The text of a spec sheet · part 8 of 25
Relay and Timer Specifications, Bulletin Number 700, pages 71 to 80
Pages 71 to 80 of 250
The original document is the PDF (23 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700-HA33Z24, Allen-Bradley 700-HN153, Allen-Bradley 700-HA32Z24 and Allen-Bradley 700-HX
Page 71
General Purpose Relays
700-HJ Magnetic Latching Relay • 10 A Contact Rating • SPDT • DPDT Single Coil • DPDT Dual Coil • Blade Style Quick Connect Terminals Photo
Description
SPDT 1-Pole 1 Form C AgCdO Contacts (Single Coil AC or DC)
Contact Rating
700-HN153
Sockets
DC(3)
Coil Voltage
Cat. No.
24V AC
700-HJ36A24
120V AC
700-HJ36A1
24V DC
700-HJ36Z24
24V AC
700-HJ32A24
120V AC
700-HJ32A1
240V AC
700-HJ32A2
12V DC
700-HJ32Z12
24V DC
700-HJ32Z24
24V DC
700-HJD32Z24
700-HN154
10 A
Sockets
DPDT 2-Pole 2 Form C AgCdO Contacts (Dual Coil(1)
AC(2)
10 A
Sockets
DPDT 2-Pole 2 Form C AgCdO Contacts (Single Coil AC or DC)
Wiring Diagrams
700-HN153
10 A
700-HN154
DC Only
700-HN153 or 700-HN154
(1) Available only in DC Coil with DPDT contacts. (2) AC Relays include internal diodes. (3) For DC operation, polarity must be observed.
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
71
Page 72
General Purpose Relays
Accessories-700-HJ Relays Photo
Description
Pkg. Qty.
Cat. No.
Screw Terminal Socket, Panel or DIN Rail Mounting. Guarded Terminal Construction 11-blade socket for use with 700-HB relays. This socket has coil and contact separation as well as the ability to use optional plug-in modules ( 700-A__ accessories, LED, surge suppression, timing modules).
10
700-HN153
Screw Terminal Base Socket, Panel or DIN Rail Mounting. Open Style Construction 11-blade for use with 700-HB relays.
10
700-HN154
DIN (#3) symmetrical hat rail 35 x 7.5 x 1 m
10
199-DR1
Retainer Clip For Cat. Nos. 700-HN153 and -HN154 Sockets with 700-HJ Relays Secures relay in socket. Order must be for 10 clips or multiples of 10.
10
700-HN159
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N41
Socket and Retainer Clip Reference Relay Type 700-HJ
Socket Cat. No.
Retainer Clip Cat. No.
700-HN153
700-HN159
700-HN154
700-HN159
Specifications - 700-HJ Relays Attribute
700-HJ Electrical Ratings
Pilot Duty Rating, Rated Thermal Current (Ith)
10 A
Rated Insulation Voltage (Ui)
250V IEC, 300V UL/CSA Inductive
Contacts
120V AC 240V AC DC
Permissible Coil Voltage Variation
72
Make
Break
Hp
30 A 15 A
3A 1.5 A 24V DC, 10 A 85…110% of Nominal Voltage at 50 Hz 85…110% of Nominal Voltage at 60 Hz 80…110% of Nominal Voltage at DC
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
1/4 1/3
Page 73
General Purpose Relays
Specifications - 700-HJ Relays Single AC Coil AC Coils
Inrush Sealed
Coil Consumption ±10% DC Coils
Single DC Coil
Dual DC Coil
1.44 VA 1.44 VA, - - 1.2 W
12V 1.63 W 24V 1.67 W
Design Specification/Test Requirements
Dielectric Withstand Voltage
Pole-to-Pole
1500V AC
Contact-to-Pole
1500V AC
Contact-to-Frame
1500V AC Mechanical
Open Type (Guarded Terminal Sockets)
Degree of Protection Mechanical Life Operations
10 x 106
Switching Frequency Operations
1800/HR
Coil Voltages Operating Time at Nominal Voltage at 20 °C
See Product Selection Pickup Dropout
25 ms 25 ms
Maximum Operating Rate, Environmental
Operating
–45…+50 °C (–49…+122 °F)
Storage
–45…+100 °C (–49…+212 °F)
Temperature
Altitude
2000 m (6560 ft.) Construction
Insulating Material Enclosure Contact Material Terminal Markings on Socket Sockets
Molded High Dielectric Material Transparent Dust Cover Silver Cad. Ox. In accordance with EN50 0005 11-Blade Socket Cat. No. 700-HN153 Cat. No. 700-HN154
Certifications
CSA Certified, File LR700026, UL Recognized, File E3125, Guide NLDX 2
Standards
UL 508, CSA 22.2 No. 14, EN/IEC 60947-4-1, -5-1
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
73
Page 74
General Purpose Relays
Dimensions - 700-HJ Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
700-HJ Relay
Cat. No. 700-HN153 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in
Cat. No. 700-HN154 Wire Size: 2 x 2.5 mm2 Single Wire – Up to #12 AWG Double Wire – 2 x 2.5 mm2 (#2–14 AWG… #2–20 AWG) (Either Solid or Stranded) Strip Length: 9 mm (3/8 in) – Torque: 0.8 N•m (7 lb•in)
5.2 (13/64)
6.2 (15/64)
50 (1-63/64)
12.5 (1/2)
1.0 (0.04)
35.0 (1.38)
27.0 (1.06)
7.5 (0.3)
1000 (39-3/8)
Cat. No. 199-DR1 DIN Mounting Rail Series B Cat. No. 199-DR4 DIN Mounting Rail Series B Has No Mounting Holes
Cat. No.
A
B
C
D
Approx. Shipping Wt.
199-DR1
35 (1-3/8)
27 (1-1/16)
7.5 (19/64)
1.02 (1/64)
1.85 kg (4.07 lb) (10/pkg)
199-DR4
35 (1-3/8)
27 (1-1/16)
15 (19/32)
2.3 (3/32)
3.68 kg (8 lb) (5/pkg)
74
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 75
General Purpose Relays
700-HG Power Relay • 40 A Contact Ratings • SPST-NO-DM, SPDT, DPST-NO, DPDT • Panel Mounted • Options: Magnetic Blowout for High DC Loads, Auxiliary Snap Action Switch • Screw Terminals #6-32 for Coil, #8-32 for Contacts Description
SPST-NO-DM 1 Form X AgCdO Contacts
SPDT 1-pole 1 Form C AgCdO Contacts
DPST-NO 2-pole 2 Form A AgCdO Contacts
DPDT 2-pole 2 Form C AgCdO Contacts
Contact Ratings
Wiring Diagrams
40 A (A600)
40 A (A600)
40 A (A600)
40 A (A600)
Coil Voltage
Cat. No.(1)
24V AC
700-HG45A24
120V AC
700-HG45A1
240V AC
700-HG45A2
277V AC
700-HG45A27
480V AC
700-HG45A4
12V DC
700-HG45Z12
24V DC
700-HG45Z24
48V DC
700-HG45Z48
110V DC
700-HG45Z1
24V AC
700-HG46A24
120V AC
700-HG46A1
240V AC
700-HG46A2
12V DC
700-HG46Z12
24V DC
700-HG46Z24
48V DC
700-HG46Z48
110V DC
700-HG46Z1
24V AC
700-HG47A24
120V AC
700-HG47A1
240V AC
700-HG47A2
480V AC
700-HG47A4
12V DC
700-HG47Z12
24V DC
700-HG47Z24
48V DC
700-HG47Z48
110V DC
700-HG47Z1
24V AC
700-HG42A24
120V AC
700-HG42A1
240V AC
700-HG42A2
277 AC
700-HG42A27
12V DC
700-HG42Z12
24V DC
700-HG42Z24
48V DC
700-HG42Z48
110V DC
700-HG42Z1
220V DC
700-HG42Z2
250V DC
700-HG42Z25
(1) Auxiliary Snap Switch Option: Add suffix (-5) to the selected 700-HG relay Cat. No., except for the 220V DC add (-5L). Magnetic Blowout Option: Add suffix (-6) to the selected 700-HG relay Cat. No. (suppresses the arc when switching DC loads – ratings listed below).
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
75
Page 76
General Purpose Relays
Accessories - 700-HG Relays Photo
Description
Pkg. Qty.
Cat. No.
Pre-Printed Identification Tags, contains 10 sheets of pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N40
Blank Identification Tags, contains 10 sheets of blank identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
700-N41
Type 1 Enclosure For use with any of the listed relays. Knockouts for 1/2 in. and 3/4 in. conduit connections. The enclosure exceeds the minimum clearances required by U.S. standards, resulting in generous wiring spaces.
1
700-HN120
Auxiliary Snap Action Switch Contact
Material
Rating
Dielectric Withstand V (1 Min.)
SPDT (1 Form C)
Silver Cad. Ox.
10 A at 120 or 240 Resistive
1500V AC RMS Contact to Frame
76
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 77
General Purpose Relays
Specifications - 700-HG Relays Attribute
700-HG
Electrical Ratings Pilot Duty Rating (1)
A600
Rated Thermal Current (Ith)
40 A
Rated Insulation Voltage (Ui)
600V UL Contact Ratings: AC Ratings SPST-NO-DM Inductive
Volts
Contact Ratings: AC Ratings SPDT, DPST - NO and DPDT Resistive Make/Break and Continuous
Make
Break
Continuous
120
60 A
6A
10 A
40 A
240
30 A
3A
10 A
40 A
480V
15 A
1.5 A
10 A
12 A
600V
12 A
1.2 A
10 A
10 A
Inductive HP
2
2
Volts
Resistive Make/Break and Continuous Continuous
Make
Break
120
60 A
6A
10 A
40 A
240
30 A
3A
10 A
40 A
480
15 A
1.5 A
10 A
5A
600
15 A
1.2 A
10 A
5A
HP (2)
1 - 1/2
1 - 1/2
DC Ratings: Without Magnetic Blowouts - 28V 40 A - Make, Break and Continuous Est Drop 125V 1.2...3 A SPST - NO DM
SPDT, DPST - NO and DPDT
110V
20 A
10 A
220V
8A
4A
325V
4A
2A
500V
2A, DC Ratings: With Magnetic Blowouts:
Make, Break, and Continuous
80...100% of Nominal Voltage at 50 Hz Permissible Coil Voltage Variation
85...110% of Nominal Voltage at 60 Hz 80...110% of Nominal Voltage at DC 50 HZ
Coil Consumption ±10%
AC Coils
60 HZ
Inrush
13 VA
16 VA
Sealed
10 VA
11 VA
DC Coils
2.0 W Design Specification/Test Requirements
Dielectric Withstand Voltage
Pole-to-Pole
2200V AC
Contact to Pole
2200V
Contact to Frame
2200V AC Mechanical
Degree of Protection
Open Type
Mechanical Life Operations
5 x 106
Switching Frequency Operations
1600/Hr
Coil Voltage
See Overview/Product Selection
Operating Time at Nominal Voltage at Pickup 20 °C Dropout
40 ms 35 ms
Maximum Operating Rate, Rockwell Automation Publication 700-TD552B-EN-P - August 2018
77
Page 78
General Purpose Relays
Specifications - 700-HG Relays Environmental Temperature
Operating
30...+55 °C (-22...+149 °F)
Storage
-30...+65 °C (-22...+149 °F)
Altitude
2000 m (6560 ft.) Construction
Insulating Material Enclosure Contact Material
Molded Thermo Setting Plastic, Silver Cadmium Oxide
Terminal Markings on Socket, Sockets, Certifications
CSA Certified, File 225674, UL Listed, File E3125, Guide NLDX, CE Marked
Standards
UL 508, CSA 22.2 No. 14, EN/IEC 60947-1, -5-1
(1) NEMA Rating Chart is on page 19 of publication 700-SG003B-EN-P. (2) For DPDT only: 2 Hp Switching 2 Poles, 200...600V AV, 50/60 Hz.
78
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
Page 79
General Purpose Relays
Dimensions - 700-HG Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
700-HG Relay, SPST-NO-DM
700-HG Relay
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
79
Page 80
General Purpose Relays
700-HHF Flange Mount Power Relay • Flange-Mounted • Blade Style 0.250 x 0.032 Quick Connect/Solder (no socket) Terminals • Solder Terminals (no socket) Description
SPST-NO-DM 1 Form X AgCdO Contacts
DPDT 2-Pole 2 Form C AgCdO Contacts
3PDT 3-Pole 3 Form C AgCdO Contacts
Wiring Diagrams
Contact Rating
U.S./Canada
International
30 A (A600)
25 A (B600)
20 A (B300)
Coil Voltage
Cat. No.
120V AC
700-HHF45A1
24V DC
700-HHF45Z24
24V AC
700-HHF62A24
120V AC
700-HHF62A1
240V AC
700-HHF62A2
12V DC
700-HHF62Z12
24V DC
700-HHF62Z24
120V AC
700-HHF73A1
Specifications - 700-HHF Relays Attribute
700-HHF…
Electrical Ratings
Pilot Duty Rating
SPST-NO-DM
NEMA A600
DPDT
NEMA B600
3PDT
NEMA B300
(1)
Rated Thermal Current (Ith)
SPST-NO-DM 30 A, DPDT 25A, 3PDT 20 A
Rated Insulation Voltage (Ui)
250V IEC-300V UL/CSA
Contacts
Inductive
SPST-NO-DM
120V AC
60 A
6A
1
30 A
3A
1
30 A
3A
1/2
240V AC
30 A
3.0 A
1-1/2
15 A
1.5 A
1-1/2
15 A
1.5 A, DC
80
Hp
28V DC, 30 A
DPDT
Hp
28V DC, 13 A
Rockwell Automation Publication 700-TD552B-EN-P - August 2018
3PDT
Hp