The text of a spec sheet · part 9 of 25
Relay and Timer Specifications, Bulletin Number 700, pages 81 to 90
Pages 81 to 90 of 250
The original document is the PDF (23 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX
Page 81
General Purpose Relays
Specifications - 700-HHF Relays Attribute
700-HHF… 85…110% of Nominal Voltage at 50 Hz
Permissible Coil Voltage Variation
85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC SPST-NO-DM 50 Hz
Coil Consumption ±10%
AC Coils
DPDT 60 Hz
3PDT
50 Hz
60 Hz
50 Hz
60 Hz
Inrush
7.2 VA
6.3 VA
7.2 VA
6.3 VA
7.2 VA
6.3 VA
Sealed
4.8 VA
4.2 VA
4.8 VA
4.2 VA
4.8 VA
4.2 VA
DC Coils
1.4 W 25% of VA
Max. Allowable Leakage
10% of W
Design Specification/Test Requirements Dielectric Withstand Voltage
Pole-to-Pole
2200V AC
Contact-to-Pole
2200V AC
Contact-to-Frame
1600V AC
Mechanical Mechanical Life Operations
5 x 106
Switching Frequency Operations
3600/Hr
Coil Voltages Operating Time at Nominal Voltage at 20 °C
See Overview/Product Selection Pickup
20 ms
Dropout
15 ms
Maximum Operating Rate
4 Ops/s.
Environmental –30…+50 °C
Operating
(–22…+122 °F)
Temperature
–30…+100 °C
Storage
(–22…+212 °F)
Altitude
2000 m (6560 ft)
Construction Insulating Material
Molded High Dielectric Material
Enclosure
Transparent Dust Cover
Contact Material
Silver Cadmium Oxide
Terminal Markings
In accordance with EN50 0005 (2)
Sockets Certifications cURus Recognized, File E3125,Guide NLDX2/NLDX8, CE Marked
Standards
UL 508, CSA 22.2 No.14, EN/IEC 60947-1, -5-1
(1) See NEMA Ratings and Test Values on page 5. (2) 700-HHF relay wiring and terminals are the quick connect / solder type 6.35 x 0.82 mm (0.250 x 0.032 in) termination.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
81
Page 82
General Purpose Relays
Dimensions - 700-HHF Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
35.7 (1-13/32)
3.97 (5/32)
63.5 (2-1/2)
38.9 (1-17/32)
73.8 (2-29/32) 700-HHF Relay
82
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 83
General Purpose Relays
700-HTA Alternating Relay • Alternating Relay • Rugged Pin Style Socket Mounting • 10 A, SPDT, DPDT, and Cross Wired • Excellent for Pump Panel Applications
700
– a
HTA
2
A12
7 b c d e
Catalog Number Explanation - 700-HTA Relays a Bulletin Number
-
700 b Relay Type c Model Type d Coil Voltage e Gold Plated Contacts Option
HTA - Tube Base Alternating Relay
1 - SPDT 2 - DPDT 3 -Cross-Wired
A12 - 12V AC 50/60 Hz A24 - 24V AC 50/60 Hz A1 - 120V AC 50/60 Hz A2 - 240V AC 50/60 Hz
Blank - Without switch 7 - With switch
Alternating Relays with Pin-Style Terminations 700-HTA
Alternating Relay
SPDT Form C Contact
SPDT
DPDT 2 Form C Contact
DPDT
Cross-Wired DPDT 2 Form C Contacts
Cross-Wired
Wiring Diagrams U.S./Canada
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
International
83
Page 84
General Purpose Relays
Accessories - 700-HTA Relays Photo
84
Description
Pkg. Qty. Cat. No.
Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Guarded Terminal Construction. 8-Pin for use with 700-HTA1A or -HTA3A alternating relays. Order ten or multiples of ten.
10
700-HN100
Screw Terminal Tube Base Socket, Panel or DIN Rail Mounting; Open Style Construction. 8-Pin for use with 700-HTA1A or -HTA3A alternating relays. Order ten or multiples of ten. No retainer clip required.
10
700-HN125
Screw Terminal Tube Base Sockets, Panel or DIN Rail Mounting; Guarded Terminal Construction. 11pin for use with 700-HTA2A alternating relays. Order in multiples of 10.
10
700-HN101
Screw Terminal Tube Base Sockets, Panel or DIN Rail Mounting; Open Style Terminal Construction. 11-pin for use with 700-HTA2A alternating relays. Order in multiples of 10. No retainer clip required. 10
700-HN126
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Retainer Clip for Cat. Nos. 700-HN100 and -HN101 Sockets with 700-HT Timing Relays, and 700-HTA Alternating Relays Secures relay in socket. Order must be for 10 clips or multiples of 10.
10
700-HN110
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N41
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 85
General Purpose Relays
Specifications - 700-HTA Relays Attribute
700-HTA Electrical Ratings
Pilot Duty Rating (1)
NEMA B300 AC 15
Rated Thermal Current (Ith)
10 A
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA Inductive
Contacts
Make
Break
120V AC
30 A
3A
1/3
240V AC
15 A
1.5 A
1/2
Resistive 30V DC
10 A
10 A, 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz
Permissible Coil Voltage Variation
Power Consumption ±10%
HP
AC
24V AC
2 VA
120V AC
4 VA
240V AC
4 VA
Design Specification/Test Requirements
Dielectric Withstand Voltage
Pole-to-Pole, same circuit (VRMS)
1000V AC
Pole-to-Pole, different circuits (VRMS)
2000V AC
Contact-to-Coil (VRMS)
2000V AC
Electrical Life Operations
100,000 minimum
Switching Frequency Operations
1800/hr
Coil Voltages
See product selection Mechanical
Degree of Protection
Open Type (Guarded Terminal Sockets)
Mechanical Life Operations
10 x 106
Switching Frequency Operations
18,000/hr
Start-up Time (max. time from power application until unit is timing)
0.05 sec
Max. Function Time (max. time power can drop out and unit continues timing)
0.01 sec
Min. Cycle Time
100 ms on release of the control switch
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
85
Page 86
General Purpose Relays
Specifications - 700-HTA Relays Attribute
700-HTA Environmental
Operating
–28…+65 °C (50 °C max., 240V AC coil) (–18…+149 °F) (122 °F max., 240V AC coil)
Storage
–55…+85 °C (–67…+185 °F)
Temperature
Altitude
2000 m (6560 ft) Construction
Insulating Material
Molded High Dielectric Material
Enclosure
Impact Resistant Dust Cover
Contact Material
Silver Tin Oxide
Terminal Markings on Socket Sockets
In accordance with EN50 005 8- or 11-Pin Socket 700-HN100, -HN125 700-HN101, -HN126
Certifications
CSA Certified, File 223833, UL Recognized (File E3125 Guide NLDX2/NLDX8), cULus Listed with 700-HN100, 700-HN101, 700-HN125, and 700-HN126 Sockets (File No. E3125 Guide NLDX/NLDX7), CE-Marked (per EU Low Voltage Directive)
Standards
EN 61812-1, CSA 22.2 No. 14, UL 508
(1) See NEMA Ratings and Test Values on page 5
86
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 87
General Purpose Relays
Trigger Signal Cat. Nos. 700-HTA Contact closure provides signal to timer. The 700-HTA alternating relay generates a low energy signal. For optimum reliability, use contacts designed for low energy switching (10V, 1 mA) (Example: Bul. 800F-X_V, 800T-X_V). No external voltage can be connected to the contact signal.
Load Diagrams - 700-HTA Relays Cross Wired Lead/Lag/Lag/lead Sequence
Common Input/Output SPDT/DPDT Lead
B1 Load A
Lag
Load B
Load A
LED A
Load B
LED B
LED A LED B
Power
Power Socket Pinout Map SPDT Relay Socket 4 A1 3 A2
Socket Pinout Map DPDT Relay Socket 4 A1 8 A2
Note: pin out in wiring diagram may not match actual printed socket see pinout map for wiring up the power source
Socket Pinout Map Cross-Wired Relay Socket 3 A1 6 A2
Note: pin out in wiring diagram may not match actual printed socket see pinout map for wiring up the power source
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
87
Page 88
General Purpose Relays
Dimensions - 700-HTA Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
79 (3-7/64)
74 (2-29/32)
60 (2-23/64) 43 (1-11/16)
24.6 (31/32)
40.1 (1-37/64)
20.8 (53/64)
30.0 (1-3/16) 26 (1-1/32)
24.9 (63/64)
65.0 (2-35/64)
54.9 (2-5/32) 51.1 (2-1/64)
4.2 (5/32) 38.0 (1-1/2) #4–40 M3
Cat. No. 700-HN100 Panel Mounting Double Wire, 2 x 2.5 mm2 (#2 – 14 AWG…#2 – 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)
33.0 (1-19/64)
14.7 (37/64)
Cat. No. 700-HN125 Wire Size: 2 x 2.5 mm2 Single Wire, Up to #12 AWG Double Wire, 2 x 2.5 mm2 (#2 – 14 AWG… #2 – 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in), Torque: 0.8 N•m (7 lb•in)
59.2 (2-1/3) 30 (1-3/16)
26 (1-1/32)
7.9 (0.31)
24.6 (31/32) 20.8 (53/64) 26.9 (1.06) 54.9 (2-5/32)
65.0 (2-35/64)
4.2 (5/32)
51.1 (2-1/64)
38.0 (1-1/2) #4-40 M3
Cat. No. 700-HN101 Panel Mounting Double Wire – 2 x 2.5 mm2 (#2 – 14 AWG…#2 – 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)
88
52.3 (2.06)
Cat. No. 700-HN126 Wire Size: 2 x 2.5 mm2 Single Wire, Up to 12 AWG Double Wire, 2 x 2.5 mm2 (#2 – 14 AWG…#2 – 20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in), Torque: 0.8 N•m (7 lb•in)
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 89
General Purpose Relays
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
89
Page 90
General Purpose Electronic Timers and Counters
General Purpose Electronic Timers and Counters Product Overview
Bulletin No.
700-FE
700-FS
700-HR52, -HRP, -HRS, -HRT, -HRV
700-HRM/-HRC
700-HRF
Type
DIN Rail Timer
DIN Rail Timer
Multifunction Timer
On-Delay Timer
Twin Timer
Features
• Only 17.5 mm wide • 5 A contact rating • Multifunction or single function • No additional socket required
• Only 22.5 mm wide • 8 A contact rating • Multifunction or single function • No additional socket required • Optional: • Star-delta timing function • True off-delay timing function • Hazardous location certification
• Dial timing relays • 5 A contact rating • Multiple programmable timing ranges • Tube base pin style terminals • Multi-voltage inputs • Timed contacts and instantaneous contacts • Transistor outputs • Single function and multifunction • 7 different operating modes
• Dial timing relays • 5 A contact rating • Multiple programmable timing ranges • Tube base pin-style terminals • Multi-voltage inputs • Timed contacts and instantaneous contacts • Transistor outputs • Single function and multifunction
• Independent ON and OFF settings • 14 time ranges • 8-pin models available • Dial timing relays • UL508
Control Outputs: Time Limit Instantaneous
1 N.O. or SPDT timed
SPDT or DPDT or 2 N.O. + 1 common
DPDT Timed, Transistor SPDT Timed/Instantaneous
DPDT Timed, Transistor SPDT Timed/Instantaneous
DPDT Timed
On-delay Off-delay One shot Operation Modes: Repeat cyclepulse Fleeting off-delay Pulse converter
11 timing modes
On-Delay Off-Delay One Shot Repeat Cycle Off Start Repeat Cycle On Start Signal On/Off-Delay On-Delay One Shot
On-Delay
Repeat Cycle Off Start Repeat Cycle On Start
Time Range
0.05 s…10 hr
0.05 s…60 hr
0.05 s…300 h
0.05 s…300 h
0.05 s…300 h
Supply Voltage
24V AC/DC 110…240V AC 24…48V AC/DC 24…240V AC
12V DC 24V…48V DC 24V…240V AC
12…48V DC 24…48V AC 100…240V AC 100…125V DC
12…48V DC 24…48V AC 100…240V AC 100…125V DC
12V DC 24V AC/DC 48…125V DC 100…240V AC
Contact Rating at 120V AC
5A
8A
5A
5A
5A
Certifications
CE, cULus
CE, cULus cURus, CE, C-Tick cURus, CE, C-Tick cURus, CE, C-Tick
Socket Cat. No(s).
DIN Rail or panel mount
DIN Rail or panel mount
700-HN100 OR 700-HN101 700-HN125 OR 700-HN126
700-HN100 700-HN125
700-HN100 700-HN125
Page
92
96
116
117
117
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
89