The text of a spec sheet · part 5 of 25
Relay and Timer Specifications, Bulletin Number 700, pages 41 to 50
Pages 41 to 50 of 250
The original document is the PDF (23 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX
Page 41
General Purpose Relays
Photo
Description
Pkg. Qty.
Cat. No.
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Retainer Clip for Cat. Nos. 700-HN103, -HN104 and -HN128 Sockets with 700-HC Relays. Secures relay in socket.(1)
10
700-HN114
Plastic Retainer and Ejection Lever For use with the 700-HN104 Sockets for 700-HC relays. Built-in ability to accept 1492 Snap-in Markers
10
700-HN124
(1) See 700-HC Miniature Square Base Relay, Socket, and Retainer Clip Reference Chart
Description
Photo
Relay Identification Snap-in Markers Snap-in markers fit on top of product covers. Squares slip into molded slot on top of product cover.
Pkg. Qty. Cat. No. 5
1492-MS5X12
5
1492-MS6X9
5
1492-MS6X12
5
1492-MS8X9
5
1492-MS8X12
100
1492-MP-Blank
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Markers, Used for terminal identification
50
700-N41
Socket and Retainer Clip Reference Relay Type
700-HC
Socket Cat. No.
Retainer Clip Cat. No.
700-HN103
700-HN114
700-HN128
700-HN114
700-HN104
700-HN114 or 700-HN124
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
41
Page 42
General Purpose Relays
Specifications- 700-HC Relays Attribute
700-HC Electrical Ratings
Pilot Duty Rating
(1)
NEMA C300, R300
Rated Thermal Current (Ith)
7 A and 10 A
Rated Insulation Voltage (Ui)
250V IEC – 300V UL/CSA 700-HC_4
Hp
700-HC22
Hp
Inductive 120V AC
15 A
1.5 A
1/8
15 A
1.5 A
1/3
240V AC
7.5 A
0.75 A
1/3
7.5 A
0.75 A
3/4
Contacts General-purpose
7 A, 277V AC
10 A, 277V AC
Resistive
7 A, 30V DC
10 A, 24V DC 100 mW (10V, 10 mA) - Silver Contacts 50 mW (5V, 10 mA, or 25V, 2 mA) - Gold Contacts
Min. Low Energy Permissible Load
Permissible Coil Voltage Variation
Coil Consumption ±10%
AC Coils
Pickup:
80…110% of nom voltage at 50 Hz 80…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC
Must Dropout Voltage:
20% of nom voltage at AC 10% of nom voltage at DC
50 Hz
60 Hz
Inrush
2.2VA
1.6VA
Sealed
1.3VA
1.1VA
DC Coils
1.0 W 20% of VA (AC)
Max. Allowable Leakage
10% of W (DC) Design Specification/Test Requirements Electrical Dielectric Withstand Voltage
Pole-to-Pole
2000V
Contact to Coil
2000V
Electrical Life (Cycles)
100 000 min Mechanical
Degree of Protection (Open Type) IEC 529
IP 20 (Guarded Terminal Sockets)
Mechanical lifecycles
20 x 106 (AC), 50 x 106 (DC)
Switching Frequency Operations
1800/HR
Coil Voltages Operating Time (ms)
See Product Selection Max. Pickup
10
Max. Dropout
3
Maximum Operating Rate
8 cycles/s Environmental
Temperature Altitude Insulating Material Enclosure Contact Material
Operating
–30…+55 °C (–22…+131 °F)
Storage
–55…+85 °C (–67…+185 °F) 2000 m (6560 ft) Molded High Dielectric Material Transparent Dust Cover AgNi (700-HC2), AgNi + 5 μm All (700-HC1)
Terminal Markings on Socket
In accordance with EN50 0005
Sockets
700-HN103, -HN128, -HN104
Certifications cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), cULus Listed when used with 700- HN103, -HN104, and -HN128 sockets (File No. E14843, Guide NRNT/NRNT7), CE Marked, LR Certified
Standards
UL 508, CSA 22.2 No. 14, EN 61810-1
(1) See General Information on page 3
42
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 43
General Purpose Relays
Dimensions, 700-HC Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
37.2 (1.46)
36.7 (1.44)
5.6 (0.22)
6.1 (0.24) 20.7 (0.82)
27.7 (1.09)
20.7 (0.82)
27.7 (1.09)
700-HC Relay (Two-Pole)
700-HC Relay (Four-Pole) 27.0 (1.06)
60.9 (2.40) 21.5 (0.85)
76.0 (2.99)
35.6 (1.40) 3.2 (0.13) 18.9 (0.74) 34.9 (1.37)
32.0 (1.26) 35.5 (1.40) 2.5 (0.10)
Cat. No. 700-HN104
Single Wire: 0.2 mm2…2.5 mm2 (24 AWG…14 AWG), Double Wire: 0.2 …2.5 mm2 (24 AWG…14 AWG), Qty. 2 wires Wire Type: solid or stranded, copper only, Strip Length: 7 mm (9/32 in.), Torque: 0.5 N•m (4.4 lb•in)
30.0 (1-3/16) 6.1 (15/64)
Panel Mounting
24.5 (31/32)
28.9 (1-9/64)
8
7
6
5
4
3
2
1
67.0 (2-5/8)
4.2 (5/32)
14 12
#4-40 M3
30.0 (1-11/64)
24.9 (57/64) 21.1 (53/64)
13 11
10
62.0 (2-15/64)
65.0 (2-9/16)
9
26.0 (1-1/64)
Cat. No. 700-HN103
Cat. No. 700-HN128
Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…14 AWG) Double Wire: 0.2…2 x 1.5 mm2 (24 AWG…16 AWG), Qty. 2 wires Wire Type: Solid or Stranded, Copper only Strip Length: 8 mm (5/16 in.), Torque: 0.5 N•m (4.4 lb•in)
Wire Size: 2 x 1.5 mm2 (#2-16 AWG…#1-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Toque: 0.8 N•m (7 lb•in
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
43
Page 44
General Purpose Relays
700-HK Slim Line Relay • 8 A/16 A contact ratings • DPDT/SPDT • Plug-in blade-style terminals • Retainer clip with sockets • Options: LED, push-to-test and manual override, socket-mounted surge suppressor module, or timer module • Standard ON/OFF flag indicator • Relay faceplate accepts optional 1492 snap-in markers • Choice of standard silver/nickel contacts or silver/nickel with gold plated contacts • Maximum duty version available Photo
Description
SPDT 1-Pole 1 Form C AgNi Contacts
Contact Rating
Wiring Diagrams U.S./Canada
International
16 A
Input
700-HN121, 700-HN221, 700-HN223
Socket
DPDT 2-Pole 2 Form C AgNi Contacts
700-HN121, 700-HN221, 700-HN223
8A
Input
Socket
44
700-HN122, 700-HN222, 700-HN224
700-HN122, 700-HN222, 700-HN224
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Coil Voltage
Cat. No.
6V AC
700-HK36A06
12V AC
700-HK36A12
24V AC
700-HK36A24
120V AC
700-HK36A1
240V AC
700-HK36A2
6V DC
700-HK36Z06
12V DC
700-HK36Z12
24V DC
700-HK36Z24
48V DC
700-HK36Z48
110V DC
700-HK36Z1
6V AC
700-HK32A06
12V AC
700-HK32A12
24V AC
700-HK32A24
120V AC
700-HK32A1
240V AC
700-HK32A2
6V DC
700-HK32Z06
12V DC
700-HK32Z12
24V DC
700-HK32Z24
48V DC
700-HK32Z48
110V DC
700-HK32Z1
Page 45
General Purpose Relays
Accessories- 700-HK Relays Photo
Description
Pkg. Qty.
Cat. No.
Screw Terminal Socket, Panel or DIN Rail Mounting 5-blade miniature socket with 10 A rating for use with 1-pole, 700-HK relays. Accepts forked lug conductors. Socket includes a retainer clip.
10
700-HN121
Screw Terminal Socket, Panel or DIN Rail Mounting 5-blade miniature socket with 16 A rating for use with 1-pole, 700-HK relays. Retainer clips are packaged separately with socket. Guarded terminal construction and compatible with optional plug-in module accessories.
10
700-HN221
Spring Clamp Terminal Socket, Panel or DIN Rail Mounting 5-blade miniature socket for use with 1-pole, 700-HK relays.
10
700-HN223
Screw Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket with 5 A rating for use with 2-pole, 700-HK relays. Accepts forked lug conductors. This socket includes a retainer clip.
10
700-HN122
Screw Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket with 8 A rating for use with 2-pole, 700-HK relays. Retainer clips are packaged separately with socket. Guarded terminal construction and compatible with optional plug-in module accessories.
10
700-HN222
Spring Clamp Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket for use with 2-pole 700-HK relays.
10
700-HN224
Flange Mount Adapter Used for panel-mounting bulletin 700-HK relays. Order must be for 10 adapters or multiples of 10.
10
700-HN226
35 mm Rail Mount Adapter Mounts bulletin 700-HK relays to a 35 mm rail. Order must be for 10 adapters or multiples of 10.
10
700-HN227
Socket Retainer Clip and Ejection Lever For use with 700-HN22, -HN222, -HN223, and -HN224 sockets. Orders must be for 10 clips or multiples of 10.
10
700-HN229
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
45
Page 46
General Purpose Relays
Specifications- 700-HK Relays Attribute
700-HK Electrical Ratings
Rated Thermal Current (Ith)
1-Pole, 1 CO, SPDT, 16 A
2-Pole, 2 CO, DPDT, 8 A
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA 120V AC
AC-15, 6.2 A B300 Pilot Duty, 3 A A300 (700-HKM_) 1/3 Hp (0.24 kW) 1-phase
120V AC
AC-15, 2.9 A B300 Pilot Duty, 3.0 A 1/4 Hp (0.18 kW), 1-phase
240V AC
AC-15, 3.1 A B300 Pilot Duty, 1.5 A A300(700-HKM_) 3/4 Hp (0.55 kW), 1-phase
240V AC
AC-15, 1.4 A B300 Pilot Duty, 1.5 A 1/2 Hp (0.37 kW), 1-phase
230V AC
0.55 kW, 1-phase
230V AC
0.37 kW, 1-phase
24V DC
DC-13, 5.0 A
24V DC
DC-13, 3.0 A
125V DC
DC-13, 0.2 A / R300 Pilot Duty, 0.22 A
125V DC
DC-13, 0.2 A / R300 Pilot Duty, 0.22 A
250V DC
DC-13, 0.1 A / R300 Pilot Duty, 0.11 A
5 A, 250V AC
DC-13, 0.1 A / R300 Pilot Duty, 0.11 A
230V AC
AC-1, 16 A
230V AC
AC-1, 8 A
277V AC
16 A, General Use
277V AC
8 A, General Use
30V DC
DC-1, 12 A / 10 A, Resistive
30V DC
DC-1, 6 A / 6 A, Resistive
Inductive V AC
Contacts Inductive V DC
Resistive Make, Break , and Continuous Min. Permissible Contact Ratings
Permissible Coil Voltage Variation
Pickup: holding Voltage: Must Dropout Voltage:
300 mW (5V/60 mA or 60V/5 mA) for AgNi Contacts (700-HK3_) 50 mW (5V/10 mA or 25V/2 mA) for AgNi + Gold Contacts (700-HKX_) 500 mW (100V/5 mA or 5V/100 mA) for AgSnO2 Contacts (700-HKM_) 80…110% of Nominal Voltage at 50/60 Hz, 73...110% of Nominal Voltage at DC 80% of Nominal V AC at 50/60 Hz, 40% of Nominal V DC 20% of Nominal V AC at 50/60 Hz, 10% Nominal V DC
Power Consumption
1.2V A (V AC Coils), 0.5 W (V DC Coils)
Coil Voltages
See Overview/Product Selection Design Specification/Test Requirements
Dielectric Withstand Voltage
Pole to Pole (VRMS) Contact to Coil (VRMS)
2000V AC 4000V AC Mechanical
Degree of Protection
IP 20 (guarded terminal sockets), RT II, Flux-proof (Relay) 10 x 106
Mechanical Life Operations 230V AC, 16 A Resistive: 100 000 min. 277V AC, 16 A Resistive: 30 000 min. 30V DC, 10 A Resistive: 30 000 min. B300, R300, Hp (kW): 6000 min. A300 (700-HKM_): 100,000 min.
Electrical Lifecycles
Mechanical: 18,000 cycles/hr. Electrical: 900 cycles/hr.
Switching Frequency Operating Time at Nominal Voltage at 20 °C (ms)
230V AC, 8 A Resistive: 100 000 min. 277V AC, 8 A Resistive: 30 000 min. 30V DC, 6 A Resistive: 30 000 min. B300, R300, Hp (kW): 6000 min.
Pickup
15 ms max.
Dropout
5 ms max.
Vibration
Operational Non-Operational
10…2000 Hz, 0.76 mm (0.03 in.) 2.5 G 10…2000 Hz, 0.76 mm (0.03 in.) 5.0 G
Shock
Operational Non-Operational
15 G 50 G Environmental
Temperature
Operating Storage
–40…+70 °C (–40…+158 °F) –40…+85 °C (–40…+185 °F)
Altitude
2000 m (6560 ft) Construction
Insulating Material Enclosure Contact Material Terminal Markings on Socket
46
Molded High Dielectric Material Transparent Dust Cover 700-HK3_: Silver nickel (AgNi); 700-HKX_: Silver Nickel + Gold Plating (AgNi + Au); 700-HKM_: Silver Tin Oxide(AgSnO2) In accordance with EN 50005
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 47
General Purpose Relays
Attribute
700-HK
Sockets
1-Pole
2-Pole
Screw Terminal
700-HN121 (10 A @ 70 °C) 700-HN221 (16 A @ 50 °C, 12 A @ 70 °C)
700-HN122 (2 x 5 A @ 70 °C) 700-HN222 (2 x 8 A @ 70 °C)
Spring Clamp
700-HN223 (15 A @ 40 °C with 2 conductors per terminal) (10 A @ 70 °C with 1 conductor per terminal)
700-HN224 (2 x 8 A@ 70 °C)
Approvals Certifications
CSA Certified, File 75088, UL Recognized, File E3125 Guide NLDX2/NLCX8, cULus Listed with Allen-Bradley sockets (File No. 3125 Guide NLDX/NLDX7), CE Marked
Standards
EN61810-1, CSA 22.2 No. 14, UL 508
Dimensions- 700-HK Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 12.4 (1/2)
12.4 (1/2)
29.0 (1-9/64)
32.8 (1-19/64)
29.0 (1-9/64)
32.8 (1-19/64)
30.1 (1-3/16)
6.5 (1/4)
6.5 (1/4)
2.5 (3/32) 4.75 (3/16) A1 5
0.5 (1/32) COM 11 4
A2 NC 22 NO 24 1 5 7 COM 21 6
NC 12 NO 14 2 3 Cat. No. 700-HK36_ (SPDT) NO 14 4
NC 12 2
0.5 (1/32)
COM 11 3 NO 14 A1 NC 12 4 2 8
A2 1
COM 11 3
30.1 (1-3/16)
Cat. No. 700-HK32_ (DPDT) COM 11 NO 14 NC 12 3 4 2
A1 8
A1 8 15.8 (5/8)
15.8 (5/8) COM 21 6
NO 24 5
NC 22 7 Cat. No. 700-HN224
A2 1
COM 21 NO 24 NC 22 6 5 7
A2 1 Cat. No. 700-HN222
COM 11 4
NO 14 3
NC 12 2
A1 5
COM 11 NO 14 NC 12 4 3 2
A1 5
15.8 (5/8)
15.8 (5/8)
A2 1
A2 1 Cat. No. 700-HN221
Cat. No. 700-HN223
64.9 (2-9/16)
44.7 (1-3/4)
32.5 22.6 (1-9/32) (57/64)
35.3 (1-25/64)
34.7 (1-3/8) 95.6 (3-49/64)
35.4 (1-13/32) 82.85 (3-17/64)
Cat. No. 700-HN223, 700-HN224 Wire Size: 0.2 mm2...1.5 mm2 (#24 AWG....#14 AWG) Either Solid or Stranded Strip Length: 8 mm (5/16 in)
Cat. No. 700-HN221, 700-HN222 Wire Size: 0.2 mm2...2.5 mm2 (#24 AWG....#12 AWG) Either Solid or Stranded Strip Length: 8 mm (5/16 in), Torque: 0.8Nm (7.0 lb.-in.)
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
47
Page 48
General Purpose Relays
Dimensions - 700-HK Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 46.0 (1-13/16) 14.4 (37/64)
3.6 (9/64)
14.4 (37/64)
38.0 (1-1/2)
46.9 (1-27/32)
42.4 (1-43/64)
36.6 (1-11/16)
39.8 (1-37/64)
18.1 (23/32)
2.0 (5/64)
34.8 (1-3/8) Cat. No. 700-HN227
Cat. No. 700-HN226
6.2 (15/64)
50 (1-63/64)
1.0 (0.04)
12.5 (1/2)
27.0 (1.06)
35.0 (1.38)
5.2 (13/64)
7.5 (0.30)
1000 (39-3/8) Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes Cat. No. 199-DR1 DIN Mounting Rail Series B
A
B
C
D
Approx. Shipping Wt.
199-DR1
35 (1-3/8)
27 (1-1/16)
7.5 (19/64)
1.02 (1/64)
1.85 kg (4.07 lb) (10/pkg)
199-DR4
35 (1-3/8)
27 (1-1/16)
15 (19/32)
2.3 (3/32)
3.68 kg (8 lb) (5/pkg)
Cat. No.
48
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 49
General Purpose Relays
7.11 (9/32)
11 4 14 3
Five M3.5 x 0.315 Screws 4.06 (5/32)
12 2 3.0 Ø (1) (1/8) Use M3 Screws
84.1 (3-5/16) 5 (+) (A1)
39.5 (1-17/32) 35.5 (1-13/32)
1 (-) (A2)
4.06 (5/32) 15.6 (5/8)
29.9 (1-3/16)
7.11 (9/32)
21 6
2.03 (5/64) 22 7 24 5
Eight M3.5 x 0.315 Screws 12 2 14 4 3.0 Ø (1) (1/8) Use M3 Screws
84.1 (3-5/16) 8 (+) (A1) 4.06 (5/32)
1 (-) (A2) 15.6 (5/8)
54.1 (2-1/8)
Cat. No. 700-HN121 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #14 AWG Double Wire – 2 x 2.5 mm2 (14 AWG… 20 AWG) Qty. 2 wires (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)
2.03 (5/64)
11 3
4.06 (5/32) 39.5 (1-17/32) 35.5 (1-13/32)
29.9 (1-3/16) 54.1 (2-1/8)
Cat. No. 700-HN122 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #14 AWG Double Wire – 2 x 2.5 mm2 (14 AWG… 20 AWG) Qty. 2 wires (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
49
Page 50
General Purpose Relays
700-HL Terminal Block Relay • Relay and socket assembled interface modules for high density interposing or isolation applications • Screw terminal and spring-clamp bases • 6 A relay, choice of silver or gold contacts • 2 A solid-state relay, DC output • 2 A solid-state relay, AC output • SPDT (relay), 1 N.O. (solid-state) • Built-in retainer clip and snap-in marker lever • Standard LED, reverse polarity protection, and surge protection • Externally replaceable relay modules • Unique leakage current suppression version to address industry concerns of nuisance coil turn-on or contact non-drop out when connecting to PLCs with leakage current • Available with hazardous location certification Standard built-in Features: • LED • Reverse Polarity Protection for DC Inputs • Coil Surge Protection(1) Cat. No. 700-HLT1Z24
Cat. No. 700-HLT2Z24
Cat. No. 700-HLS1Z24
Cat. No. 700-HLS11Z24
(3)
Specifications
Output Type
SPDT (1 C/O); Ith = 6A(2)
Recommended Tightening Torque
0.5 N• m max. (4.4 lb• in)
Wire Range
Screw Terminal: 0.14 mm2…2.5 mm2 (#26…#14 AWG), Spring Terminal: 0.2 mm2…2.5 mm2 (#24…#14 AWG)
Approvals
UL, cULus, cURus, ABS, CE
1 N.O. solid-state; Ith = 2 A, 24V DC or Ith = 2 A, 240V AC
(1) Diode surge protection provided. (2) For Gold-plated contacts: Add the letter “X” at the end of the catalog number. For example: if Cat. No. 700-HLT1Z24 is required with gold plating, the new cat. no. is 700-HLT1Z24X. (3) Reverse polarity on the output terminals of the solid-state relay will result in the output being "ON" regardless of the state of the input voltage.
Input Voltage
Pkg. Qty.
Cat. No. Cat. No. (Spring Clamp (Screw Terminals) Terminals)
Cat. No. Pkg. Quantity (Screw Terminals) (DC Output)
Cat. No. (Spring Clamp Terminals) (DC Output)
Cat. No. (Screw Terminals) (AC Output)
12V DC
10
(2), - - - 10
(2)
10
(2)
700-HLS1Z24
700-HLS2Z24
700-HLS11Z24
48V DC
10
(2)
700-HLT2Z48
10
(2)
700-HLS1Z48
700-HLS2Z48
700-HLS11Z48
12V AC/DC
10
700-HLT1U12
700-HLT2U12, - - - 24V AC/DC
10
700-HLT1U24
700-HLT2U24, - - - 48V AC/DC
10
700-HLT1U48
700-HLT2U48, - - - 10
(2)
700-HLS1U1
700-HLS2U1
700-HLS11U1
700-HLS1U2
700-HLS2U2
700-HLS11U2, - 24V DC
110/125V AC/DC
10
700-HLT1Z12 700-HLT1Z24 700-HLT1Z48
700-HLT1U1
700-HLT2Z12 700-HLT2Z24
700-HLT2U1
220…240V AC/DC
10
700-HLT1U2
700-HLT2U2
10
(2)
240V AC
10
700-HLT1A2, - - 50
Rockwell Automation Publication 700-TD552B-EN-P - August 2018