Spec sheet · Allen-Bradley
Bulletin 700S-CF, Bulletin 700S-P Safety Control Relays
Spec sheet16 pagesPDF 5.0 MB
Product guide for Allen-Bradley Bulletin 700S-CF and 700S-P safety control relays: selection, specifications, dimensions.
What this file really is
The old site listed this file as a spec sheet for the Allen-Bradley 700DC-F220, 700DC-F220Z24 and 700S-CF620DC. Linked as a spec sheet for the 700DC-F220, but it is a guide to the Bulletin 700S-CF and 700S-P safety control relays and does not name the 700DC-F220.
Names · 1 model
The models it names
Filed with · 2 models
Also filed with these models on the old site
Summary
What is in it
Allen-Bradley guide to the Bulletin 700S safety control relays with mechanically-linked contacts, used in safety circuits such as e-stops, safety gates and light curtains. For the 8-pole 700S-CF (including the 700S-CF620) and the 2 to 12 pole 700S-P (including 24V DC types such as the 700S-DCP220Z24) it gives product selection and coil voltage codes, contact ratings, coil data, operating times, environmental data, dimensions, and a diagram for expanding Bulletin 440 safety relay outputs.
Its parts
- Bulletin 700S-CF: Product Selection
- Bulletin 700S-CF: Specifications
- Bulletin 700S-CF: Dimensions
- Bulletin 700S-P: Product Selection
- Bulletin 700S-P: Specifications
- Bulletin 700S-P: Approximate Dimensions
- Bulletin 700S: Overview
From the sheet · read page by page
Key facts from this sheet
Each line names its page in the PDF.
Selection guide (publication 700S-SG001A-EN-E, October 2001) for Allen-Bradley Bulletin 700S-CF and Bulletin 700S-P safety control relays, which have mechanically-linked contacts on all poles. For both lines it gives catalog numbers and coil codes, specifications, dimensions and example safety circuits. It does not print the 700DC-F220 or 700DC-F220Z24 numbers the site files it under.
- What it is
- Safety control relays with mechanically-linked contacts on all poles, for safety feedback circuits p. 2
- 700S-CF poles
- 700S-CF: 8 poles, all permanently attached; AC or DC operating coils p. 3
- 700S-CF contacts
- 700S-CF: 6 N.O. + 2 N.C. (700S-CF620), 5 + 3 (700S-CF530), 4 + 4 (700S-CF440), 3 + 5 (700S-CF350) p. 4
- 700S-CF main poles
- 700S-CF: NEMA A600, P600; 20A UL general purpose current p. 5
- 700S-CF DC coils
- 700S-CF: DC coils from 9 to 250V; 24V also with built-in diode suppressor (DJ) p. 4
- 700S-CF temperature
- 700S-CF: -25 to +60°C operating at nominal current, -55 to +80°C storage p. 6
- 700S-P poles
- 700S-P: 2 to 12 poles, double-break, N.O. or N.C. (8 N.C. maximum) p. 10
- 700S-P rating
- 700S-P: 10 A @ 600V AC, 5 A @ 600V DC continuous; NEMA A600, P600 p. 10
- 700S-P coils
- 700S-P: 60 Hz AC suffixes A24, A1 (115-120V), A2 (230-240V), A27 (277V), A4 (460-480V); 24V DC types such as 700S-DCP220Z24 p. 9
- 700S-P temperature
- 700S-P: -20 to +65°C operating (inside the panel), -40 to +65°C storage p. 10
- 700S-P life
- 700S-P: 12.5 million operations mechanical life p. 10
- 700S-P mounting
- 700S-P: panel mount or 700-MP rail, horizontal mounting recommended p. 10
- 700S-P wiring
- 700S-P: 1X #18 AWG to 2X #12 AWG; 8 to 12 lb-in. torque p. 10
- 700S-P weight
- 700S-P 2- and 4-pole: about 0.68 kg (1.5 lbs.) AC, 1.34 kg (2.95 lbs.) DC shipping weight p. 11
What this sheet walks you through
- How mechanically-linked and double-break contacts work p. 2
- Choosing a 700S-CF relay and its coil voltage code p. 4
- 700S-CF contact ratings and coil specifications p. 5, 6
- 700S-CF dimensions and accessory sizes p. 7
- Choosing a 700S-P relay and its coil voltage code p. 9
- 700S-P specifications p. 10
- 700S-P dimensions and mounting on the universal rail p. 11
- Expanding Bulletin 440 safety relay outputs with 700S relays p. 12, 13
- Building a five-output circuit with three 700S-CF relays p. 14
- Building an eight-output circuit with 700S-P relays p. 15
Good to know
- 700S-CF: a pneumatic timer or latch accessory has no mechanically-linked guidance; its contacts are independent. p. 5
- 700S-CF: wire with sixteen or more strands needs an end ferrule. p. 5
- 700S-CF350 with a DC coil is limited to 40 degrees; 70°C ambient is allowed only with a 15% current reduction. p. 6
- 700S-P: contacts cannot be added, removed or changed, and there is no push-to-test function. p. 8
Questions this sheet answers
How many contacts does a 700S-CF620 have?
Eight poles: 6 N.O. and 2 N.C. p. 4
What does mechanically-linked mean on a 700S safety relay?
The contacts are linked together, so if a N.O. contact welds, all N.C. contacts stay open, and the other way round. p. 2
How do I order a 700S-CF with a 24V DC coil with built-in suppression?
Use the DJ coil code and remove the Z from the catalog number, for example 700S-CF440DJC. p. 4
What is the contact rating of a 700S-P relay?
10 A at 600V AC and 5 A at 600V DC continuous. p. 10
Can 700S relays add outputs to a Bulletin 440 safety relay?
Yes. The guide shows two 700S relays expanding Bulletin 440 safety relay outputs. p. 12
The whole text · 2 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file