Page 9
Bulletin 700-P, -PK, -PH
Industrial Relays
Accessories, Continued Adder Decks Contacts Description
N.O.
N.C.
Continuous Carrying Current (A)
2, 10
2, 20
Arrangement
Cat. No. ➋
B1X
700-PB20
B4X
Second Deck (2-pole) 700-PKB20
B1Y
Second Deck Cat. No. 700-PB40
4, 10
4, 20
2, 10
2, 20
B4Y
B1X
B2X
B3X
B4X
B1Y
B2Y
B3Y
B4Y
700-PB40
Second Deck (4-pole)
C1X
700-PKB40 700-PC20
C4X
Third Deck (2-pole)
Third Deck Cat. No. 700-PC40
4, 10
4, 20
700-PKC20
C1Y
C4Y
C1X
C2X
C3X
C4X
C1Y
C2Y
C3Y
C4Y
700-PC40
Third Deck (4-pole) 700-PKC40
Contact Cartridges (Convertible from N.O. to N.C. and N.C. to N.O.) Description
Standard Contact Cartridge Cat. No. 700-CP1, -CP11Z
Standard Contact Cartridge AC Rating NEMA A600 DC Rating NEMA P600 Overlap Contact Cartridges ➊ Overlapping Used in pairs. N.O. contact closes before N.C. contact opens on pick-up and vice versa on drop-out.
Master Contact Cartridge Cat. No. 700-CPM
DC Rating NEMA P150 125V DC, 138 VA Make and Break
Master Contact Cartridge AC Rating Twice NEMA A600 DC Rating Twice NEMA P600
Logic Reed Cartridge for Low Energy Circuits ➊ 150V AC 500 mA 25 VA Max. 30V DC 200 mA 6 W Max. Logic Reed Cartridge Cat. No. 700-CPR
➊ Not Direct Drive. ➋ All Cat. Nos. are factory stocked.
236
AC Rating NEMA A600
Continuous Carrying Current (A)
Arrangement
Pkg. Qty.
Cat. No. ➋
10
OR
1
700-CP1
OR
2
700-CP11Z
OR
1
700-CPM
OR
1
700-CPR
10
5
20
Maximum 150V AC
Maximum 30V DC
500 mA
200 mA
Page 10
Bulletin 700-P, -PK, -PH
Industrial Relays
Accessories, Continued Pneumatic Time-Delay Unit – 1 N.O. and 1 N.C. Convertible Contact Cartridge ➊ Description Mode
Continuous Carrying Current (A)
Contacts N.O.
Arrangement
Cat. No. ➌
N.C.
D1X
10
Pneumatic Time-Delay
On-Delay/ Off-Delay
1
Timing Range
Open Type Without Enclosure
D2X
1
700-PT 0.1…60 s. 700-PKT
20
D1Y
D2Y
Bulletin 700-PS and -PSR Solid-State Timers Description
Continuous Carrying Current (A)
Timing Range ➋
Cat. No. ➌
0.1…2 s
700-PSAA1
0.4…8 s
700-PSBA1
1.5…30 s
700-PSCA1
S2
6…120 s
700-PSDA1
ADJ. POT.
0.1…2 s
700-PSPA1
0.4…8 s
700-PSRA1
1.5…30 s
700-PSTA1
6…120 s
700-PSUA1
0.1…2 s
700-PSRAA1
0.4…8 s
700-PSRBA1
1.5…30 s
700-PSRCA1
6…120 s
700-PSRDA1
0.1…2 s
700-PSRPA1
0.4…8 s
700-PSRRA1
1.5…30 s
700-PSRTA1
6…120 s
700-PSRUA1
Arrangement
External Initiating Contact
Self-Contained Potentiometer On-Delay
C1
S1
5 Output Contact (C1, C2)
C2
Off-Delay
L1
L2
110/120V, 50/60 Hz Power
External Potentiometer
C1 Output Contact (C1, C2)
On-Delay 5
C2
S1
S2
R1
R2
L1
L2
Off-Delay
Remote Pot. Max. Shielded Cable Length 50 FT UL Style #2517 or Equivalent ➊ Mounts on 4-pole Bulletin 700-P or -PK relay or 2-pole Bulletin 700-PH relay. ➋ Maximum time may be 50% greater and the minimum time may be 50% less than the value specified. ➌ All Cat. Nos. are factory stocked.
Remote Potentiometers for Cat. No. 700-PSR… Timing Range (s) 0.1…2 0.4…8 1.5…30 6…120
Resistance (MΩ) 0.75 0.75 2.0 3.5
Cat. No. 700-N35 700-N35 700-N36 700-N37
237
Page 11
Bulletin 700-P, -PK, -PH
Industrial Relays
Accessories, Continued Mechanical Latch Units Description
Arrangement D1X
D2X
Continuous Carrying Current (A)
Open Type Without Enclosure
Without
700-PLL⊗
10
700-PLL11⊗
20
700-PKLL11⊗
Without
700DC-PLL⊗
10
700DC-PLL10⊗
20
700DC-PKLL10⊗
K3
AC-Operated Latch Units D1Y
D2Y
K4
Reset Input D1X
D2X
K3
DC-Operated Latch Units
D1Y
Cat. No. ➊
D2Y
K4
⊗ AC Voltage Suffix Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700-PLL⊗ becomes Cat. No. 700-PLLA1. For other coil voltages, consult your local Allen-Bradley Sales Office.
Hz
24
127 200-208 220-230 230-240 277 347 380
415 440-480 460-480 500 575-600
50
B24 B48 A1*
48
110 110-115 115-120 120 B11†, - B27, B22
B2, - B3
B41
B44, B50, 60
A24 A48, A1*
B11†, A20
A22
A2
A27 A35, - - A4, A6, * Optimized for 115…120V, 60 Hz. Operates satisfactorily at 110V, 50 Hz. † Optimized for 110…115V, 50 Hz. Operates satisfactorily at 120V, 60 Hz.
⊗ DC Voltage Suffix Code
The Cat. No. as listed is incomplete. Select a voltage suffix code from the table below to complete the Cat. No. Example: Cat. No. 700DC-PLL⊗ becomes Cat. No. 700DC-PLLZ12. For DC Coils, see page 232. For other coil voltages, consult your local Allen-Bradley Sales Office. 6
12
18
24
32
48
64
72
90
115-125
230-250
500-550
575-600
Z06
Z12
Z18
Z24
Z32
Z48
Z64
Z72
Z90
Z1
Z2
Z5
Z6
Relays Per Strip
Pkg Qty.
Cat. No. ➊
4
5
700-MP4
8
5
700-MP8
12
5
700-MP12
16
5
700-MP16
Type 1 Enclosure – Use for all Bulletin 700-P, -PH and -PK relays except 10- and 12-pole DC relays or 5- and 6-pole DC Bulletin 700-PH relays. Order electrically held relays (Bulletin 700-P, -PH, or -PK) in a NEMA Type 1 enclosure directly from the tables on pages 229…232. This enclosure is also suitable for Bulletin 700-RTC timing relays.
1
700-N31
Type 4/4X Enclosure – For 2- and 4-pole Bulletin 700-P, -PH, -N and -R relays and 2-pole Bulletin 700-PH relays.
1
700-N39
Type 7 & 9 Enclosure – For 2- and 4-pole Bulletin 700-P, -PK, -N and -R relays and 2-pole Bulletin 700-PH relays. 1 conduit hub; top and bottom.
1
700-N33
Description
Mounting Strip Cat. No. 700-MP4
Cat. No. 700-N31
➊ All Cat. Nos. are factory stocked.
238
Universal Mounting Strips – Accepts Bulletin 700-P, -PH, -PK, -R, -RM, and -N control relays, as well as Bulletin 700-RTC timing relays. These strips are easily cut to the required length and bolted, riveted, or spot-welded in place. Relays are installed adjacent to one another on the mounting strip with the captive mounting screws provided. 5 strips/package.
Page 12
Bulletin 700-P, -PK, -PH
Industrial Relays Accessories, Continued
Description ot Cat. No. ® Mounting behind 1 700-N5 Surge Suppressors (RC Circuit), Surge suppressors _ [relay reduce the high transient voltages generated when the coil Surge Suppressor circuit is opened. These suppressors can be used with a Bulletin 700-P, -PH, -PK and -N relays, and other electromechanical devices. They contain a resistor and capacitor. Maximum ratings: 150V, AC or DC, 35 VA. eS ; Cat. No. 700-N5 requires 1 in. additional depth of Mounting on 00 ame enclosure. : i 1 700-N24 coil terminal Surge Suppressor Cat. No. 700-N24 24...48V AC/DC 1 199-FSMAQ MOV Surge Suppressors 15 J Used on Bulletin 700-P, -PH, -PK, -N, -F, -R (DC Only) and | 50...120V AC/DC 1 499-FSMA10 -RM (DC Only) relays. Mounting on coil terminal. 15J 1J=1Vx1Ax18 130...250V AC/DC 4 199-FSMA11 Surge Suppressor Cat. No. 199-FSMA1 Diode Surge Suppressor, for 6...300V DC voltage coils. Used on Bulletin 700-P, 1 199-ESMZ-1 -PH, -PK, -N, -F, and -R relays. << 35 A Jumper Kit, CSA Approved, UL Listed e@ This 35 A Jumper Kit can be used with any Bulletin 700-P and -PK AC or DC relay, Time-Delay relay or Latch Unit equipped with 20 A Master Cartridges. It does not require any additional panel space. Vo Jumper Kit terminals are designed for one #8 AWG wire or two #10 AWG wires. 1 700-CPH When connecting the two 20 A Master Cartridges in parallel, it is important that 35A Jumper Kit they be the same configuration (Normally Open or Normally Closed). Cat. No. 700-CPH . . Jumpers can be added to any contact cartridge location on a relay except the two center poles because of the wide spacing. An adhesive label is included with each < a kit listing the contact ratings. Le = Jumpers (Not applicable for Bulletin 700-PH or Jumper, For outer ys 2 -PK relays), For connection between a middle pole and an 700-N3 : : poles Jumper Jumper outer pole on the left or right side of the relay. Ip Ip. 50 Cat. No. 700-N3__ - Cat. No. 700-N4 Jumpers (Not applicable for Bulletin 700-PH or Jumper, For middle 700-N4 -PK relays), For connection between two middle poles. | poles Check Out Tool, Mechanically holds the Bulletin 700-P, -PH or -PK relay in the 700-N23 operated position for troubleshooting purposes. 1 Adapter Plate, Simplified relay conversion. Allows you to use the existing Check Out Tool mounting holes when you replace a Bulletin 700-B, -BR, -BX or -D relay with a 700-N34 Cat. No. 700-N23 Bulletin 700-P, -PH, or -PK relay. Protective Cover - For 700-PT Timing Adjustment Knob. Helps prevent tampering “ab at : 5 700-N38 with time setting. @ All Cat. Nos. are factory stocked. Allen-Bradley 239
Page 13
Bulletin 700-P, -PK, -PH
Industrial Relays Specifications Type
700-P, PLL, PT
700-PK, PKLL, PKT
700-PH
Electrical 10 A @ 600V AC 5 A @ 600V DC
Contact Rating Continuous Ratings Make/Break
35 A @ 600V AC 20 A @ 600V DC
AC
NEMA A600
2 x NEMA A600
2 x NEMA A600
DC
NEMA P600
2 x NEMA P600
2 x NEMA P600
Additional Contact Ratings for AC single-phase loads
Cartridge Cat. No. 700-CP1
Contacts in Series DC Switching
5 Hp @ 240V AC - N.O. 3 Hp @ 240V AC - N.O./N.C. 2 Hp @ 120V AC - N.O./N.C. 35 A General Use At 0.75 PF to 600V AC 35 A Tungsten Lighting Load to 480V AC
3 Hp @ 240V AC - N.O. 2 Hp @ 240V AC - N.O./N.C. 1 Hp @ 120V AC - N.O./N.C. 20 A Resistive Heating to 600V AC 20 A Tungsten Lighting Load to 480V AC, DC Current Ratings Make/Break
Coil Voltage Range
20 A @ 600V AC 10 A @ 600V DC
Cartridge Cat. No. 700-CPM
Cartridge Cat. No. 700-CPH
Volts DC 24
64
125 250
500
600
24
64
125
250
500
600
24 480W
64 480W
125 275W
250 138W
500 135W
1
5 A 2.2 A 1.1 A .55 A .24 A .2 A
10 A
5A
2.2 A
.55 A
.24 A
.2 A
10 A
5A
2.2 A
.55 A
.24 A
.2 A
2
10 A 10 A
20 A
10 A
5A
2A
.7 A
.5 A
20 A
10 A
5A
2A
.7 A
.5 A
5A
2A
.7 A
.5 A
3, - 7A
3 A 1.5 A 1.0 A, 15 A
7A
3A
1.5 A
1.0 A, 15 A
7A
3A
1.5 A
1.0 A
4, - 10 A 5 A 2.5 A 1.5 A, 20 A
10 A
5A
2.5 A
1.5 A, 20 A
10 A
5A
2.5 A
1.5 A
AC
85…110%
85…110%
85…110%
DC
80…110%
80…110%
80…110%
Battery Charging
85…115%
85…115%
85…115%
A Inrush Coil Consumption C Sealed P-PH-PK D Inrush C Sealed
50 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
132 VA
138 VA
132 VA
132 VA
19 VA
19.3 VA
138 VA 19 VA
138 VA 19 VA
19.3 VA 12.7 VA
12.7 VA
12.7 VA
12.7 VA
19.3 VA 12.7 VA 12.7 VA
PLL - PKLL
Inrush
15 VA
15.6 VA
5 VA
15.6 VA
15 VA
AC Latch Unit
Sealed
5.4 VA
5.5 VA
5.4 VA
5.5 VA
5.4 VA
PLL - PKLL
Unlatch
35 VA
35 VA
35 VA
DL Latch Unit
Intermitten t
35 W
35 W, Reset Time
PT – PKT
75 ms
75 ms, Minimum Pulse
PLL–PKLL
75 ms
15.6 VA
75 ms, 5.5 VA
Mechanical Pickup
AC – 10…20 ms DC – 30…50 ms
AC – 10…20 ms DC – 30…50 ms
AC – 10…20 ms DC – 30…50 ms
Dropout
AC – 10…20 ms DC – 20…33 ms
AC – 10…20 ms DC – 20…33 ms
AC – 10…20 ms DC – 20…33 ms
Operating Time Mechanical Life
10 million operations
Construction Contact Arrangement
Up to 12 Poles, Convertible to N.O. or N.C. (8 N.C. Maximum)
Up to 12 Poles, Convertible to N.O. or N.C. (8 N.C. Maximum)
Up to 6 Poles, Convertible to N.O. or N.C. (4 N.C. Maximum)
Nickel Silver
Silver Cadmium Oxide
Silver Cadmium Oxide
Panel or Strip Mount Horizontal Mounting Recommended
Panel or Strip Mount Horizontal Mounting Recommended
Panel or Strip Mount Horizontal Mounting Recommended
Contact Material Mounting
Environmental Temperature
Operating ➊
–20…+65°C (–4…149°F)
–20…+65°C (–4…149°F)
–20…+65°C (–4…149°F)
Storage
–40…+65°C (–40…149°F)
–40…+65°C (–40…149°F)
–40…+65°C (–40…149°F)
➊ Temperature inside the panel.
240
600 120W
Page 14
Bulletin 700-P, -PK, -PH
Industrial Relays
Specifications, Continued Operating Coils Bulletin 700 Bulletin 700-P-PH-PK Relays, Bulletin 700-PLL-PKLL Mechanical Latch Attachments ➊ Coil Volts 24
Bulletin 700-P Operating Coil
Bulletin 700-PL Unlatch Coil and Magnet Assembly
Bulletin 700-P, -PK 2-…12-pole, Bulletin 700-PH 1-…6-pole AC
Bulletin 700-PLL–PKLL AC Mechanical Latch Attachment
Bulletin 700-P-PK 2-…12-pole, Bulletin 700-PH 1-…6-pole DC
60 Hz
50 Hz
60 Hz
50 Hz, PA013
PA407
PL013
PL407
PD714 PD718
32, - - - 48
PA222
PA314
PL222
PL314
PD724
110 ➋, PA236, PL236
PD733 ➍ (100…110)
115…120 ➋
PA236, PL236, - 110…115 ➌, PA322, PL322, 115…125, - - - PD735
120 ➌
PA322, PL322, - 130…140, - - - PD738
200…208
PA249, PL249, - 220…230
PA251
PA339, PL339, 230…240
PA254
PA342
PL254
PL342, 230…250, - PD748, PD748
277
PA260, - - - 380, PA354, PL354, 415, PA357, PL357, 440…460, PA360, PL360, 460…480
PA273, PL273, - 500, PA364, PL364
PD759
575…600
PA273, PL278, PD758
➊ Coils for AC relays cannot be used in DC relays and vice versa. ➋ This coil is optimized for 115…120V, 60 Hz applications and will operate satisfactorily at 110V, 50 Hz. ➌ This coil is optimized for 110…115V, 50 Hz applications and will operate satisfactorily at 120V, 60 Hz. ➍ This coil is designed and marked for use at 100…110V DC.
241
Page 15
Bulletin 700-P, -PK, -PH
Industrial Relays
Approximate Dimensions Dimensions in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
Bulletin 700-P, -PH and -PK Relays AC – 97.63 (3-27/32) DC – 120.49 (4-3/4)
57.15 (2-1/4)
AC – 165.89 (6-17/32)
57.15 (2-1/4)
7.94 (5/16)
DC – 188.75 (7-7/16)
7.94 (5/16)
89.69 (3-17/32) 79.38 (3-1/8)
89.69 (3-17/32) 79.38 (3-1/8)
Provision for 2–#8/#10 Mfg. Screws Provision for 2–#8/#10 Mfg. Screws
2- and 4-pole Bulletin 700-P or -PK Relay, 2-pole Bulletin 700-PH Relay Approximate Shipping Weight AC – 0.68 kg (1.5 lbs.), DC – 1.34 kg (2.95 lbs.)
2- and 4-pole Bulletin 700-P or -PK Relay or 2-pole Bulletin 700-PH Relay with Pneumatic Time Delay Attachment Approximate Shipping Weight AC – 0.85 kg (1.88 lbs.), DC – 1.5 kg (3.33 lbs.)
AC – 130.97 (5-5/32) 57.15 (2-1/4)
DC – 153.83 (6-1/16)
AC – 165.89 (6-17/32) 7.94 (5/16)
57.15 (2-1/4)
DC – 188.75 (7-7/16)
7.94 (5/16)
89.63 (3-17/32)
89.63 (3-17/32) 79.38 (3-1/8)
79.38 (3-1/8)
Provision for 2–#8/#10 Mfg. Screws
Provision for 2–#8/#10 Mfg. Screws
2- and 4-pole Bulletin 700-P or -PK Relay or 2-pole Bulletin 700-PH Relay with Mechanical Latch Attachment Approximate Shipping Weight AC – 0.97 kg (2.13 lbs.), DC – 1.62 kg (3.58 lbs.)
6- and 8-pole Bulletin 700-P or -PK Relay, 4-pole Bulletin 700-PH Relay Approximate Shipping Weight AC – 0.79 kg (1.75 lbs.), DC – 1.45 kg (3.20 lbs.) AC – 164.31 (6-15/32) DC – 187.17 (7-3/8)
57.15 (2-1/4)
Cat. No. 700
7.94 (5/16)
34.93 (1-3/8)
89.69 (3-17/32) 79.38 (3-1/8)
{
-MP4 229 (9) -MP8 457 (18) -MP12 686 (27) -MP16 914 (36)
92.08 (3-5/8)
12.7 (1/2)
Provision for 2–#8/#10 Mfg. Screws
10- and 12-pole Bulletin 700-PPK Relay, 6-pole Bulletin 700-PH Relay Approximate Shipping Weight AC – 1.02 kg (2.25 lbs.), DC – 1.68 kg (3.7 lbs.) 109.54 (4-5/16)
123.83 (4-7/8)
28.58 (1-1/8)
57.15 (2-1/4)
57.15 (2-1/4)
#8 Screws (Captive)
Universal Mounting Strip for Bulletin 700-P, -PH, -PK, -N, -NM, -R, -RM, -RT, -RTA Relays Secure the mounting strip with 2 screws at each end relay position. Use a minimum of one screw at the 3rd, 5th, 7th, etc., relay positions. Alternate between upper and lower horizontal slots. AC – 164.7 (6-1/2) DC – 187 (7-25/64)
142.88 (5-5/8)
195.26 (7-11/16)
700-PS Timer
95.25 (3-3/4)
Type 1 Enclosure (Approximate Shipping Weight 1.04 kg (2.3 lb.) for Bulletin 700-P or -PK Relay (2…4-pole); Bulletin 700-PH Relay (1…2-pole only); Cat. No. 700-N31 NEMA Type 1 Enclosure for other Bulletin 700-P, -PH, -PK, -RTC Relays has same dimensions except the depth is 178 mm (7"). Approximate Shipping Weight 1.26 kg (2.8 lb.)
242
Bulletin 700-PS Timer Mounted on a 4-pole Bulletin 700 Bulletin 700-P or -PK Relay or 2-pole Bulletin 700-PH Relay. Approximate Shipping Weight AC – 0.68 kg (1.5 lbs.) without 700-PS, eDC – 1.34 kg (2.9 lbs.) without 700-PS