Page 51

General Purpose Relays

Cat. No. (Spring Clamp Terminals) (DC Output)

Cat. No. (Screw Terminals) (AC Output)

700-HLS1L1, 700-HLS11L1

700-HLS1L2, 700-HLS11L2

10

700-HLS1Z24-EX, - - 10, - - - 10

700-HLS1U1-EX, - Input Voltage

Pkg. Qty.

Cat. No. Cat. No. (Spring Clamp (Screw Terminals) Terminals)

Cat. No. Pkg. Quantity (Screw Terminals) (DC Output)

Built-in LCSC (leakage current suppression circuit) 120V AC and 125V DC(1)

10

(2)

700-HLT1L1, 10

(2)

Built-in LCSC (leakage current suppression circuit) 240V AC (1)

10

(2)

700-HLT1L2, 10

(2)

Hazardous Location Certification 24V DC

10

700-HLT1Z24-EX, Hazardous Location Certification 12V DC

10

700-HLT1Z12-EX

Hazardous Location Certification 110/125V AC/DC

10

700-HLT1U1-EX

(1) Leakage current suppression up to 2.2 mA off state current. (2) Electromechanical relay to solid-state relay interchangeability is possible.

Accessories - 700-HLT, -HLS Relays Photo

Description

Replacement Relays(1) Order must be for 20 relays or multiples of 20.

Pkg. Quantity

20

Socket Input Voltage

Cat. No.

12V AC/DC

700-TBR12

24V AC/DC

700-TBR24

48V AC/DC

700-TBR48

110/125V AC/DC 220…240V AC/DC

700-TBR60

Replacement SSR 4-blade miniature relay for use with 1 N.O. SSR DC output. Order multiples of 20.

24V DC

700-TBS24

20

48V DC, 110/125V AC/DC 220…240V AC/DC

700-TBS60

Replacement SSR 4-blade miniature relay for use with 1 N.O. SSR AC output. Order multiples of 20.

20

24V DC

700-TBS124

Replacement SSR 4-blade miniature relay for use with 1 N.O. SSR AC output. Order must be for 20 relays or multiples of 20.

20

48V DC 110/125V AC/DC 220…240V AC/DC

700-TBS160

Color 20-Way Jumper Can be cut to required length. Ith = 36 A max per 20-way jumper.

1

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Red

700-TBJ20R

Grey

700-TBJ20G

Blue

700-TBJ20B

51

Page 52

General Purpose Relays

Photo

Description

Pkg. Quantity

Socket Input Voltage

Cat. No.

End Barrier Used for visual inspection of groups, safe separation of neighboring 700-HL modules that end with jumpers.

10

Black

700-HN177

100

Blank

1492-MC6X10

Snap-in Marker These snap-in markers have a 6 x 10 mm surface and snap into the ejection lever for the relay. For custom markers, contact your local Rockwell Automation sales office or Allen-Bradley distributor for more information.

(1) For gold-plated contacts: Add the letter “X” at the end of the catalog number. For example: if Cat. No. 700-TBR24 is required with gold plating, the new cat. no. is 700-TBR24X

Dimensions - 700-HL Relays

700-HL Spring Terminal Design Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…#14 AWG )Wire Type: Solid or stranded, copper only.Strip Length: 9 mm (11/32

Cat. No. 199-DR1 DIN Mounting Rail Series B, Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Specifications - 700-HLT Relays Cat. No. 700-HLT… (Relay Output) Electrical Ratings Pilot Duty Rating

B 300, R 300

Rated Thermal Current (Ith)

1-Pole, 6 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA Inductive

Contacts

24V AC, 1-phase

30 A

5A

120V AC, 1-phase

30 A

3A

240V AC, 1-phase

15 A

Make, Break and Continuous V DC

1.0 A

120V DC

0.2 A

240V DC

0.1 A

12V, 6 mA (72 mW) for Silver Contacts, 8V, 2.5 mA (20 mW) for Gold Contacts

Min. Permissible Contact Ratings

52

1.5 A 24V DC

AC-15 250V, 3 A N.O. Contact, 1.5 A N.C. Contact DC-13 24V, 1 A N.O., and N.C. Contact

Inductive Load

Permissible Coil Voltage Variation

1-Pole

Pickup:

85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Must Dropout Voltage:

10% of Nominal Voltage at AC 5% of Nominal Voltage at DC

Page 53

General Purpose Relays

Cat. No. 700-HLT… (Relay Output) Power Consumption ±10%

AC DC

0.3VA 0.2 W Design Specification / Test Requirements

Dielectric Withstand Voltage Input Voltage

Pole to Pole (VRMS)

1000V

Contact to Coil (VRMS)

4000V

12V AC/DC

24V AC/DC

48V AC/DC

120V AC/DC

240V AC/DC

120V LCSC

240V LCSC

1K

2K

6K

26 K

56 K

16 K

35 K

Impedance (Ohms)

Mechanical Degree of Protection

IP20

Mechanical Life Operations

1 x 107

Electrical Life Operations

6 A Resistive: 100 000 min. 24V DC, 1 A Inductive: 200 000 min. 120V AC 1 A Inductive: 300 000 min.

Switching Frequency Operations (no-load)

10 cycles/sec

Coil Voltages Operating Time at Nominal Voltage at 20 °C (ms)

See Overview/Product Selection Pickup

7 ms

Dropout

3 ms

Maximum Operating Rate (full load = 6 A)

6 cycles/min. Per EN 61000-4.5; Surge Immunity (801-5) Class III: 2 kV common and 1 kV differential mode

Coil Surge Protection

Environmental Temperature

Operating

–40…+55 °C

Storage

–40…100 °C

Altitude

2000 m (6560 ft) Construction

Insulating Material

Molded High Dielectric Material

Enclosure

Relay IP67

Contact Material

Silver Tin Ox, AgSnO2 or Silver with Gold Plating, AgSnO2 + Au

Terminal Markings on Socket

In accordance with EN50 0005

Certifications cULus Listed (File No. E3125, E14843 Guide NLDX/NLDX7) with Allen-Bradley socket, CE Marked, ABS (American Bureau of Shipping)

Standards

EN 61810-1, CSA 22.2,UL 508,NEMA IEE MAC Compliant, ICS-2 Compliant Class 1, Zn 2, Groups IIC, Ex nC IIC T5 Ta < 55 °C

Hazardous Location Approvals

UL Listed (UL 60079-15)

700-HLT1Z12-EX (12V DC supply) 700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply) 700-HLT1U1-EX, 700-HLS1U1-EX (110V/125V AC/DC supply)

CSA Certified (1) (CAN/CSA E60079-15)

700-HLT1Z12-EX (12V DC supply) 700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)

(1) Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.

Cat. No. 700-HLS… (Solid-state Output) Electrical Rated Thermal Current (Ith)

2 A (DC output)

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

2 A (AC output)

53

Page 54

General Purpose Relays

Cat. No. 700-HLS… (Solid-state Output)

Control Circuit

Min. Control Voltage

80% nominal voltage

Maximum Control Voltage

110% nominal voltage

Control Current

9 mA ±10% (24V) 4 mA ±10% (120/240V)

Release Voltage

0.4 x nominal voltage (24V), 0.35 x nominal voltage (120/240V)

Min. Control Circuit Resistance Load Voltage Range

Outputs

2500 ohms (24V), 12k ohms (120V), 24k ohms (240V)

0…24V DC

24…240V AC

Max. Repetitive Blocking Voltage

33V

600V

Max. Switching Current (inductive/ resistive)

2 A DC

1 A AC

<120 mV DC

<1V AC

On State Voltage Drop @ Max. Switching Current

Power Consumption ±10%

3200 ohms (24V), 16k ohms (120V), 32k ohms (240V)

Leakage Current max. 100 μA (@U = 24V)

AC

0.6VA(120V), 1VA(240V)

DC

0.2 W

0.3 W

Design Specification/Test Requirements Dielectric Withstand Voltage

Pole to Pole (VRMS)

2500V

Contact to Coil (VRMS)

2500V

Input Voltage

24V DC

48V DC

120V AC/DC

240V AC/DC

120V LCSC

240V LCSC

Impedance (Ohms)

2K

9K

26 K

58 K

16 K

35 K

Mechanical Degree of Protection

IP20

Input Voltages Operating Time at Nominal Voltage at 20 °C (ms)

See Overview/Product Selection Turn on Time

30 μs (DC only input voltage), 7 ms (AC/DC input voltage)

Drop Out Time

350 μs (DC only input voltage), 10 ms (AC/DC input voltage)

Maximum Operating Rate

300 Hz Environmental

Temperature

Operating

–20…+55 °C

Storage

–40…70 °C

Altitude

2000 m (6560 ft) Construction

Insulating Material

Molded High-Dielectric Material

Enclosure

Relay IP67

Terminal Markings on Socket

In accordance with EN50 0005

Certifications cULus Listed (File No. E14843, Guide NLDX/NLDX7), CE Marked, ABS (American Bureau of Shipping)

Standards

UL 508, CSA C22.2 No. 14, EN 61810-1 Class 1, Zn 2, Groups IIC, Ex nC IIC T5 Ta < 55 °C

Hazardous Location Approvals

UL Listed (UL 60079-15)

700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply) 700-HLT1U1-EX, 700-HLS1U1-EX (110V/125V AC/DC supply)

CSA Certified (1) (CAN/CSA 60079-15)

700-HLT1Z24-EX, 700-HLS1Z24-EX (24V DC supply)

(1) Product shall be installed in an enclosure providing at least IP54 protection. Provisions shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40%.

54

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 55

General Purpose Relays

Dimensions - 700-HLT, -HLS Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.

76.0 (2.99)

88.0 (3.46)

76.0 (2.99)

93.0 (3.66)

6.2 (0.24)

6.2 (0.24)

700-HLT / -HLS Spring Terminal Design Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…#14 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in.)

700-HLT / -HLS Screw Terminal Design Single Wire: 0.14 mm2…2.5 mm2 (#26 AWG…#14 AWG) Double Wire: 2 x 0.14 mm2…2 x 1.5 mm2 (2 x #26 AWG…2 x #16 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in). Torque: 0.5 N•m (4.4 lb•in)

Dimensions - 700-HLT, -HLS Relay Accessories 6.2 (15/64)

50 (1-63/64)

5.2 (13/64)

12.5 (1/2)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

7.5 (0.3)

1000 (39-3/8)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No.

A

B

C

D

Approx. Shipping Wt.

Pkg. Qty.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lb)

10/pkg

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lb)

5/pkg

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

55

Page 56

General Purpose Relays

700-HL 2-pole Terminal Block Relay • Relay and socket assembled interface modules for high density interposing or isolation applications • Screw terminal and spring-clamp bases • 10 A relay, choice of silver or gold contacts • DPDT (relay) • Built-in retainer clip and snap-in marker lever • Standard LED, reverse polarity protection, and surge protection • Externally replaceable relay modules

Output Type

DPDT (2 C/O); Ith = 10 A

Recommended Tightening Torque

0.6 N•m max. (5.3 lb•in.)

Wire Range

Screw Terminal: 0.2…2.5 mm2 (#24…14 AWG), Spring Terminal: 0.2…2.5 mm2 (#24…14 AWG)

Approvals cULus, cURus, CE

Input Voltages

Pkg. Quantity

Cat. No.(1) (Screw Terminals)

Cat. No.(Spring Clamp Terminals)

12V DC

10

700-HLT12Z12

700-HLT22Z12

24V DC

10

700-HLT12Z24

700-HLT22Z24

48V DC

10

700-HLT12Z48

700-HLT22Z48

24V AC/DC

10

700-HLT12U24

700-HLT22U24

110/125V AC/DC

10

700-HLT12U1

700-HLT22U1

220…240V AC/DC

10

700-HLT12U2

700-HLT22U2

(1)

For Gold-plated contacts: Add the letter "X" at the end of the catalog number. Example: Cat. No. 700-HLT12Z24 with gold plated contacts is Cat. No. 700-HLT12Z24X. The following relays are available with the gold-plated contact option: 700-HLT_2Z24, 700-HLT_2U24, 700-HLT_2U1, and 700-HLT_2U2. Not available on 12V and 48V DC products.

Accessories - 700-HL Relays (2- pole) Photo

Description

Replacement Relays Order must be for 20 relays or multiples of 20.

Pkg. Qty.

20

Socket Input Voltage/Color

Cat. No.

12V DC

700-TBR212

24V AC/DC

700-TBR224

48V DC

700-TBR248

110/125V AC/DC, 220…240V AC/DC

700-TBR2110

Red

700-TBJ08R

Grey

700-TBJ08G

Blue

700-TBJ08B

8-Way Jumper Can be cut to required length. Ith = 10 A max per 8-way jumper.

1

End Barrier Used for visual inspection of groups, safe separation of neighboring 700-HL modules that end with jumpers.

10

Black

700-HN177

Snap-in Marker(1) These snap-in markers have a 6 x 12 mm surface and snap into the ejection lever for the relay.

100

Blank

1492-MS6X12

(1) For custom markers, contact your local Rockwell Automation sales office or Allen-Bradley distributor for more information.

56

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 57

General Purpose Relays

Specifications - 700-HL Relays (2-Pole) Cat. No. 700-HLT…2-Pole (Relay Output) Electrical Ratings

Pilot Duty Rating

B 300, R 300

Rated Thermal Current (Ith)

2-Pole, 10 A

Rated Insulation Voltage (Ui)

250V IEC, 300V UL/CSA

Inductive V AC UL

Contacts

Inductive V DC

Resistive Make, Break, and Continuous

120V AC

AC-15, 3.0A B 300, 3.0 A

1/4 HP (186 W), 1-phase

240V AC

AC-15, 3.0 A B 300, 1.5 A

1/2 HP (373 W), 1-phase

24V DC

DC-13, 2.0 A

125V DC

DC-13, 0.3 A

250V DC

DC-13, 0.2 A

250V AC

10 A

24V DC

10 A

250V DC

0.28 A

Min. Permissible Contact Ratings

12V, 10 mA (120 mW) for Silver Contacts, 5V, 1 mA (50 mW) for Gold Contacts

Permissible Coil Voltage Variation

85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC

Pickup:

Must Dropout Voltage:

10% of Nominal Voltage at AC 5% of Nominal Voltage at DC

Design Specification/Test Requirements

Dielectric Withstand Voltage

Input Voltage

1000V

Contact to Coil (VRMS)

5000V

Adjacent Contacts (VRMS)

2500V

12V AC/DC

24V AC/DC

48V DC

120V AC/DC

240V AC/DC

1K

2K

3K

34 K

72 K

AC

N/A

0.5V A

N/A

0.4V A

0.8V A

DC

0.4 W

0.5 W

0.8 W

0.5 W

0.7 W

Impedance (Ohms) Power Consumption ±10%

Pole to Pole (VRMS)

Mechanical

Degree of Protection

IP20

Mechanical Life Operations

3 x 107

Electrical Life Operations

250V AC/24V DC, 8 A Resistive: 100 000 min. 24V DC, 10 A Resistive: 6000 min. 250V DC, 0.28 A Resistive: 6000 min. 250V AC, 10 A Resistive: 30 000 min.

Switching Frequency Operations (no-load)

1200 cycles/sec

Coil Voltages Operating Time at Nominal Voltage at 20 °C (ms) Maximum Operating Rate (full load = 6 A)

See Overview/Product Selection Pickup typical 10 ms

Dropout typical 10 ms 6 cycles/min.

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

57

Page 58

General Purpose Relays

Cat. No. 700-HLT…2-Pole (Relay Output) Environmental

Temperature

Operating

–40…+60 °C

Storage

–40…+100 °C

Altitude

2000 m (6560 ft) Construction

Insulating Material

Molded High-Dielectric Material

Enclosure

Relay RT II, flux-proof, pollution degree 2 installation environment

Contact Material

AgNi 90/10 or AgNi 90/10 + Au

Terminal Markings on Socket

In accordance with EN50 0005

Certifications cULus Listed (File No. E3125, Guide NRNT/NRNT7), CE Marked

Standards

UL 508, CSA C22.2 No. 14, EN 61810-1

Dimensions - 700-HL (2-pole) Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. 92.8 (3.65)

87.7 (3.45)

14 (0.55)

14 (0.55)

75 (2.95)

75 (2.95)

Bulletin 700-HL Screw Terminal Design Single Wire: 0.14 mm2…2.5 mm2 (#26 AWG…14 AWG) Double Wire: 2 x 0.14 mm2…2 x 1.5 mm2 (2 x #26 AWG…2 x 16 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in). Torque: 0.5 N•m (4.4 lb•in)

Bulletin 700-HL Spring Terminal Design Single Wire: 0.2 mm2…2.5 mm2 (#24 AWG…#14 AWG) Wire Type: Solid or stranded, copper only Strip Length: 9 mm (11/32 in)

97.8 (3.85)

Bulletin 700-TBJ08_ 8-Way Jumper

58

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

Page 59

General Purpose Relays

6.2 (15/64)

50 (1-63/64)

5.2 (13/64)

12.5 (1/2)

1.0 (0.04)

35.0 (1.38)

27.0 (1.06)

7.5 (0.3)

1000 (39-3/8)

Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes

Cat. No.

A

B

C

D

Approx. Shipping Wt.

199-DR1

35 (1-3/8)

27 (1-1/16)

7.5 (19/64)

1.02 (1/64)

1.85 kg (4.07 lb) (10/pkg)

199-DR4

35 (1-3/8)

27 (1-1/16)

15 (19/32)

2.3 (3/32)

3.68 kg (8 lb) (5/pkg)

Rockwell Automation Publication 700-TD552B-EN-P - August 2018

59

Page 60

General Purpose Relays

700-HLF Terminal Block Timing Relay • Relay and socket assembled modules for high-density applications • Screw terminal bases • 6 A relay, choice of silver or gold contacts • SPDT (relay) • Four timing functions • Time range from 0.1 sec...6 hr • Built-in retainer clip and snap-in marker lever • Standard LED, reverse polarity protection, and surge protection • Externally replaceable relay modules

Wiring Diagram

Output Type

SPDT (1 C/O); Ith = 6A§

Recommended Tightening Torque

0.5 N•m max. (4.4 lb•in)

Wire Range

Screw Terminal: 0.14 mm2…2.5 mm2 (#26…#14 AWG)

Approvals cULus, cURus, CE

Assembled Device Input Voltage

Pkg. Quantity

Cat. No.(1)

24V AC/DC

10

700-HLF1U24

(1) For gold-plated contacts add an X after the catalog number listed.

Accessories - 700-HLF Relays Terminal block timing relay bases are not sold separately. Photo

Description

Pkg. Quantity

Socket Input Voltage

Cat. No.

Replacement Relays Order must be for 20 relays or multiples of 20.

20

24V AC/DC

700-TBR24(1)

Color 20-Way Jumper Can be cut to required length. Ith = 36 A max per 20-way jumper.

1

Red

700-TBJ20R

Grey

700-TBJ20G

Blue

700-TBJ20B

End Barrier Used for visual inspection of groups, safe separation of neighboring 700-HL modules that end with jumpers.

10

Black

700-HN177

Snap-in Marker These snap-in markers have a 6 x 10 mm surface and snap into the ejection lever for the relay.

100

Blank

1492-MC6X10

(1) For gold-plated contacts: Add the letter “X” at the end of the catalog number. For example: if Cat. No. 700-TBR24 is required with gold plating, the new cat. no. is 700-TBR24X.

60

Rockwell Automation Publication 700-TD552B-EN-P - August 2018