For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX

Page 41

General Purpose Relays

Photo

Description

Pkg. Qty.

Cat. No.

DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m

10

199-DR1

Retainer Clip for Cat. Nos. 700-HN103, -HN104 and -HN128 Sockets with 700-HC Relays. Secures relay in socket.(1)

10

700-HN114

Plastic Retainer and Ejection Lever For use with the 700-HN104 Sockets for 700-HC relays. Built-in ability to accept 1492 Snap-in Markers

10

700-HN124

(1) See 700-HC Miniature Square Base Relay, Socket, and Retainer Clip Reference Chart

Description

Photo

Relay Identification Snap-in Markers Snap-in markers fit on top of product covers. Squares slip into molded slot on top of product cover.

Pkg. Qty. Cat. No. 5

1492-MS5X12

5

1492-MS6X9

5

1492-MS6X12

5

1492-MS8X9

5

1492-MS8X12

100

1492-MP-Blank

Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.

10

700-N40

Markers, Used for terminal identification

50

700-N41

Socket and Retainer Clip Reference Relay Type

700-HC

Socket Cat. No.

Retainer Clip Cat. No.

700-HN103

700-HN114

700-HN128

700-HN114

700-HN104

700-HN114 or 700-HN124

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

41

Page 42

General Purpose Relays

Specifications- 700-HC Relays Attribute

700-HC Electrical Ratings

Pilot Duty Rating

(1)

NEMA C300, R300

Rated Thermal Current (Ith)

7 A and 10 A

Rated Insulation Voltage (Ui)

250V IEC – 300V UL/CSA 700-HC_4

Hp

700-HC22

Hp

Inductive 120V AC

15 A

1.5 A

1/8

15 A

1.5 A

1/3

240V AC

7.5 A

0.75 A

1/3

7.5 A

0.75 A

3/4

Contacts General-purpose

7 A, 277V AC

10 A, 277V AC

Resistive

7 A, 30V DC

10 A, 24V DC 100 mW (10V, 10 mA) - Silver Contacts 50 mW (5V, 10 mA, or 25V, 2 mA) - Gold Contacts

Min. Low Energy Permissible Load

Permissible Coil Voltage Variation

Coil Consumption ±10%

AC Coils

Pickup:

80…110% of nom voltage at 50 Hz 80…110% of nom voltage at 60 Hz 80…110% of nom voltage at DC

Must Dropout Voltage:

20% of nom voltage at AC 10% of nom voltage at DC

50 Hz

60 Hz

Inrush

2.2VA

1.6VA

Sealed

1.3VA

1.1VA

DC Coils

1.0 W 20% of VA (AC)

Max. Allowable Leakage

10% of W (DC) Design Specification/Test Requirements Electrical Dielectric Withstand Voltage

Pole-to-Pole

2000V

Contact to Coil

2000V

Electrical Life (Cycles)

100 000 min Mechanical

Degree of Protection (Open Type) IEC 529

IP 20 (Guarded Terminal Sockets)

Mechanical lifecycles

20 x 106 (AC), 50 x 106 (DC)

Switching Frequency Operations

1800/HR

Coil Voltages Operating Time (ms)

See Product Selection Max. Pickup

10

Max. Dropout

3

Maximum Operating Rate

8 cycles/s Environmental

Temperature Altitude Insulating Material Enclosure Contact Material

Operating

–30…+55 °C (–22…+131 °F)

Storage

–55…+85 °C (–67…+185 °F) 2000 m (6560 ft) Molded High Dielectric Material Transparent Dust Cover AgNi (700-HC2), AgNi + 5 μm All (700-HC1)

Terminal Markings on Socket

In accordance with EN50 0005

Sockets

700-HN103, -HN128, -HN104

Certifications cURus Recognized (File No. E14843, Guide NRNT2/NRNT8), cULus Listed when used with 700- HN103, -HN104, and -HN128 sockets (File No. E14843, Guide NRNT/NRNT7), CE Marked, LR Certified

Standards

UL 508, CSA 22.2 No. 14, EN 61810-1

(1) See General Information on page 3

42

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 43

General Purpose Relays

Dimensions, 700-HC Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

37.2 (1.46)

36.7 (1.44)

5.6 (0.22)

6.1 (0.24) 20.7 (0.82)

27.7 (1.09)

20.7 (0.82)

27.7 (1.09)

700-HC Relay (Two-Pole)

700-HC Relay (Four-Pole) 27.0 (1.06)

60.9 (2.40) 21.5 (0.85)

76.0 (2.99)

35.6 (1.40) 3.2 (0.13) 18.9 (0.74) 34.9 (1.37)

32.0 (1.26) 35.5 (1.40) 2.5 (0.10)

Cat. No. 700-HN104

Single Wire: 0.2 mm2…2.5 mm2 (24 AWG…14 AWG), Double Wire: 0.2 …2.5 mm2 (24 AWG…14 AWG), Qty. 2 wires Wire Type: solid or stranded, copper only, Strip Length: 7 mm (9/32 in.), Torque: 0.5 N•m (4.4 lb•in)

30.0 (1-3/16) 6.1 (15/64)

Panel Mounting

24.5 (31/32)

28.9 (1-9/64)

8

7

6

5

4

3

2

1

67.0 (2-5/8)

4.2 (5/32)

14 12

#4-40 M3

30.0 (1-11/64)

24.9 (57/64) 21.1 (53/64)

13 11

10

62.0 (2-15/64)

65.0 (2-9/16)

9

26.0 (1-1/64)

Cat. No. 700-HN103

Cat. No. 700-HN128

Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…14 AWG) Double Wire: 0.2…2 x 1.5 mm2 (24 AWG…16 AWG), Qty. 2 wires Wire Type: Solid or Stranded, Copper only Strip Length: 8 mm (5/16 in.), Torque: 0.5 N•m (4.4 lb•in)

Wire Size: 2 x 1.5 mm2 (#2-16 AWG…#1-20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Toque: 0.8 N•m (7 lb•in

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

43

Page 44

General Purpose Relays

700-HK Slim Line Relay • 8 A/16 A contact ratings • DPDT/SPDT • Plug-in blade-style terminals • Retainer clip with sockets • Options: LED, push-to-test and manual override, socket-mounted surge suppressor module, or timer module • Standard ON/OFF flag indicator • Relay faceplate accepts optional 1492 snap-in markers • Choice of standard silver/nickel contacts or silver/nickel with gold plated contacts • Maximum duty version available Photo

Description

SPDT 1-Pole 1 Form C AgNi Contacts

Contact Rating

Wiring Diagrams U.S./Canada

International

16 A

Input

700-HN121, 700-HN221, 700-HN223

Socket

DPDT 2-Pole 2 Form C AgNi Contacts

700-HN121, 700-HN221, 700-HN223

8A

Input

Socket

44

700-HN122, 700-HN222, 700-HN224

700-HN122, 700-HN222, 700-HN224

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Coil Voltage

Cat. No.

6V AC

700-HK36A06

12V AC

700-HK36A12

24V AC

700-HK36A24

120V AC

700-HK36A1

240V AC

700-HK36A2

6V DC

700-HK36Z06

12V DC

700-HK36Z12

24V DC

700-HK36Z24

48V DC

700-HK36Z48

110V DC

700-HK36Z1

6V AC

700-HK32A06

12V AC

700-HK32A12

24V AC

700-HK32A24

120V AC

700-HK32A1

240V AC

700-HK32A2

6V DC

700-HK32Z06

12V DC

700-HK32Z12

24V DC

700-HK32Z24

48V DC

700-HK32Z48

110V DC

700-HK32Z1

Page 45

General Purpose Relays

Accessories- 700-HK Relays Photo

Description

Pkg. Qty.

Cat. No.

Screw Terminal Socket, Panel or DIN Rail Mounting 5-blade miniature socket with 10 A rating for use with 1-pole, 700-HK relays. Accepts forked lug conductors. Socket includes a retainer clip.

10

700-HN121

Screw Terminal Socket, Panel or DIN Rail Mounting 5-blade miniature socket with 16 A rating for use with 1-pole, 700-HK relays. Retainer clips are packaged separately with socket. Guarded terminal construction and compatible with optional plug-in module accessories.

10

700-HN221

Spring Clamp Terminal Socket, Panel or DIN Rail Mounting 5-blade miniature socket for use with 1-pole, 700-HK relays.

10

700-HN223

Screw Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket with 5 A rating for use with 2-pole, 700-HK relays. Accepts forked lug conductors. This socket includes a retainer clip.

10

700-HN122

Screw Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket with 8 A rating for use with 2-pole, 700-HK relays. Retainer clips are packaged separately with socket. Guarded terminal construction and compatible with optional plug-in module accessories.

10

700-HN222

Spring Clamp Terminal Socket, Panel or DIN Rail Mounting 8-blade miniature socket for use with 2-pole 700-HK relays.

10

700-HN224

Flange Mount Adapter Used for panel-mounting bulletin 700-HK relays. Order must be for 10 adapters or multiples of 10.

10

700-HN226

35 mm Rail Mount Adapter Mounts bulletin 700-HK relays to a 35 mm rail. Order must be for 10 adapters or multiples of 10.

10

700-HN227

Socket Retainer Clip and Ejection Lever For use with 700-HN22, -HN222, -HN223, and -HN224 sockets. Orders must be for 10 clips or multiples of 10.

10

700-HN229

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

45

Page 46

General Purpose Relays

Specifications- 700-HK Relays Attribute

700-HK Electrical Ratings

Rated Thermal Current (Ith)

1-Pole, 1 CO, SPDT, 16 A

2-Pole, 2 CO, DPDT, 8 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA 120V AC

AC-15, 6.2 A B300 Pilot Duty, 3 A A300 (700-HKM_) 1/3 Hp (0.24 kW) 1-phase

120V AC

AC-15, 2.9 A B300 Pilot Duty, 3.0 A 1/4 Hp (0.18 kW), 1-phase

240V AC

AC-15, 3.1 A B300 Pilot Duty, 1.5 A A300(700-HKM_) 3/4 Hp (0.55 kW), 1-phase

240V AC

AC-15, 1.4 A B300 Pilot Duty, 1.5 A 1/2 Hp (0.37 kW), 1-phase

230V AC

0.55 kW, 1-phase

230V AC

0.37 kW, 1-phase

24V DC

DC-13, 5.0 A

24V DC

DC-13, 3.0 A

125V DC

DC-13, 0.2 A / R300 Pilot Duty, 0.22 A

125V DC

DC-13, 0.2 A / R300 Pilot Duty, 0.22 A

250V DC

DC-13, 0.1 A / R300 Pilot Duty, 0.11 A

5 A, 250V AC

DC-13, 0.1 A / R300 Pilot Duty, 0.11 A

230V AC

AC-1, 16 A

230V AC

AC-1, 8 A

277V AC

16 A, General Use

277V AC

8 A, General Use

30V DC

DC-1, 12 A / 10 A, Resistive

30V DC

DC-1, 6 A / 6 A, Resistive

Inductive V AC

Contacts Inductive V DC

Resistive Make, Break , and Continuous Min. Permissible Contact Ratings

Permissible Coil Voltage Variation

Pickup: holding Voltage: Must Dropout Voltage:

300 mW (5V/60 mA or 60V/5 mA) for AgNi Contacts (700-HK3_) 50 mW (5V/10 mA or 25V/2 mA) for AgNi + Gold Contacts (700-HKX_) 500 mW (100V/5 mA or 5V/100 mA) for AgSnO2 Contacts (700-HKM_) 80…110% of Nominal Voltage at 50/60 Hz, 73...110% of Nominal Voltage at DC 80% of Nominal V AC at 50/60 Hz, 40% of Nominal V DC 20% of Nominal V AC at 50/60 Hz, 10% Nominal V DC

Power Consumption

1.2V A (V AC Coils), 0.5 W (V DC Coils)

Coil Voltages

See Overview/Product Selection Design Specification/Test Requirements

Dielectric Withstand Voltage

Pole to Pole (VRMS) Contact to Coil (VRMS)

2000V AC 4000V AC Mechanical

Degree of Protection

IP 20 (guarded terminal sockets), RT II, Flux-proof (Relay) 10 x 106

Mechanical Life Operations 230V AC, 16 A Resistive: 100 000 min. 277V AC, 16 A Resistive: 30 000 min. 30V DC, 10 A Resistive: 30 000 min. B300, R300, Hp (kW): 6000 min. A300 (700-HKM_): 100,000 min.

Electrical Lifecycles

Mechanical: 18,000 cycles/hr. Electrical: 900 cycles/hr.

Switching Frequency Operating Time at Nominal Voltage at 20 °C (ms)

230V AC, 8 A Resistive: 100 000 min. 277V AC, 8 A Resistive: 30 000 min. 30V DC, 6 A Resistive: 30 000 min. B300, R300, Hp (kW): 6000 min.

Pickup

15 ms max.

Dropout

5 ms max.

Vibration

Operational Non-Operational

10…2000 Hz, 0.76 mm (0.03 in.) 2.5 G 10…2000 Hz, 0.76 mm (0.03 in.) 5.0 G

Shock

Operational Non-Operational

15 G 50 G Environmental

Temperature

Operating Storage

–40…+70 °C (–40…+158 °F) –40…+85 °C (–40…+185 °F)

Altitude

2000 m (6560 ft) Construction

Insulating Material Enclosure Contact Material Terminal Markings on Socket

46

Molded High Dielectric Material Transparent Dust Cover 700-HK3_: Silver nickel (AgNi); 700-HKX_: Silver Nickel + Gold Plating (AgNi + Au); 700-HKM_: Silver Tin Oxide(AgSnO2) In accordance with EN 50005

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 47

General Purpose Relays

Attribute

700-HK

Sockets

1-Pole

2-Pole

Screw Terminal

700-HN121 (10 A @ 70 °C) 700-HN221 (16 A @ 50 °C, 12 A @ 70 °C)

700-HN122 (2 x 5 A @ 70 °C) 700-HN222 (2 x 8 A @ 70 °C)

Spring Clamp

700-HN223 (15 A @ 40 °C with 2 conductors per terminal) (10 A @ 70 °C with 1 conductor per terminal)

700-HN224 (2 x 8 A@ 70 °C)

Approvals Certifications

CSA Certified, File 75088, UL Recognized, File E3125 Guide NLDX2/NLCX8, cULus Listed with Allen-Bradley sockets (File No. 3125 Guide NLDX/NLDX7), CE Marked

Standards

EN61810-1, CSA 22.2 No. 14, UL 508

Dimensions- 700-HK Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 12.4 (1/2)

12.4 (1/2)

29.0 (1-9/64)

32.8 (1-19/64)

29.0 (1-9/64)

32.8 (1-19/64)

30.1 (1-3/16)

6.5 (1/4)

6.5 (1/4)

2.5 (3/32) 4.75 (3/16) A1 5

0.5 (1/32) COM 11 4

A2 NC 22 NO 24 1 5 7 COM 21 6

NC 12 NO 14 2 3 Cat. No. 700-HK36_ (SPDT) NO 14 4

NC 12 2

0.5 (1/32)

COM 11 3 NO 14 A1 NC 12 4 2 8

A2 1

COM 11 3

30.1 (1-3/16)

Cat. No. 700-HK32_ (DPDT) COM 11 NO 14 NC 12 3 4 2

A1 8

A1 8 15.8 (5/8)

15.8 (5/8) COM 21 6

NO 24 5

NC 22 7 Cat. No. 700-HN224

A2 1

COM 21 NO 24 NC 22 6 5 7

A2 1 Cat. No. 700-HN222

COM 11 4

NO 14 3

NC 12 2

A1 5

COM 11 NO 14 NC 12 4 3 2

A1 5

15.8 (5/8)

15.8 (5/8)

A2 1

A2 1 Cat. No. 700-HN221

Cat. No. 700-HN223

64.9 (2-9/16)

44.7 (1-3/4)

32.5 22.6 (1-9/32) (57/64)

35.3 (1-25/64)

34.7 (1-3/8) 95.6 (3-49/64)

35.4 (1-13/32) 82.85 (3-17/64)

Cat. No. 700-HN223, 700-HN224 Wire Size: 0.2 mm2...1.5 mm2 (#24 AWG....#14 AWG) Either Solid or Stranded Strip Length: 8 mm (5/16 in)

Cat. No. 700-HN221, 700-HN222 Wire Size: 0.2 mm2...2.5 mm2 (#24 AWG....#12 AWG) Either Solid or Stranded Strip Length: 8 mm (5/16 in), Torque: 0.8Nm (7.0 lb.-in.)

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

47

Page 48

General Purpose Relays

Dimensions - 700-HK Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 46.0 (1-13/16) 14.4 (37/64)

3.6 (9/64)

14.4 (37/64)

38.0 (1-1/2)

46.9 (1-27/32)

42.4 (1-43/64)

36.6 (1-11/16)

39.8 (1-37/64)

18.1 (23/32)

2.0 (5/64)

34.8 (1-3/8) Cat. No. 700-HN227

Cat. No. 700-HN226

6.2 (15/64)

50 (1-63/64)

1.0 (0.04)

12.5 (1/2)

27.0 (1.06)

35.0 (1.38)

5.2 (13/64)

7.5 (0.30)

1000 (39-3/8) Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes Cat. No. 199-DR1 DIN Mounting Rail Series B

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lb) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lb) (5/pkg)

Cat. No.

48

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 49

General Purpose Relays

7.11 (9/32)

11 4 14 3

Five M3.5 x 0.315 Screws 4.06 (5/32)

12 2 3.0 Ø (1) (1/8) Use M3 Screws

84.1 (3-5/16) 5 (+) (A1)

39.5 (1-17/32) 35.5 (1-13/32)

1 (-) (A2)

4.06 (5/32) 15.6 (5/8)

29.9 (1-3/16)

7.11 (9/32)

21 6

2.03 (5/64) 22 7 24 5

Eight M3.5 x 0.315 Screws 12 2 14 4 3.0 Ø (1) (1/8) Use M3 Screws

84.1 (3-5/16) 8 (+) (A1) 4.06 (5/32)

1 (-) (A2) 15.6 (5/8)

54.1 (2-1/8)

Cat. No. 700-HN121 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #14 AWG Double Wire – 2 x 2.5 mm2 (14 AWG… 20 AWG) Qty. 2 wires (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)

2.03 (5/64)

11 3

4.06 (5/32) 39.5 (1-17/32) 35.5 (1-13/32)

29.9 (1-3/16) 54.1 (2-1/8)

Cat. No. 700-HN122 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #14 AWG Double Wire – 2 x 2.5 mm2 (14 AWG… 20 AWG) Qty. 2 wires (Either Solid or Stranded) Strip Length: 9 mm (3/8 in.) – Torque: 0.8 N•m (7 lb•in)

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

49

Page 50

General Purpose Relays

700-HL Terminal Block Relay • Relay and socket assembled interface modules for high density interposing or isolation applications • Screw terminal and spring-clamp bases • 6 A relay, choice of silver or gold contacts • 2 A solid-state relay, DC output • 2 A solid-state relay, AC output • SPDT (relay), 1 N.O. (solid-state) • Built-in retainer clip and snap-in marker lever • Standard LED, reverse polarity protection, and surge protection • Externally replaceable relay modules • Unique leakage current suppression version to address industry concerns of nuisance coil turn-on or contact non-drop out when connecting to PLCs with leakage current • Available with hazardous location certification Standard built-in Features: • LED • Reverse Polarity Protection for DC Inputs • Coil Surge Protection(1) Cat. No. 700-HLT1Z24

Cat. No. 700-HLT2Z24

Cat. No. 700-HLS1Z24

Cat. No. 700-HLS11Z24

(3)

Specifications

Output Type

SPDT (1 C/O); Ith = 6A(2)

Recommended Tightening Torque

0.5 N• m max. (4.4 lb• in)

Wire Range

Screw Terminal: 0.14 mm2…2.5 mm2 (#26…#14 AWG), Spring Terminal: 0.2 mm2…2.5 mm2 (#24…#14 AWG)

Approvals

UL, cULus, cURus, ABS, CE

1 N.O. solid-state; Ith = 2 A, 24V DC or Ith = 2 A, 240V AC

(1) Diode surge protection provided. (2) For Gold-plated contacts: Add the letter “X” at the end of the catalog number. For example: if Cat. No. 700-HLT1Z24 is required with gold plating, the new cat. no. is 700-HLT1Z24X. (3) Reverse polarity on the output terminals of the solid-state relay will result in the output being "ON" regardless of the state of the input voltage.

Input Voltage

Pkg. Qty.

Cat. No. Cat. No. (Spring Clamp (Screw Terminals) Terminals)

Cat. No. Pkg. Quantity (Screw Terminals) (DC Output)

Cat. No. (Spring Clamp Terminals) (DC Output)

Cat. No. (Screw Terminals) (AC Output)

12V DC

10

(2), - - - 10

(2)

10

(2)

700-HLS1Z24

700-HLS2Z24

700-HLS11Z24

48V DC

10

(2)

700-HLT2Z48

10

(2)

700-HLS1Z48

700-HLS2Z48

700-HLS11Z48

12V AC/DC

10

700-HLT1U12

700-HLT2U12, - - - 24V AC/DC

10

700-HLT1U24

700-HLT2U24, - - - 48V AC/DC

10

700-HLT1U48

700-HLT2U48, - - - 10

(2)

700-HLS1U1

700-HLS2U1

700-HLS11U1

700-HLS1U2

700-HLS2U2

700-HLS11U2, - 24V DC

110/125V AC/DC

10

700-HLT1Z12 700-HLT1Z24 700-HLT1Z48

700-HLT1U1

700-HLT2Z12 700-HLT2Z24

700-HLT2U1

220…240V AC/DC

10

700-HLT1U2

700-HLT2U2

10

(2)

240V AC

10

700-HLT1A2, - - 50