A, @ 50/60 Hz for 1 cycle 12 A (10 ms)
Characteristics Description Load Switching Method/Device Pick-up Time Drop-out Time Output ON Voltage Drop Output Leakage Current
Cat. No. 700-SAZY5Z25 Cat. No. 700-SANY3Z25 Triac Transistor 0.5 ms max. 1/2 cycle of load power source cycle time (4) + 1 ms max. 1/2 cycle of load power source cycle time (4) + 1 ms max. 2.5 ms max. 1.6V (RMS) max. 1.5V max. 5 mA max. (at 100V AC); 10 mA max. (at 200V AC) 5 mA max. (at 125V DC) 600 150 50, 500, 41.6, 125 150 100 MΩ min. (at 500V DC) 1500V AC, 50/60 Hz for 1 min 10…55 Hz, 1.5 mm double amplitude (10 G) 1000 m/s2 (100 G) –30…80 °C (–22…176 °F) with no icing or condensation –30…100 °C (–22…212 °F) with no icing or condensation 45…85% (no condensation) UL 508, CSA C22.2 No. 14, EN 60947-1, -4-3 cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, VDE Certified Approx. 70 g
Output VDRM VCEO (V)
Output di/dt (V/uS) Output dv/dt (V/uS) Output I2t (A2S) Output Tj (ºC) Max. Insulation Resistance Dielectric Strength Vibration Resistance (Max.) Shock Resistance (max.) Ambient Temperature
Operating Storage
Ambient Humidity Standards Compliance Certifications Weight
With constant current input system. SSR input impedance varies with a change in input (control) voltage. See the following graph “Load Current Vs. Ambient Temperature Characteristics” for additional load current details. If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. See “Inrush Current Resistivity” graph. 60 Hz full cycle time = 16.6 ms, 50 Hz full cycle time = 20 ms.
Inrush Current Resistivity (1)
Load Current vs. Ambient Temperature Characteristics 700-SA
700-SA 80
2 1
50 40
700-SAZY5Z25
30 20 10 500
700-SANY3Z25 100
0
200
80
Ambient Temperature [° C]
100
40
60
20
0
-30 -20
0
5000
700-SANY3Z25 3
30 50
Load Current [A]
4
70 60
1000
Inrush Current [A. Peak]
700-SAZY5Z25 5
10
(1) (2) (3) (4)
Energizing Time [ms]
(1) Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period. Surges are considered non-repetitive (max. repeatability once every 5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
224
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 226
Solid-State Relays
Terminal Arrangement (Bottom View)
Load
Load
Load power supply
Input
Input voltage Note: The plus and minus symbols shown in parentheses are for DC loads.
Basic Application Considerations High Density Mounting of Multiple Solid-state Relays (SSRs) If multiple SSRs are installed side by side,, the outer case wall of the SSR serves to dissipate heat. Install the relays so that they are adequately ventilated. If poor ventilation is unavoidable, reduce the load current to half.
Protective Component When controlling AC inductive loads, connect an inrush/surge absorbing device (varistor) across the SSR load terminals. If the SSR has built- in surge suppression (s 700-SE and 700-SH) and additional surge suppression is required, connect the varistor across the terminals of the load device. Select a varistor that meets the conditions of the load voltage that is outlined in the table. Load Voltage
Varistor Voltage [V]
100…120V AC
240…270
200…240V AC
440…470
380…480V AC
820…1000
TIP
Varistor Surge Resistance
1000 A min.
For additional details on solid-state relays, see the Solid-State Relay Application Guide, publication 700-AT001.
For a DC inductive load, a diode should be connected parallel to the load to absorb the counter electromotive force (OFF) of the load. EMC Directive Compliance 1. AC-switching models comply with EMC Directives under the following conditions:
Load Load power supply
SSR
Input
3 m max. Load Input
700-SA Output
Varistor: 470 V, 0.6 W Film Capacitor: 1µ F, 250 VAC
Varistor
Film Capacitor
• Connect a varistor between the output terminals. • Connect a film capacitor to the load power supply. • The input cable must be less than 3 m. 2. DC-switching models comply with EMC Directives under the following conditions: Less than 10 m Load Input
700-SA Output
• The input cable must be less than 10 m.
Dimensions - 700-SA Relays
All units in millimeters unless otherwise indicated. To convert millimeters to inches multiply by 0.0394. Dimensions are not intended to be used for manufacturing purposes. 700-SA (1)
+ 35 max.
+ 35 max. (1)
52.5 max.
700-SA is compatible with Cat. Nos. 700-HN100, -108, -125, and -204 (sockets).
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
225
Page 227
Solid-State Relays
700-SC Ice Cube Relays • 3 A (resistive) max. continuous load (output) current • 264V AC, 48V DC or 125V DC max. load voltage options • 5…24V DC or 110/220V AC control (input) voltage options • LED indicator (optional) for input/logic On/Off status monitoring • 700-HN103, 700-HN104, or 700-HN128 socket compatible • Compatible with 700-AT1 or 700-AT2 timer modules Input-to-Output Isolation Method
Photocoupler
Zero Cross Function
Status Indicator
Yes
Photocoupler
Rated Input (Control) Voltage
Cat. No.
3 A @ 100…240V AC(1)
5…24V DC
700-SCZY3Z25
100/110V AC
700-SCZY2A1
2 A @ 100…240V AC(1)
200/220V AC
700-SCZY2A2
No
3 A @ 100…240V AC (1)
24V DC
700-SCTY3Z24
Not Applicable
3 A @ 4…48V DC
5…24V DC
700-SCNY3Z25
4…24V DC
700-SCZN3Z26
24V DC
700-SCTN3Z24
3 A @ 4…48V DC
4…24V DC
700-SCNN3Z26
2 A @ 5…110V DC
5…24V DC
700-SCNN2Z25
Yes Phototriac
Output (Load) Max. Continuous Current and Rated Voltage Range
Yes
Phototriac
No
Photocoupler
Not Applicable
3 A @ 100…240V AC (1) No
(1) 47…63 Hz
Accessories - 700-SC Relays Photo
226
Description
Pkg. Quantity
Cat. No.
Screw Terminal Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction.Ith = 10 A per pole. 14-blade miniature socket for use with 700-SC Relays.
10
700-HN103
Screw Terminal Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction Ith = 10 A per pole. 14-blade miniature socket for use with 700-SC relays. This socket has coil and contact separation and the ability to plug in optional plug-in modules (700-A__ accessories: LED, Surge Suppression, Timing Modules)
10
700-HN104
Screw Terminal Base Socket, Panel or DIN Rail Mounting; Open-Style Construction Ith = 10 A per pole. 14-blade miniature socket for use with 700-SC Relays.
10
700-HN128
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 228
Solid-State Relays
Photo
Description
Pkg. Quantity
Cat. No.
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N41 (1)
Retainer Clip for Cat. Nos. 700-HN103, -HN104, and -HN128 Sockets with 700-HC Relays. Secures relay in socket.
10
700-HN114
(1) Series B retainer clip must be used with 700-SC
Specifications- 700-SC Relays Control/Input Ratings Max. Reverse Control Voltage [V]
Impedance
700-SCTY3Z24
5…24V DC 100/110V AC 200/220V AC 24V DC
Max. Operating Control Voltage Range 4…28V DC 75…125V AC 150…250V AC 19.2…28.8V DC
-28.8 NA NA -28.8
4V DC max. 75V AC max. 150V AC max. 19.2V DC max.
700-SCNY3Z25
5…24V DC
4…28V DC
-28
15mA max.(1) 41 kΩ ±20% 72 kΩ ±20% 2 kΩ ±20% 1.5 kΩ +20%/ -10% (2)
4V DC max.
15mA max. (1) 2 kΩ ±20%
3V DC max. 19.2V DC max.
1.5 kΩ +20%/ -10%
3V DC max.
Cat. No.
Rated Control Voltage
700-SCZY3Z25 700-SCZY2A1 700-SCZY2A2
700-SCZN3Z26 700-SCTN3Z24 700-SCNN3Z26 700-SCNN2Z25
4…24V DC 24V DC 4…24V DC 5…24V DC
3…28V DC 19.2…28.8V DC 3…28V DC
-28.8 -28.8 -28 -28.8
(2)
Control Voltage Levels Pick-up Voltage Drop-out Voltage 1V DC min. 20V AC min. 40V AC min.
1V DC min.
Load/Output Ratings Cat. No.
Rated Control Voltage
Max. Load Voltage Range
100…240V AC
75…264V AC
Continuous Load Current (Resistive) [A] Min. Max. (3)
Max. Inrush Current (4)
700-SCZY3Z25 700-SCTY3Z24 700-SCZN3Z26 700-SCTN3Z24
0.1
700-SCZY2A1 700-SCZY2A2 700-SCNN3Z26 700-SCNY3Z25 700-SCNN2Z25 (1) (2) (3) (4)
3 45 A (@50/60 Hz, 1 cycle)
0.1
2
4…48V DC
3…52.8V DC
0.1
3
18 A (10 ms)
5…110V DC
3…125V DC
0.1
2
10 A (10 ms)
With constant current input circuit system. SSR impedance varies with a change in input (control) voltage. Input impedance attains its maximum at the operating voltage. If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. See “Inrush Current Resistivity” graphs on page 112 for details See the following “Load Current Versus Ambient Temperature Characteristics” graphs on page 112 for additional load current details.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
227
Page 229
Solid-State Relays
Characteristics Description
Cat. No. 700-SCZ…
Load Switching Method/Device
Pick-up time
Drop-out time Output On Voltage Drop Output Leakage Current Output VDRM, VCEO (V) Output di/dt (A/uS) Output dv/dt (V/uS) Output I2t (A2S) Output Tj (°C) Max. Insulation Resistance Dielectric Strength Vibration Resistance (max.) Shock Resistance (max.) Ambient Temperature Standards Compliance Certifications Ambient Humidity Weight
Cat. No. 700-SCT
Cat. Nos. 700-SCNY, 700Cat. Nos. 700-SCNN2… SCNN3… Transistor
Triac 1/2 of load power source cycle time (1) + 1 ms max. (DC input) 3/2 of load power source cycle time (1) + 1 ms max. (AC input) 1/2 of load power source cycle time (1) + 1 ms max. (DC input) 1/2 of load power source cycle 2 ms max. 2.5 ms max. time (1) + 1 ms max. 3/2 of load power source cycle (1) time + 1 ms max. (AC input) 1.6V (RMS) max. 1.6V (RMS) 1.5V max. 1.5V max. 5 mA max (@ 100V AC) 2.5 mA max (@ 100V AC) 5 mA max (@ 50V DC) 0.1 mA max (@ 100V DC) 10 mA max (@ 200V AC) 5 mA max (at 200V AC) 600 600 80 80 50 50, - 250 250, - 18 18, - 125 125 150 150 100 MΩ min (@500V DC) 1500V AC, 50/60 Hz for 1 minute 10…55 Hz, 1.5 mm double amplitude (10 G) 1000 m/s2 (100 G) Operating: -30…+80 °C (-22...+176 °F) with no icing or condensation Storage: -30…+100 °C (-22...+212 °F) with no icing or condensation UL 508, CSA C22.2 No. 14, EN/IEC 60950, EN 50011, EN 61000-6-2, EN/IEC 60947-1, -4-3 cURus Recognized (File No. E96956, Guide NMFT2/NMFT8), CE Marked, VDE Certified Operating: 45…85% (no condensation) Approx. 50 g
(1) 60 Hz full cycle time = 16.6 ms, 50 Hz full cycle time = 20 ms
Load Current Versus Ambient Temperature Characteristics
700-SC_ _2... 5
4
4
Ambient Temperature [° C]
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
100
80
60
40
100
80
60
0 40
0 20
1
0
1
Ambient Temperature [° C]
228
2
20
2
3
0
3
-30 -20
Load Current [A]
5
-30 -20
Load Current [A]
700-SC_ _3...
Page 230
Solid-State Relays
Inrush Current Resistivity (1) 700-SCNN3...
8 6 4
5000
3000
1000
300 500
0
100
2
20 30 50
Inrush Current [A. Peak] Energizing Time [ms]
Energizing Time [ms]
10
10
5000
500
1000
200
10
0
100
10
2000
20
700-SCNN2... 12
1000
30
700-SCNY3
200 300 500
Inrush Current [A. Peak]
40
30 50
Inrush Current [A. Peak]
50
30 28 26 24 22 20 18 16 14 12 10 8 6 4 2 0
20 30 50 70 100
700-SCT...
10
700-SCZ....
Energizing Time [ms]
(1) Inrush current resistivity is the ability of an SSR to withstand a large surge current for a short period. Surges are considered non-repetitive (max. repeatability once every 2…5 seconds). Keep the inrush current to half the rated value if it occurs repetitively. Exceeding the non-repetitive inrush current will damage the SSR.
EMC Directive Compliance 1. AC-switching models comply with EMC Directives under the following conditions 3 m max. Load Input
700-SC
Varistor: 470 V, 0.6 W Film capacitor: 1µ F, 250 VAC
Output
Varistor
Film capacitor
• Connect a varistor between the output terminals. • Connect a film capacitor to the load power supply. • The input cable must be less than 3 m.
2. DC-switching models comply with EMC Directives under the following conditions Less than 10 m Load Input
700-SC
Output
• The input cable must be less than 10 m.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
229