Page 201
IEC Industrial Relays
Specifications - 700-CF..., 700S-CF Relays
Contact Ratings, NEMA Min. Contact Rating
Contact Ratings, IEC AC-15 (solenoids, contactors) at rated voltage IEC 60947-5-1
40 °C AC-12 (Control of resistive loads) IEC 60947-5-1 60 °C
DC-12 Switching DC Loads L/R < 1ms, Resistive Loads IEC 60947-5-1
DC-13 IEC 60947-5-1, Solenoids and contactors
Mechanically Linked Contacts (1)
Main Relay Cat. Nos. 700-CF, 700S- CF
Front Mounted Standard Auxiliary Contacts
Main Relay Cat. No. 700-CFB, 700S- CFB
Master Relay Cat. No. 700-CFM
Front Mounted Bifurcated Auxiliary Contacts
Side-mounted Auxiliary Contacts
A600, P600
A600, Q600
A600, Q600
2 x A600, P600
A600, Q600
A600, Q600
17V, 10 mA
17V, 5 mA
8V, 5 mA, 5V, 3 mA
17V, 10 mA
24V
10 A
6A
3A
15 A
3A
6A
48V
10 A
6A
3A
15 A
3A
6A
120V
10 A
6A
3A
15 A
3A
6A
240V
10 A
5A
3A
15 A
3A
5A
400V
6A
3A
2A
7.5 A
2A
3A
480V/500V
2.5 A
1.6 A
1.2 A
5A
1.2 A
1.6 A
600V
1A
1A
0.7 A
2A
0.7 A
1A
690V
1A
1A
0.7 A
2A
0.7 A
1A
10 A
10 A
20 A
10 A
10 A
6A
6A
20 A
6A
6A
10 A
6A
20 A
6A
6A
Ith
20 A
230V
8 kW
400V
14 kW
690V
24 kW
Ith
20 A
230V
8 kW
400V
14 kW
690V
24 kW
24V
15 A
48V
10 A
9A
3.2 A
20 A
3.2 A
3.2 A
110V
6A
3.5 A
1A
8A
1A
1A
220V
1A
0.7 A
0.5 A
1.5 A
0.5 A
0.5 A
440V
0.4 A
0.2 A
0.2 A
0.4 A
0.2 A
0.2 A
24V
5A
5A
2.5 A
5A
2.5 A
5A
48V
3A
3A
1.5 A
3A
1.5 A
2.5 A
110V
1.2 A
1.2 A
0.6 A
1.2 A
0.6 A
0.68 A
220V
0.6 A
0.6 A
0.3 A
0.6 A
0.3 A
0.32 A
440V
0.3 A
0.15 A
0.15 A
0.3 A
0.15 A
0.15 A
State of N.C. Contacts if N.O. contact welds
Location of welded N.O. contacts
Main
Front aux.
Side aux.
Main
Open
Open
Open (2)
Front aux.
Open
Open, (1) Side mounted auxiliary contacts provide “mirror contact” performance with main poles only. (2) Defined in IEC 60947-5-1 annex L. Mechanically linked is a relationship between contacts of opposite types (i.e., N.O. and N.C.).
200
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 202
IEC Industrial Relays
Attribute
Aux./Pneumatic Timer Contact (Front mounted)
Cat. No. 700-CF
Mechanical Life
[Mil]
15
5
Electrical Life
AC-15 (240V, 3 A)
[Mil]
1.5
1.5
Weight
AC Coil
[g]
390, 2 x A4
2 x A4
1 Conductor
[mm2]
1.5…6
0.5…2.5
2 Conductor
[mm2]
1.5…6
0.75…2.5
Max. Wire Size per UL/CSA
[AWG]
16…10
18…14
Tightening Torque
[lb·in]
13.3…17.7
8.9…13.3
Tightening Torque
[N·m]
1.5…2.0
1…1.5
Terminal Cross-Sections Terminal Type Terminal Size per IEC60 947-1 Solid/Stranded (1)
(1) For 16 or more strands, end ferrule is required.
DC Switching Ratings for 700-CF Main Poles in Series (Resistive Load at 60 °C) Attribute
1 pole
2 poles
3 poles
24/48V
15/10 A
25 A
25 A
125V
6A
25 A
25 A
220V
1A
6A
25 A
440V
0.4 A
1A
3A
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
201
Page 203
IEC Industrial Relays
Control Circuit Attribute
Cat. No. 700-CF
Operating Voltage AC 50/60 Hz DC (conventional) (1)
DC (electronic EQ, EW)
DC (electronic EY)
DC (electronic ED)
DC (electronic EA)
Pickup
[x Us]
0.85…1.1
Dropout
[x Us]
0.3…0.6
Pickup
[x Us]
0.8…1.1
Dropout
[x Us]
0.1…0.6
Pickup
[x Us]
0.7...1.25
Dropout
[x Us]
0.3...0.4
Pickup
[x Us]
0.8...1.25
Dropout
[x Us]
0.3...0.4
Pickup
[x Us]
0.7...1.12 (2)
Dropout
[x Us]
0.3...0.4
Pickup
[x Us]
0.8...1.1
Dropout
[x Us]
0.3...0.4
Coil Consumption AC 50/60 Hz
DC (conventional)
DC (electronic EQ, EJ)
DC (electronic EY)
DC (electronic ED)
DC (electronic EA)
Inrush
[VA]
75
Sealed
[VA/W]
9.5/2.7
Inrush
[W]
7.7
Sealed
[W]
6.3
Inrush (avg./ peak)
[W]
10/17
Sealed
[W]
1.7
Inrush (avg./ peak)
[W]
10/17
Sealed
[W]
1.9
Inrush (avg./ peak)
[W]
12/19
Sealed
[W]
2.1
Inrush (avg./ peak)
[W]
14/22
Sealed
[W]
3.0
Pickup Time
[ms]
15…30
Dropout Time
[ms]
10…60
Operating Times AC 50/60 Hz
Pickup Time
[ms]
40…70
Dropout Time
[ms]
7…15
With integrated diode
Opening Delay
[ms]
14...20
With external diode
Opening Delay
[ms]
70...125
Closing Delay
[ms]
25…50
Opening Delay
[ms]
27...45
[ms]
50
DC (conventional)
DC (electronic- EQ, EJ) Min OFF time Max. ripple DC (electronic- EY, ED, EA)
202
± 15% Closing Delay
[ms]
25...50
Opening Delay
[ms]
23...33
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 204
IEC Industrial Relays
Attribute
Cat. No. 700-CF
Min OFF time
[ms]
Max. ripple
50 ± 15%
Latch Attachment Release, 100-FL Coil Consumption
AC
[VA/W]
45/40
DC
[W]
25
[min./max]
0.03…15 s at min. time setting
[ms]
10 at max. time setting
[ms]
70
Contact Signal Duration Timing Attachment Reset Time, 100- ETA, 100-ETB Repeat Accuracy
± 10%
(1) For 9V DC, code ZR, use operating voltage 0.65…1.3 x Us. For 24V DC, code ZJ, DJ, or EJ use operating voltage 0.7…1.25 x Us. (2) At 110V DC, coil code ED has an operating voltage range of 0.7...1.25 x Us.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
203
Page 205
IEC Industrial Relays
General Specifications - 700-CF Relays Cat. No. 700-CF Rated Insulation Voltage Ui IEC UL; CSA
690V 600V 6 kV 2500V
Rated Impulse Strength Uimp
High Test Voltage 1 minute (per IEC 60947Rated Voltage Ue AC DC
115, 230, 400, 500, 690V 24, 48, 110, 220, 440V Short-Circuit Protection gG Fuse 20 A 50/60 Hz, DC
Rated Frequency
Ambient Temperature Storage Operation at nominal current 15% current reduction for AC-12 at > 60 °C
–55…+80 °C (–67…+176 °F) –25…+60 °C (–13…+140 °F) –25…+70 °C (–13…+158 °F) humid-alternating climate, cyclic, per IEC 60068-2-30 and DIN 50 016, 56 cycles 2000 m above mean sea level, per IEC 60 947-4
Corrosion Resistance Altitude
Type of Protection IP2X (IEC 60529 and DIN 40050) Shock Resistance Vibration Resistance Standards Compliance
Certifications in connected state IEC 60068-2: Half sinusoidal shock 11 ms, 30 G (in 3 directions) IEC 60068-2: Static >2 G, in normal position no malfunction <5 G UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1, Meets the material restrictions for European Directive 2002/95/EC - EUcULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, CCC Certified
Utilization Category Table from EN 60947-5-1 Verification of Making and Breaking Capacities of Switching Elements Under Normal Conditions Corresponding to the Utilization Categories (1) Normal Condition of Use Number and Rate of Making and Breaking Break (3) Make (3) Utilization operations Category No. Operating ON time [s] U/Ue cos φ I/Ie U/Ue cos φ operating I/Ie cycles per (6) (5) cycles minute AC-12 (2) 1 1 0.9 1 1 0.9 6050 6 0.05 AC-13 (2) 2 1 0.65 1 1 0.65 6050 6 0.05 (2) AC-14 6 1 0.3 1 1 0.3 6050 6 0.05 10 1 0.3 1 1 0.3 6050 6 0.05 AC-15 (2), - T0.95, - - DC, - T0.95 DC-12 1 1 1 ms 1 1 1 ms 6050 6 0.05 (6) DC-13 1 1 6 x P (4) 1 1 6 x P (4) 6050 6 0.05 (6) (2) DC-14 10 1 15 ms 1 1 15 ms 6050, 0.05 (6) (1) See sub-clause 8.3.3.5.2. (2) Where the break current differs from the make current value, the ON time refers to the make current value after which the current is reduced to the break current value for a suitable period e.g., 0.05 s. (3) For tolerances on test quantities, see sub-clause 8.3.2.2. (4) The value ”6 x P” results from an empirical relationship which is found to represent most DC magnetic loads to an upper limit of P = 50 W, e.g., 6 x P = 300 W. (5) The first 50 operating cycles shall be run at U/Ue = 1.1 with the loads set at Ue. (6) The ON time shall be at least equal to T0.95. Ie Rated operational current, I Current to be made or broken Ue Rated operational voltage, U Voltage before make PUeIe Steady-state power consumption (W) T0.95 Time to reach 95% of the steady-state current (ms)
204
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 206
IEC Industrial Relays
Dimensions - 700-CF... Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Mounting Position AC and DC Control Relay with DC Electronic Coil
(1)
Front View
Side View
(1) May be mounted to 35 mm EN 50 022 DIN Rail.
DC Control Relay
Side View
Front View
AC and DC Control Relays with 12V or 24V DC Electronic Coil Type a b 45 (1-25/32)
700-CF, -CFB, -CFM c 81 (3-3/16)
c1 80.5 (3-11/64)
Ød c2 75.5 (3-3/32)
6 (1/4)
d1
2 screws 4.5 (3/16)
d2 60 (2-23/64)
35 (1-25/64)
DC Control Relays with 48...72V, 110...125V or 220...250V DC Electronic Coil Type a b c
45 (1-25/32)
700-CF, -CFB, -CFM
105 (4-1/8)
c1 80.5 (3-11/64)
Ød c2 75.5 (3-3/32)
6 (1/4)
d1
2 screws 4.5 (3/16)
d2 60 (2-23/64)
35 (1-25/64)
DC Control Relays with Conventional Coil Type 700-CF, -CFB, -CFM a b 45 (1-25/32)
c 81 (3-3/16)
c1 106.5 (4-3/16)
Ød c2 101.5 (4)
6 (1/4)
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
2 screws 4.5 (3/16)
d1 d2 60 (2-23/64)
35 (1-25/64)
205
Page 207
IEC Industrial Relays
Accessories - 700-CF Relays Relay with
206
AC Control Relay
DC Control Relay mm
(inches)
mm
(inches)
Auxiliary Contact for Front Mounting
2- or 4-pole c/c1 + 39
(c/c1 + 1 – 37/64)
c/c1 + 39 c/c1 + 1 – 37/64)
Auxiliary Contact for Side Mounting
1- or 2-pole a+9
(a + 23/64)
a+9
(a + 23/64)
Pneumatic Timing Module, c/c1 + 58
(c/c1 + 2 – 23/64), - Solid-state Timing Module on coil terminal side b + 24
(b + 15/16)
b + 24
(b + 15/16)
Mechanical Latching, c/c1 + 61
(c/c1 + 2 – 31/64), - DC Interface on coil terminal side b+9
(b + 23/64), - Surge Suppressor on coil terminal side b+3
(b + 1/8)
b+3
(b + 1/8)
Labelling with:
label sheet
+0
(+0)
+0
(+0), marking tag with cover
+0
(+0)
+0
(+0), marking tag carrier for System V4/V5
+5.5
(+7/32)
+5.5
(+7/32), marking tag carrier for System Bull. 1492W
+5.5
(+7/32)
+5.5
(+7/32)
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 208
IEC Industrial Relays
700S-CF Control Relays The 700S-CF Safety Control Relay provides mechanically or mirror contact performance, which are required in feedback circuits for safety applications. Bifurcated contacts are ideal for low energy feedback safety circuits where high contact reliability is required. • IEC industrial safety relay • Mechanically linked contacts as per IEC 60947-5-1 • Third party certification SUVA • Red cover and mechanically linked contact symbol on front face • Gold plated, bifurcated version for low level switching applications • Permanently fixed front mounted auxiliary contact block
Type CF and CFB Safety Control Relays, 8-Pole AC Coil Voltage (Ratings for 700S-CF Only) AC-12
AC-15
Contacts Connection Diagrams
Ith [A]
Ie [A]
Main Contacts 40 60 24/ °C °C 48V
120 V
240 V
400 V
500 V
600 V
690 V
20
10
10
6
2.5
1
1
20
10
Auxiliary Contacts
Standard Contacts (Main) Gold-Plated Bifurcated (Front) Cat. No.
Gold-Plated Bifurcated, All Contacts Cat. No. (1)
N.O.
N.C.
4
4
700SCF440⊗BC
700SCFB440⊗C
5
3
700SCF530⊗BC
700SCFB530⊗C
6
2
700SCF620⊗BC
700SCFB620⊗C
Main Contacts
Adder Deck Contacts
10
6
6
6
5
3
1.6
1
1
(1) Ratings for 700S-CFB are on Specifications
⊗ AC Coil Voltage Code The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700S-CF440⊗BC becomes Cat. No. 700S-CF440DBC for 120V, 60 Hz. [V]
12
24
32
36
42
48
100
100... 110
110
120
127
200
200... 220
208
208... 240
220... 230
50 Hz
R
K
V
W
X
Y
KP, D
P
S
KG
L, - F
60 Hz
Q
J, V, X, KP, D, - KG
H
L, 50/60, KJ, - - KY
KP, KD, - KG
KL, - KL
Hz [V]
230
230... 240
240
277
347
380
380... 400
400
400... 415
440
480
500
550
600
50 Hz, VA
T, - - N, G
B, M
C, 60 Hz, - A
T
I
E, - - N
B, - C
50/60 Hz KF, KA, - - - KN, KB, - - - Rockwell Automation Publication 700-TD552B-EN-P - August 2018
207
Page 209
IEC Industrial Relays
Type CF and CFB Safety Control Relays, 8-Pole DC Coil Voltage (Ratings for 700S-CF Only) AC-12
AC-15
Ith [A]
Ie [A]
Contacts Connection Diagrams
Main Contacts
Auxiliary Contacts
Gold Plated Bifurcated All Contacts Cat. No.(1)
40 °C
60 °C
24/48V
120V
240V
400V
500V
600V
690V
No. of N.O. Contacts
No. of N.C. Contacts
20
20
10
10
10
6
2.5
1
1
4
4
700SCF440⊗BC
700SCFB440⊗C
5
3
700SCF530⊗BC
700SCFB530⊗C
6
2
700SCF620⊗BC
700SCFB620⊗C
Main Contacts
Adder Deck Contacts
Standard Contacts (Main) GoldPlated Bifurcated (Front) Cat. No.
10
6
6
6
5
3
1.6
1
1
(1) Ratings for 700S-CFB are on Specifications
⊗ DC Coil Voltage Code The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700S-CFB440⊗C becomes Cat. No. 700S-CFB440EJC for 24V DC, electronic with diode. [V]
9
12
24
36
48
48... 72
60
64
72
80
110
110... 115 125
125
220
220... 250
230
250
Electronic with diode, EQ
EJ
EW, EY, - - - - ED, - - EA, - Electronic with diode/ Quick Pick-up, - QJ, - - - - - - - - - - - - - - 208
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 210
IEC Industrial Relays
Assignment of Contacts Safety Control Relays with Front-mount Auxiliary Contacts, 8-Pole AC or DC Coil Voltage
A1
53 61 71 81
53 61 71 83
53 61 73 83
54 62 72 82
54 62 72 84
54 62 74 84
A1
13 21 33 43
K1
13 21 33 43
K1 A2
13 21 33 43
A2
14 22 34 44
K1 A2
14 22 34 44
700S-CF440… 700S-CFB440…
A1
14 22 34 44
700S-CF530… 700S-CFB530…
700S-CF620… 700S-CFB620…
Specifications - 700S-CF Relays For more 700S-CF Specifications, see Specifications - 700-CF..., 700S-CF Relays on page 200.
Mechanical Life
Cat. No. 700S-CF
Aux. Contact (Front-mounted)
[Mil]
15
15
Electrical Life
AC-15 (240V, 3 A)
[Mil]
1.5
1.5
Weight
AC Coil
[g]
390, 2 x A4
2 x A4
Terminal Cross-Sections Terminal Type Terminal Size per IEC 947-1 1 Conductor
[mm2]
1.5…6
0.5…2.5
2 Conductor
[mm2]
1.5…6
0.75…2.5
Max. Wire Size per UL/CSA
[AWG]
16…10
18…14
Tightening Torque
[lb•in]
13.3…22
8.9…13.3
Tightening Torque
[N•m]
1.5…2.5
1…1.5
Solid/ Stranded (1)
Standards Compliance
Certifications
UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1, Meets the material restrictions for European Directive 2002/95/EC - EU-RoHS cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, CCC Certified
(1) For 16 or more strands, end ferrule is required
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
209