Page 211

IEC Industrial Relays

Dimensions - 700S-CF Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. c2 c1 c

AC and DC Safety Control Relays with 12V or 24V DC Electronic Coil Cat. No.

a b c c1

Ød c2 d1 d2

45

81

119.5

114.5

6

2 - 4.5

60

35

(1-25/32)

(3-3/16)

(4-3/4)

(4-43/64)

(1/4)

(2 - 3/16)

(2-23/64)

(1-25/64)

700S-CF

DC Safety Control Relays with 48...72V, 110...125V or 220...250V DC Electronic Coil Cat. No.

a b c c1

Ød c2 d1 d2

45

105

119.5

114.5

6

2 - 4.5

60

35

(1-25/32)

(4-1/8)

(4-3/4)

(4-43/64)

(1/4)

(2 - 3/16)

(2-23/64)

(1-25/64)

700S-CF

DC Safety Control Relays with Conventional Coil Cat. No.

a b c c1

Ød c2 d1 d2

45

81

145.5

140.5

6

2 - 4.5

60

35

(1-25/32)

(3-3/16)

(5-49/64)

(5-37/64)

(1/4)

(2 - 3/16)

(2-23/64)

(1-25/64)

700S-CF

Accessories - 700S-CF Relays Safety Control Relays with Auxiliary contact block for side mounting 1- or 2-pole Electronic Timing Module on coil terminal side Interface Module on coil terminal side Surge Suppressor on coil terminal side Labeling with label sheet Marking tag sheet with clear cover Marking tag adapter for System Bul. 1492W

Mounting Position AC and DC E Safety Control Relays

Front View

210

Side View

DC Safety Control Relays

Front View

Side View

Rockwell Automation Publication 700-TD552B-EN-P - August 2018 mm

[in.] a+9 b + 24 b+9 b+3 +0 +0 + 5.5

(a + 23/64) (b + 15/16) (b + 23/64) (b + 1/8) (+ 0) (+ 0) (+ 7/32)

Page 212

IEC Industrial Relays

Safety Relay Circuit With 5 Safety Outputs • Use for E-stop control. E-stop will work properly if any one fault occurs (a fault could be one welded contact or one undesired open connection such as a loose wire). • High output switching capability and long contact life. • Circuit complies with EN 954 categories 1, 2, 3, 4. • Helps prevent restart of the 5 safety outputs if there is a single fault anywhere in the system. • Use (3) 700S-CF relays and this diagram to construct the circuit Basic Circuit (1) Output Circuit (3 Relays, 9 Terminal Blocks)

Start

Push To Stop Pull To Reset

Included in factory wired units

LOAD 1 (5) Output Circuit (3 Relays, 17 Terminal Blocks) LOAD 2 LOAD 3 LOAD 4 LOAD 5

* Numbers shown are the line numbers where the contacts for this relay appear. Contact your local Rockwell Automation sales office or Allen-Bradley distributor for availability.

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

211

Page 213

IEC Industrial Relays

700-K Miniature Control Relays • IEC compact industrial relay • IP2X Finger Protection • Bifurcated contacts for low-level signals • Optional integrated coil protection diode

4-Pole AC or DC Coil Voltage AC-12

AC-15 (B600)

Ith [A]

Ie [A]

40 °C

10

60 °C

6

Contacts Pkg. Qty.(2)

Connection Diagrams

24/48V

3

120V

3

240V

400V

2

500V

1

1

600V

0.6

690V

Cat. No.

N.O.

N.C.

4

0

1

700-K40E-⊗

3

1

1

700-K31Z-⊗

2

2

1

700-K22Z-⊗

1

700-KL22Z-⊗

0.6

1+1L (1) 1+1L (1) 1L = Late Break N.C. / Early Make N.O. (2) May be ordered in package quantities of 20. Add letter M to the end of the cat. no. Example: 700-K40E-ZJM.

⊗ Coil Voltage Codes The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: 230V, 50/60 Hz: Cat. No. 700K40E-⊗ becomes Cat. No. 700-K40E-KF. For other voltages, consult your local Rockwell Automation sales office or Allen-Bradley distributor. For Screw Type Terminal Versions [V]

12

24

110

120

125

220

230

240

250

400

440

480

525

600

AC, 50 Hz, - D, - - - - - - B, VC, AC, 60 Hz, - - D, - - - - - - B, VC

AC, 50/60 Hz, KJ, - - - KF

KA, KN, - - - ZQ

ZJ

ZD, ZS

ZA, - ZT, - - - - - DJ, - - - - - - - - - - - Standard Standard diode

DC

For Spring Clamp Type Terminal Versions AC, 50 Hz, - D, - - - - - - - - - - AC, 60 Hz, - - D, - - - - - - - - - AC, 50/60 Hz, KJ, - - - KF, - - - - - - - ZJ

ZD, - - - - - - - - - - - DJ, - - - - - - - - - - - Standard Standard diode

212

DC

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 214

IEC Industrial Relays

Assignment of Contacts Device Combinations in Accordance with IEC 60947-1 / -4-1 Table valid for: AC / DC = 0.85…1.1 x Us, Tamb. = -25 °C…+60 °C, normal position (horizontal rail mounting). Also valid for 700-KR relays and 100-KR auxiliary contacts. (3) Auxiliary Contact Blocks Cat. No.

Circuit Diagram

Control Relays 700-K (AC and DC Control) Control

700-K22Z-

700-K31Z-

700-K40E-

700-KL22Z-

A1 13 43 21 31

A1 13 33 43 21

A1 13 23 33 43

A1 13 47 21 35

A2 14 44 22 32

A2 14 34 44 22

A2 14 24 34 44

A2 14 48 22 36

AC/DC, 31Z + 02E = 33Y (1)

40E + 02E = 42Y, AC/DC

22Z + 11E = 33Y

31Z + 11E = 42Y

40E + 11E = 51Y

L22Z + 11E = L33Y

AC/DC

22Z + 20E = 42Y

31Z + 20E = 51Y

40E + 20E = 60Y

L22Z + 20E = L42Y

AC/DC, - 40E + 04E = 44Y (1), AC/DC, 31Z + 13E = 44Y (1)

40E + 13E = 53Y, AC/DC, 31Z + 22Z = 53Y (1)

40E + 22Z = 62Y, AC/DC, - 40E + 31Z = 71Y (2), AC/DC

22Z + 40E = 62Y

31Z + 40E = 71Y

40E + 40E = 80Y

L22Z + 40E = L62Y

Front Mounting 51 61

100-KFA02E 52 62 53 61

100-KFA11E 54 62 53 63

100-KFA20E 54 64 51 61 71 81

100-KFA04E 52 62 72 82 53 61 71 81

100-KFA13E 54 62 72 82 53 83 61 71

100-KFA22Z 54 84 62 72 53 73 83 61

100-KFA31Z 54 74 84 62 53 63 73 83

100-KFA40E 54 64 74 84

(1) Tamb. max. +40 °C (2) Tamb. max. +40 °C and only allowed for coil voltage 24V DC or 230V AC (3) For other operating limits, please contact our technical consultant.

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

213

Page 215

IEC Industrial Relays

Auxiliary Contact Blocks Photo

Description

Connection Diagrams

For Use With

Pkg. Qty.

Screw Type Terminals

Spring Clamp Terminals

Cat. No.

Cat. No.

(1)

N.O.

N.C.

0

2

100/104-K, 700-K

1

100-KFA02E

100-KRFA02E

1

1

100/104-K, 700-K

1

100-KFA11E

100-KRFA11E

2

0

100/104-K, 700-K

1

100-KFA20E

100-KRFA20E

0

4

100/104-K, 700-K

1

100-KFA04E

100-KRFA04E

1

3

100/104-K, 700-K

1

100-KFA13E

100-KRFA13E

2

2

100/104-K, 700-K

1

100-KFA22Z

100-KRFA22Z

3

1

100/104-K, 700-K

1

100-KFA31Z

100-KRFA31Z

4

0

100/104-K, 700-K

1

100-KFA40E

100-KRFA40E

51 61 52 62 53 61 54 62 53 63 54 64

Front-mounted auxiliary contacts

• Auxiliary Contact Blocks • 2- and 4-pole versions • Choice of contact configurations • Snap on, no tools required • Electronic-compatible bifurcated contacts for signals down to 15V / 2 mA

51 61 71 81 52 62 72 82 53 61 71 81 54 62 72 82 53 83 61 71 54 84 62 72 53 73 83 61 54 74 84 62 53 63 73 83 54 64 74 84

(1) May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFA02EM.

Control Modules Description

Photo

Connection Diagrams

For Use With

Pkg. Qty.

Cat. No.

1

100-KMCH

1 (1)

100-KFSC50

(1)

100-KFSC280

1 (1)

100-KFSC480

1 (1)

100-KFSV55

1 (1)

100-KFSV136

1 (1)

100-KFSV277

1 (1)

100-KFSD250

Mechanical Interlock

• For interlocking of two adjacent contactors • No added width to contactor assembly • Front mount plug-in type • Optional auxiliary contact blocks and suppressor modules mount onto the interlock 24…48V AC RC Suppressor

110…280V AC 380…480V AC

100/104-K/KR, 700-K/- KR

12…55V AC, 12…77V DC

Surge Suppressor

• Plug-in type • Limits surge voltage on coil drop-off

100/104-K/KR, 700-K/- KR

MOV Suppressor

56…136V AC, 78…180V DC

100/104-K/KR, 700-K/- KR

137…277V AC, 181…250V DC Diode Suppressor

12…250V DC

(1) May be ordered in package quantities of 10. Add letter M to the end of the cat. no. Example: 100-KFSC50M.

214

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

100/104-K/KR, 700-K/- KR

1

Page 216

IEC Industrial Relays

Accessories Photo

Description

Pkg. Qty.

Cat. No.

Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm

10

100-FMS

Snap-In Marker Card

5

1492-M6X12

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

215

Page 217

IEC Industrial Relays

IEC Specifications - 700-K... Relays 700-K

700-KR

AC-12 Rated Thermal Current Ambient temperature 40°C

Ith

24…240V

[A]

10

230…500V

[A]

10

230…690V

[A]

10

24…240V

[A]

6

230…500V

[A]

6

230…690V

[A]

6

24V

[A]

3

48V

[A]

3

120V

[A]

3

230V

[A]

2

240V

[A]

2

400V

[A]

1.2

480V

[A]

1

Ambient temperature 60°C

Ith

AC-15/B600 Switching of Solenoids and contactors

Ie

500V

[A]

1

600V

[A]

0.6

690V

[A]

0.6

Fuse gG

[A]

10

[mA]

2

Main current circuit resistance, 1 pole

[mΩ]

6.5

Power dissipation, 4 poles

[W]

2.6

AC control, warm

[W]

4.4

DC control, warm

[W]

5.2

Mechanical

[Mio. op.]

15

Electrical AC-15 (240V / 2 A)

[Mio. op.]

0.7

AC control kg (lbs.)

0.16 (0.35)

DC control kg (lbs.)

0.2 (0.44)

Rated voltage

AC

[V]

Continuous rating

40 °C

[A]

Switching capacity

AC

[A]

B 600

Rated voltage

DC

[V] max. 600

Switching capacity

DC

[A]

Q 600

Short-circuit Protection

Min. Switching Capacity 15V

Resistance and Power Dissipation

Total power dissipation

Lifespan

Weight

Load Carrying Capacity per UL/CSA

216 max. 600 10

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

6

Page 218

IEC Industrial Relays

700-K DC-13/Q600

1 pole

24V

[A]

2.3

48V

[A]

1

110V

[A]

0.55

125V

[A]

0.55

220V

[A]

0.27

250V

[A]

0.27

400V

[A]

0.15

440V

[A]

0.15

600V

[A]

0.1

Cross Sections Conductor Cross Sections - Main Contacts, Auxiliary Contacts, and Coil Terminals

700-K

700-KR (1)

Terminal type

Fine stranded with ferrule

(1) Conductor (2) Conductors

[mm2]

Solid or coarse stranded

(1) Conductor (2) Conductors

[mm2]

0.75…2.5 0.75…2.5

0.50…2.5 0.50…2.5

[mm2]

1…4 1…2.5 + 1…4

0.75…2.5 (3) 0.75…2.5 (3)

[Nm]

1.2, Cross section per UL/CSA

[AWG]

18…12 (2)

18…14 (3)

Recommended torque

[lb-in]

10.6, Recommended torque

[mm2]

(1) Pozidriv No. 2 / Blade No. 3 screw (2) Use same cross sections (3) Stranded wire only

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

217

Page 219

IEC Industrial Relays

Coil Data 700-K Operating Limits pick-up

[x Us]

0.85…1.1 dropout

[x Us]

0.2…0.75 pick-up

[x Us]

0.8…1.1 9, 12, 24, 110V DC: 0.7…1.25 dropout

[x Us]

0.1…0.75 pick-up

[VA/W]

35/32 hold-in

[VA/W]

5/1.8 pick-up

[W] cold 3.0, warm 2.6 hold-in

[W] cold 3.0, warm 2.6 closing delay

[ms]

15…40 opening delay

[ms]

15…33 opening delay

[ms]

15…28 closing delay

[ms]

18…40 opening delay

[ms]

6…12

With integrated diode closing delay

[ms]

8…12

With external diode opening delay

[ms]

35…50

AC control 50 Hz, 60 Hz, 50/60 Hz

DC control Coil Consumption

AC control 50 Hz, 60 Hz, 50/60 Hz DC control Operating Times

AC With RC module DC

Dimensions - 700-K... Relays Approximate dimensions are shown in millimeters. To convert millimeters to inches multiply by 0.0394. Dimensions are not intended to be used for manufacturing purposes.

(mm)

12 35 45

4

35.2

*)

*) -Minimum distance to grounded parts or walls

49 79

218

180°

54

56

50

25° 25°

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 220

Solid-State Relays

Solid-state Relays Product Overview

Bulletin No.

700-SA

700-SC

Type

Tube Base, Socketed

Miniature, Ice Cube Socketed

Features

Compatible with 700-HN100, 125,108, and 204 socket, LED status, zero-cross switching

Compatible with 700-HN103 or 128 socket, LED Status, and Zerocross AC Switching Options

Load Type

AC (47…63 Hz)

DC

AC (47…63 Hz)

DC

Load Voltage Range

75…264V AC

3…125V DC

75…264V AC

3…52.8V DC or 3…125V DC

Load Current Max. (Continuous)

5A

3A

3A

3 A @ 48V DC or 2 A @ 110V DC

Max. Leakage Current to Load

5 mA @ 100V, 10 mA @ 200V

5 mA @ 125V

5 mA @ 100V AC

10 mA @ 200V AC, 5 mA @ 50V DC or 0.1 mA @ 100V DC

Zero Cross Load Switching

Yes

Not Applicable

Yes (optional)

Not Applicable

Equivalent Electromechanical Relay Contact Arrangement

Form A

Form A

Rated Control (Input) Voltage

5…24V DC

5…24V DC, 100…110V AC, 200/220V AC

5...24V DC

LED Indicator

Yes

Yes (optional)

Yes (optional for 48V DC)

Mounting Method

Panel or DIN with socket

Panel or DIN with socket

Dielectric Strength

1500V AC, 50/60 Hz, 1 min.

1500V AC, 50/60 Hz, 1 min.

Certification cURus, CE, VDE cURus, CE, VDE

Max. Ambient Operating Temperature

-30…80 °C (no condensation)

-30…80 °C (no condensation)

Page

221

226

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

219