Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 21 of 25

Relay and Timer Specifications, Bulletin Number 700, pages 201 to 210

Pages 201 to 210 of 250

The original document is the PDF (23 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX

Page 201

IEC Industrial Relays

Specifications - 700-CF..., 700S-CF Relays

Contact Ratings, NEMA Min. Contact Rating

Contact Ratings, IEC AC-15 (solenoids, contactors) at rated voltage IEC 60947-5-1

40 °C AC-12 (Control of resistive loads) IEC 60947-5-1 60 °C

DC-12 Switching DC Loads L/R < 1ms, Resistive Loads IEC 60947-5-1

DC-13 IEC 60947-5-1, Solenoids and contactors

Mechanically Linked Contacts (1)

Main Relay Cat. Nos. 700-CF, 700S- CF

Front Mounted Standard Auxiliary Contacts

Main Relay Cat. No. 700-CFB, 700S- CFB

Master Relay Cat. No. 700-CFM

Front Mounted Bifurcated Auxiliary Contacts

Side-mounted Auxiliary Contacts

A600, P600

A600, Q600

A600, Q600

2 x A600, P600

A600, Q600

A600, Q600

17V, 10 mA

17V, 5 mA

8V, 5 mA, 5V, 3 mA

17V, 10 mA

24V

10 A

6A

3A

15 A

3A

6A

48V

10 A

6A

3A

15 A

3A

6A

120V

10 A

6A

3A

15 A

3A

6A

240V

10 A

5A

3A

15 A

3A

5A

400V

6A

3A

2A

7.5 A

2A

3A

480V/500V

2.5 A

1.6 A

1.2 A

5A

1.2 A

1.6 A

600V

1A

1A

0.7 A

2A

0.7 A

1A

690V

1A

1A

0.7 A

2A

0.7 A

1A

10 A

10 A

20 A

10 A

10 A

6A

6A

20 A

6A

6A

10 A

6A

20 A

6A

6A

Ith

20 A

230V

8 kW

400V

14 kW

690V

24 kW

Ith

20 A

230V

8 kW

400V

14 kW

690V

24 kW

24V

15 A

48V

10 A

9A

3.2 A

20 A

3.2 A

3.2 A

110V

6A

3.5 A

1A

8A

1A

1A

220V

1A

0.7 A

0.5 A

1.5 A

0.5 A

0.5 A

440V

0.4 A

0.2 A

0.2 A

0.4 A

0.2 A

0.2 A

24V

5A

5A

2.5 A

5A

2.5 A

5A

48V

3A

3A

1.5 A

3A

1.5 A

2.5 A

110V

1.2 A

1.2 A

0.6 A

1.2 A

0.6 A

0.68 A

220V

0.6 A

0.6 A

0.3 A

0.6 A

0.3 A

0.32 A

440V

0.3 A

0.15 A

0.15 A

0.3 A

0.15 A

0.15 A

State of N.C. Contacts if N.O. contact welds

Location of welded N.O. contacts

Main

Front aux.

Side aux.

Main

Open

Open

Open (2)

Front aux.

Open

Open, (1) Side mounted auxiliary contacts provide “mirror contact” performance with main poles only. (2) Defined in IEC 60947-5-1 annex L. Mechanically linked is a relationship between contacts of opposite types (i.e., N.O. and N.C.).

200

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 202

IEC Industrial Relays

Attribute

Aux./Pneumatic Timer Contact (Front mounted)

Cat. No. 700-CF

Mechanical Life

[Mil]

15

5

Electrical Life

AC-15 (240V, 3 A)

[Mil]

1.5

1.5

Weight

AC Coil

[g]

390, 2 x A4

2 x A4

1 Conductor

[mm2]

1.5…6

0.5…2.5

2 Conductor

[mm2]

1.5…6

0.75…2.5

Max. Wire Size per UL/CSA

[AWG]

16…10

18…14

Tightening Torque

[lb·in]

13.3…17.7

8.9…13.3

Tightening Torque

[N·m]

1.5…2.0

1…1.5

Terminal Cross-Sections Terminal Type Terminal Size per IEC60 947-1 Solid/Stranded (1)

(1) For 16 or more strands, end ferrule is required.

DC Switching Ratings for 700-CF Main Poles in Series (Resistive Load at 60 °C) Attribute

1 pole

2 poles

3 poles

24/48V

15/10 A

25 A

25 A

125V

6A

25 A

25 A

220V

1A

6A

25 A

440V

0.4 A

1A

3A

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

201

Page 203

IEC Industrial Relays

Control Circuit Attribute

Cat. No. 700-CF

Operating Voltage AC 50/60 Hz DC (conventional) (1)

DC (electronic EQ, EW)

DC (electronic EY)

DC (electronic ED)

DC (electronic EA)

Pickup

[x Us]

0.85…1.1

Dropout

[x Us]

0.3…0.6

Pickup

[x Us]

0.8…1.1

Dropout

[x Us]

0.1…0.6

Pickup

[x Us]

0.7...1.25

Dropout

[x Us]

0.3...0.4

Pickup

[x Us]

0.8...1.25

Dropout

[x Us]

0.3...0.4

Pickup

[x Us]

0.7...1.12 (2)

Dropout

[x Us]

0.3...0.4

Pickup

[x Us]

0.8...1.1

Dropout

[x Us]

0.3...0.4

Coil Consumption AC 50/60 Hz

DC (conventional)

DC (electronic EQ, EJ)

DC (electronic EY)

DC (electronic ED)

DC (electronic EA)

Inrush

[VA]

75

Sealed

[VA/W]

9.5/2.7

Inrush

[W]

7.7

Sealed

[W]

6.3

Inrush (avg./ peak)

[W]

10/17

Sealed

[W]

1.7

Inrush (avg./ peak)

[W]

10/17

Sealed

[W]

1.9

Inrush (avg./ peak)

[W]

12/19

Sealed

[W]

2.1

Inrush (avg./ peak)

[W]

14/22

Sealed

[W]

3.0

Pickup Time

[ms]

15…30

Dropout Time

[ms]

10…60

Operating Times AC 50/60 Hz

Pickup Time

[ms]

40…70

Dropout Time

[ms]

7…15

With integrated diode

Opening Delay

[ms]

14...20

With external diode

Opening Delay

[ms]

70...125

Closing Delay

[ms]

25…50

Opening Delay

[ms]

27...45

[ms]

50

DC (conventional)

DC (electronic- EQ, EJ) Min OFF time Max. ripple DC (electronic- EY, ED, EA)

202

± 15% Closing Delay

[ms]

25...50

Opening Delay

[ms]

23...33

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 204

IEC Industrial Relays

Attribute

Cat. No. 700-CF

Min OFF time

[ms]

Max. ripple

50 ± 15%

Latch Attachment Release, 100-FL Coil Consumption

AC

[VA/W]

45/40

DC

[W]

25

[min./max]

0.03…15 s at min. time setting

[ms]

10 at max. time setting

[ms]

70

Contact Signal Duration Timing Attachment Reset Time, 100- ETA, 100-ETB Repeat Accuracy

± 10%

(1) For 9V DC, code ZR, use operating voltage 0.65…1.3 x Us. For 24V DC, code ZJ, DJ, or EJ use operating voltage 0.7…1.25 x Us. (2) At 110V DC, coil code ED has an operating voltage range of 0.7...1.25 x Us.

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

203

Page 205

IEC Industrial Relays

General Specifications - 700-CF Relays Cat. No. 700-CF Rated Insulation Voltage Ui IEC UL; CSA

690V 600V 6 kV 2500V

Rated Impulse Strength Uimp

High Test Voltage 1 minute (per IEC 60947Rated Voltage Ue AC DC

115, 230, 400, 500, 690V 24, 48, 110, 220, 440V Short-Circuit Protection gG Fuse 20 A 50/60 Hz, DC

Rated Frequency

Ambient Temperature Storage Operation at nominal current 15% current reduction for AC-12 at > 60 °C

–55…+80 °C (–67…+176 °F) –25…+60 °C (–13…+140 °F) –25…+70 °C (–13…+158 °F) humid-alternating climate, cyclic, per IEC 60068-2-30 and DIN 50 016, 56 cycles 2000 m above mean sea level, per IEC 60 947-4

Corrosion Resistance Altitude

Type of Protection IP2X (IEC 60529 and DIN 40050) Shock Resistance Vibration Resistance Standards Compliance

Certifications in connected state IEC 60068-2: Half sinusoidal shock 11 ms, 30 G (in 3 directions) IEC 60068-2: Static >2 G, in normal position no malfunction <5 G UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1, Meets the material restrictions for European Directive 2002/95/EC - EUcULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, CCC Certified

Utilization Category Table from EN 60947-5-1 Verification of Making and Breaking Capacities of Switching Elements Under Normal Conditions Corresponding to the Utilization Categories (1) Normal Condition of Use Number and Rate of Making and Breaking Break (3) Make (3) Utilization operations Category No. Operating ON time [s] U/Ue cos φ I/Ie U/Ue cos φ operating I/Ie cycles per (6) (5) cycles minute AC-12 (2) 1 1 0.9 1 1 0.9 6050 6 0.05 AC-13 (2) 2 1 0.65 1 1 0.65 6050 6 0.05 (2) AC-14 6 1 0.3 1 1 0.3 6050 6 0.05 10 1 0.3 1 1 0.3 6050 6 0.05 AC-15 (2), - T0.95, - - DC, - T0.95 DC-12 1 1 1 ms 1 1 1 ms 6050 6 0.05 (6) DC-13 1 1 6 x P (4) 1 1 6 x P (4) 6050 6 0.05 (6) (2) DC-14 10 1 15 ms 1 1 15 ms 6050, 0.05 (6) (1) See sub-clause 8.3.3.5.2. (2) Where the break current differs from the make current value, the ON time refers to the make current value after which the current is reduced to the break current value for a suitable period e.g., 0.05 s. (3) For tolerances on test quantities, see sub-clause 8.3.2.2. (4) The value ”6 x P” results from an empirical relationship which is found to represent most DC magnetic loads to an upper limit of P = 50 W, e.g., 6 x P = 300 W. (5) The first 50 operating cycles shall be run at U/Ue = 1.1 with the loads set at Ue. (6) The ON time shall be at least equal to T0.95. Ie Rated operational current, I Current to be made or broken Ue Rated operational voltage, U Voltage before make PUeIe Steady-state power consumption (W) T0.95 Time to reach 95% of the steady-state current (ms)

204

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 206

IEC Industrial Relays

Dimensions - 700-CF... Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

Mounting Position AC and DC Control Relay with DC Electronic Coil

(1)

Front View

Side View

(1) May be mounted to 35 mm EN 50 022 DIN Rail.

DC Control Relay

Side View

Front View

AC and DC Control Relays with 12V or 24V DC Electronic Coil Type a b 45 (1-25/32)

700-CF, -CFB, -CFM c 81 (3-3/16)

c1 80.5 (3-11/64)

Ød c2 75.5 (3-3/32)

6 (1/4)

d1

2 screws 4.5 (3/16)

d2 60 (2-23/64)

35 (1-25/64)

DC Control Relays with 48...72V, 110...125V or 220...250V DC Electronic Coil Type a b c

45 (1-25/32)

700-CF, -CFB, -CFM

105 (4-1/8)

c1 80.5 (3-11/64)

Ød c2 75.5 (3-3/32)

6 (1/4)

d1

2 screws 4.5 (3/16)

d2 60 (2-23/64)

35 (1-25/64)

DC Control Relays with Conventional Coil Type 700-CF, -CFB, -CFM a b 45 (1-25/32)

c 81 (3-3/16)

c1 106.5 (4-3/16)

Ød c2 101.5 (4)

6 (1/4)

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

2 screws 4.5 (3/16)

d1 d2 60 (2-23/64)

35 (1-25/64)

205

Page 207

IEC Industrial Relays

Accessories - 700-CF Relays Relay with

206

AC Control Relay

DC Control Relay mm

(inches)

mm

(inches)

Auxiliary Contact for Front Mounting

2- or 4-pole c/c1 + 39

(c/c1 + 1 – 37/64)

c/c1 + 39 c/c1 + 1 – 37/64)

Auxiliary Contact for Side Mounting

1- or 2-pole a+9

(a + 23/64)

a+9

(a + 23/64)

Pneumatic Timing Module, c/c1 + 58

(c/c1 + 2 – 23/64), - Solid-state Timing Module on coil terminal side b + 24

(b + 15/16)

b + 24

(b + 15/16)

Mechanical Latching, c/c1 + 61

(c/c1 + 2 – 31/64), - DC Interface on coil terminal side b+9

(b + 23/64), - Surge Suppressor on coil terminal side b+3

(b + 1/8)

b+3

(b + 1/8)

Labelling with:

label sheet

+0

(+0)

+0

(+0), marking tag with cover

+0

(+0)

+0

(+0), marking tag carrier for System V4/V5

+5.5

(+7/32)

+5.5

(+7/32), marking tag carrier for System Bull. 1492W

+5.5

(+7/32)

+5.5

(+7/32)

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 208

IEC Industrial Relays

700S-CF Control Relays The 700S-CF Safety Control Relay provides mechanically or mirror contact performance, which are required in feedback circuits for safety applications. Bifurcated contacts are ideal for low energy feedback safety circuits where high contact reliability is required. • IEC industrial safety relay • Mechanically linked contacts as per IEC 60947-5-1 • Third party certification SUVA • Red cover and mechanically linked contact symbol on front face • Gold plated, bifurcated version for low level switching applications • Permanently fixed front mounted auxiliary contact block

Type CF and CFB Safety Control Relays, 8-Pole AC Coil Voltage (Ratings for 700S-CF Only) AC-12

AC-15

Contacts Connection Diagrams

Ith [A]

Ie [A]

Main Contacts 40 60 24/ °C °C 48V

120 V

240 V

400 V

500 V

600 V

690 V

20

10

10

6

2.5

1

1

20

10

Auxiliary Contacts

Standard Contacts (Main) Gold-Plated Bifurcated (Front) Cat. No.

Gold-Plated Bifurcated, All Contacts Cat. No. (1)

N.O.

N.C.

4

4

700SCF440⊗BC

700SCFB440⊗C

5

3

700SCF530⊗BC

700SCFB530⊗C

6

2

700SCF620⊗BC

700SCFB620⊗C

Main Contacts

Adder Deck Contacts

10

6

6

6

5

3

1.6

1

1

(1) Ratings for 700S-CFB are on Specifications

⊗ AC Coil Voltage Code The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700S-CF440⊗BC becomes Cat. No. 700S-CF440DBC for 120V, 60 Hz. [V]

12

24

32

36

42

48

100

100... 110

110

120

127

200

200... 220

208

208... 240

220... 230

50 Hz

R

K

V

W

X

Y

KP, D

P

S

KG

L, - F

60 Hz

Q

J, V, X, KP, D, - KG

H

L, 50/60, KJ, - - KY

KP, KD, - KG

KL, - KL

Hz [V]

230

230... 240

240

277

347

380

380... 400

400

400... 415

440

480

500

550

600

50 Hz, VA

T, - - N, G

B, M

C, 60 Hz, - A

T

I

E, - - N

B, - C

50/60 Hz KF, KA, - - - KN, KB, - - - Rockwell Automation Publication 700-TD552B-EN-P - August 2018

207

Page 209

IEC Industrial Relays

Type CF and CFB Safety Control Relays, 8-Pole DC Coil Voltage (Ratings for 700S-CF Only) AC-12

AC-15

Ith [A]

Ie [A]

Contacts Connection Diagrams

Main Contacts

Auxiliary Contacts

Gold Plated Bifurcated All Contacts Cat. No.(1)

40 °C

60 °C

24/48V

120V

240V

400V

500V

600V

690V

No. of N.O. Contacts

No. of N.C. Contacts

20

20

10

10

10

6

2.5

1

1

4

4

700SCF440⊗BC

700SCFB440⊗C

5

3

700SCF530⊗BC

700SCFB530⊗C

6

2

700SCF620⊗BC

700SCFB620⊗C

Main Contacts

Adder Deck Contacts

Standard Contacts (Main) GoldPlated Bifurcated (Front) Cat. No.

10

6

6

6

5

3

1.6

1

1

(1) Ratings for 700S-CFB are on Specifications

⊗ DC Coil Voltage Code The cat. no. as listed is incomplete. Select a coil voltage code from the table below to complete the cat. no. Example: Cat. No. 700S-CFB440⊗C becomes Cat. No. 700S-CFB440EJC for 24V DC, electronic with diode. [V]

9

12

24

36

48

48... 72

60

64

72

80

110

110... 115 125

125

220

220... 250

230

250

Electronic with diode, EQ

EJ

EW, EY, - - - - ED, - - EA, - Electronic with diode/ Quick Pick-up, - QJ, - - - - - - - - - - - - - - 208

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 210

IEC Industrial Relays

Assignment of Contacts Safety Control Relays with Front-mount Auxiliary Contacts, 8-Pole AC or DC Coil Voltage

A1

53 61 71 81

53 61 71 83

53 61 73 83

54 62 72 82

54 62 72 84

54 62 74 84

A1

13 21 33 43

K1

13 21 33 43

K1 A2

13 21 33 43

A2

14 22 34 44

K1 A2

14 22 34 44

700S-CF440… 700S-CFB440…

A1

14 22 34 44

700S-CF530… 700S-CFB530…

700S-CF620… 700S-CFB620…

Specifications - 700S-CF Relays For more 700S-CF Specifications, see Specifications - 700-CF..., 700S-CF Relays on page 200.

Mechanical Life

Cat. No. 700S-CF

Aux. Contact (Front-mounted)

[Mil]

15

15

Electrical Life

AC-15 (240V, 3 A)

[Mil]

1.5

1.5

Weight

AC Coil

[g]

390, 2 x A4

2 x A4

Terminal Cross-Sections Terminal Type Terminal Size per IEC 947-1 1 Conductor

[mm2]

1.5…6

0.5…2.5

2 Conductor

[mm2]

1.5…6

0.75…2.5

Max. Wire Size per UL/CSA

[AWG]

16…10

18…14

Tightening Torque

[lb•in]

13.3…22

8.9…13.3

Tightening Torque

[N•m]

1.5…2.5

1…1.5

Solid/ Stranded (1)

Standards Compliance

Certifications

UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1, Meets the material restrictions for European Directive 2002/95/EC - EU-RoHS cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked, CCC Certified

(1) For 16 or more strands, end ferrule is required

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

209