Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a spec sheet · part 1 of 2

Bulletin 700S-CF, Bulletin 700S-P Safety Control Relays, pages 1 to 8

Pages 1 to 8 of 16

The original document is the PDF (5.0 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 700S-CF620DC

Page 1 read from a scan by OCR; it may hold reading errors

aie peed

Allen-Bradley

Bulletin 700S-CF Bulletin 700S-P

Safety Control Relays - The Safe Solution

Automation

SD gay Capea Seg py: Daeg iy jpderde ie) tg hte

Page 2

Safety Control Relays

Product Profile

Designed To Meet Worldwide Safety Standards Bulletin 700S-CF Bulletin 700S-P Rockwell Automation introduces a new category of relays designed to meet the latest and emerging worldwide safety standards. These safety control relays offer special features to enable you to design safe control circuits with current

700S-CF (8 pole) IEC mechanically-linked symbol ratings up to 20 Amps. Bulletin 700S Safety Control Relays provide mechanically-linked contacts on all poles. Mechanically-linked contacts are required in feedback circuits for modern safety applications, such as e-stops, safety gates, light curtains, and master control relays.

Mechanically-Linked Contacts This feature allows detection of a welded contact condition. Mechanically-linked contacts are linked together; they are not independent. If a N.O. contact welds, all N.C. contacts remain open. If a N.C. contact welds, all N.O. contacts remain open. 700S-P (4 –12 pole)

Double-Break Contacts

Easy Identification

This design provides better protection against contact welding

The red faceplate allows easy identification of safety than a single break design. It offers greater DC load breaking devices. This face place displays the IEC 60947-5-1 capability and better isolation. This feature also provides mechanically-linked symbol.

separation of N.O. and N.C. circuits. Double-break contacts open the circuits in two places, creating two air gaps and reducing the

Anti-Tamper probability of welded contacts by more that 50% compared to

The anti-tamper feature ensures the long-term integrity of your a single-break design.

safety system. All contact blocks are permanently fixed to ensure Double-break contacts reduce the probability of a welded contact.

that the safety function is not jeopardized. Manual operation and field modifications are prevented.

Page 3

Bulletin 700S-CF

Safety Control Relays 0

Bulletin 700S-CF • Positively guided/mechanically linked contacts • Mechanically-linked contacts symbol prominently displayed on front • Red face plate • 8 poles, all permanently attached • Ideal for use in safety circuits • AC and DC operating coils • SUVA third-party certification

TABLE OF CONTENTS Description

Page

Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Description

Page

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Description Bulletin 700S-CF Safety Control Relays provide mechanically linked, positively guided contacts, which are required in feedback circuits for modern safety applications. The positively guided N.C. auxiliary contacts will not change state if a N.O. contact welds. Use with safety relays to expand output capability.

Conformity to Standards

Approvals

Your order must include:

IEC 947-5-1 EN 50011, EN 50005, EN 50022 UL 508 VDE 0660 CSA C22.2 Part 14

CE Certified CSA Certified UL Listed, File E14840, Guide NKCR SUVA Third Party Certified

• Cat. No. of the relays required, complete with coil suffix. • Cat. No. of adder decks, timers and accessories required. • If required, the part number of replacement coils.

3

Page 4

Bulletin 700S-CF

Safety Control Relays Product Selection Type S-CF Safety Control Relays, 8-Pole AC and DC Coil Voltages

Connection Diagrams

700S-CF

Contacts

Main Contacts

AC Coils

DC Coils

Cat. No.

Cat. No. ➊

Auxiliary Contacts

33

53

61

73

83

34

54

62

74

84

33

53

61

71

83

54

62

72

84

53

61

71

81

54

62

72

82

N.O.

N.C.

6

2

700S-CF620⊗C

700S-CF620Z⊗C

5

3

700S-CF530⊗C

700S-CF530Z⊗C

4

4

700S-CF440⊗C

700S-CF440Z⊗C

3

5

700S-CF350⊗C

700S-CF350Z⊗C

K1

K1 34 33

K1 34

33

K1 34

⊗ AC Coil Voltage Suffix Code Voltage

12

24

32

36

42

50 Hz

R

K

V

W

60 Hz

Q

J

–

V

50/60 Hz

–

KJ

–

–

Voltage

230

230240

240

50 Hz

–

VA

60 Hz

–

–

50/60 Hz

KF

–

KA

48

100

X

Y

–

X

–

KY

277

347

T

–

A

T –

100110

110

120

127

200

KP

–

–

KP

KP

–

200220

208

208240

220230

D

P

S

KG

–

–

D

–

–

KG

–

–

F

H

L

KD

–

–

KG

–

–

–

–

–

440

480

500

550

600

380

380400

400

400415

–

–

N

–

G

B

–

M

C

–

I

E

–

–

–

N

B

–

–

C

–

–

–

KN

–

KB

–

–

–

–

⊗ DC Coil Voltage Suffix Code ➊ Voltage

9

12

24

36

48

60

64

72

80

110

115

125

220

230

250

Standard

R

Q

J

W

Y

Z

B

G

E

D

P

S

A

F

T

With diode suppressor, - DJ, - - - - - ➊When ordering DJ coil with built-in surge suppression, remove Z from the Cat. No. Example: Cat. No. 700S-CF440Z⊗C becomes Cat. No. 700S-CF440DJC.

4, - - - -

Page 5

Bulletin 700S-CF

Safety Control Relays Specifications General Cat. No. 700S-CF main poles front auxiliary contacts

Contact Ratings, NEMA

A600, P600

A600, Q600

UL General Purpose Current

20A

!0A

Minimum Contact Rating Contact Ratings, IEC AC-15 (solenoids, contactors) at rated voltage IEC 947, EN 60947

40°C AC-12 (Control of AC resistive loads) IEC 947, EN 60947

60°C

DC-12 (Control of DC resistive loads) IEC 947 EN 60947

DC-13 IEC 947, EN 60947, Solenoids and contactors

17 – 19.9V

Main

30 mA

20 – 24V

20 mA

24V

15 A

6A

48V

15 A

6A

120V

14 A

6A 5A

240V

10 A

400/415V

5A

3A

480V/500V

2.5 A

1.6 A

600V

1.8 A

1.2 A

690V

1A

1.0 A 10 A

Ith

20 A

230V

10 kW

400V

17 kW

690V

30 kW

Ith

20 A

230V

8 kW

400V

14 kW

690V

24 kW

24V

12 A

48V

9A

9A

60V

5.0 A

3.5 A

110V

3.5 A

3.5 A

125V

3.0 A

3.0 A

220V

0.55 A

0.55 A

440V

0.2 A

0.2 A

24V

5A

5A

48V

2A

2A

60V

1.5 A

1.5 A

Yes

Mechanically Front aux. -linked Left side Contacts ➋ aux. Right side aux.

Open

Open ➌

Open

Open

Open

Open ➌

Open

Open

Open

Open ➌

Open

Open

Open

Open ➌

Open

Open

➋ Defined in IEC 947-5-1 annex L. Mechanically-linked is a relationship between contacts of opposite types (i.e., N.O. and N.C.). ➌ If the accessory is a pneumatic timer or latch, there is no mechanically-linked guidance; the accessory contacts are independent.

6A

12 A

125V

0.7 A

0.55 A

220V

0.25 A

0.25 A

440V

0.12 A

0.12 A

600V

0.1 A

0.1 A

Avg-Mechanical Life (ops)

[Mil]

15

15

AverageElectrical Life (ops)

[Mil]

1.1

0.75

2 x A4

2 x A4

1 or 2 Solid/ Conductor Stranded ➊ Conductor

[mm2] [mm2]

1.5…6 1… 4

0.5…2.5 0.75…2.5

Max. Wire Size per UL/CSA

[AWG]

16…10

18…14

Tightening Torque

[lb.-in.]

8.9…22

8.9…13.3

Tightening Torque

[N•m]

1…2.5

1…1.5

AC-15 (240V, 3 A)

Yes

Location of State of N.C. Contacts if N.O. contact welds welded Left side N.O. Main Front aux. Right side aux. aux. contacts

Terminal Cross-Sections Terminal Type Terminal Size per IEC 947-1

➊ For sixteen or more strands, end ferrule is required.

5

Page 6

Bulletin 700S-CF

Safety Control Relays Specifications, Continued General

Control Circuit Cat. No. 700S-CF Operating Voltage AC 50/60 Hz DC ➊

IEC

DC

[x Us]

0.85…1.1

UL; CSA

600V

Dropout

[x Us]

0.3…0.6

Dielectric Withstand Voltage

2500V

Pickup

[x Us]

0.8…1.1

Rated Impulse Strength Uimp

8 kV ➋

Dropout

[x Us]

0.1…0.6

Rated Voltage Ue AC

115, 230, 400, 500, 690V

Inrush

[VA/W]

70/50

DC

24, 48, 110, 220, 440V

Seal

[VA/W]

8/2.6

[W]

6.5

Short-Circuit Protection IEC 947-5 Fuse-Type GG

Inrush/Seal warm coil Inrush/Seal cold coil

[W]

8.5

Pickup Time

[ms]

15…30

Dropout Time

[ms]

10…60

Pickup Time

[ms]

40…70

Dropout Time

[ms]

7…15

With integrated suppression

[ms]

14…20

With diode suppression

[ms]

70…95

DC

Rated Frequency

➊ For 9V DC, code ZR, use operating voltage 0.65… 1.3 x Us. For 24V DC, code ZJ or DJ, use operating voltage 0.7… 1.25 x Us.

20 A 50/60 Hz, DC

Ambient Temperature Storage

Operating Times AC 50/60 Hz

690V

Pickup

Coil Consumption at nominal voltage AC 50/60 Hz

Cat. No. 700S-CF Rated Insulation Voltage Ui

–55…+80°C (–67…176°F)

Operation at nominal current

–25…+60°C (–13…140°F)➌➍

Corrosion Resistance humid-alternating climate, cyclic, per IEC 68-2-30 and DIN 50 016, 56 cycles

Altitude

2000 m above mean sea level, per IEC 947-4

Type of Protection

IP2X in connected state

Finger Protection safe from touch by fingers and back of hand per VDE 0106, Part 100

➋ 8 kV for main poles, 6 kV for front aux. contacts. ➌ 40 degree max. for 700S-CF350 with DC coil. ➍ Operation in 70°C ambient is permitted with current reduction of 15% below rated values

6

Page 7

Bulletin 700S-CF

Safety Control Relays Dimensions c2

➊ c1 c

AC Safety Control Relays a b

45 (1-25/32)

81 (3-3/16)

c c1 119.5 (4-3/4)

114.5 (4-43/64)

c2 6 (1/4)

∅d d1 d2

Cat. No. ➊

2 - 4.5 (2 - 3/16)

60 (2-23/64)

35 (1-25/64)

700S-CF

∅d d1 d2

Cat. No. ➊

2 - 4.5 (2 -3/16)

60 (2-23/64)

35 (1-25/64)

700S-CF

DC Safety Control Relays a b

45 (1-25/32)

81 (3-3/16)

c c1

145.5 (5-49/64)

140.5 (5-37/64)

c2 6 (1/4)

➊ All Cat. Nos. are factory stocked.

Accessories Safety Control Relays with mm

(inches)

Auxiliary contact block for side mounting 1- or 2-pole a+9

(a + 23/64)

Electronic Timing Module on coil terminal side b + 24

(b + 15/16)

Mechanical Interlock on side of contactor a+9

(a + 23/64)

Interface Module on coil terminal side b+9

(b + 23/64)

Surge Suppressor on coil terminal side b+3

(b + 1/8)

Labeling with label sheet marking tag sheet with clear cover marking tag adapter for System Bul. 1492W

+0 +0 + 5.5

(+ 0) (+ 0) (+ 7/32)

Mounting Positions

Mounting Position

AC Safety Control Relays

DC Safety Control Relays

7

Page 8

Bulletin 700S-P

Safety Control Relays 0

Bulletin 700S-P • Mechanically-linked contacts meeting IEC 947-5-1-L • 2…12 poles–all mechanically-linked • Red faceplate for easy identification of safety circuits • IEC mechanically-linked contacts symbol displayed on front • Double-break contacts to reduce probability of welded contacts • Visual indication of contact state • Tamper resistant Lexan® cover helps prevent changes which could jeopardize safety • Complete catalog number displayed on front • Ideal for use in safety circuits TABLE OF CONTENTS Description

Page

Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Description

Page

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

Description The 700S-P safety control relay is designed with special features for use in safety circuits. It is designed to reduce the possibility of a welded contact, and, with external monitoring, a welded contact can be detected if one ever occurs. It features mechanically linked contacts for all N.O./N.C. contact pairs which allow detection of a welded contact in any of the poles. Contacts cannot be added, removed, nor changed so that the safety function is never jeopardized. Similarly, there is no “push-to-test” function so that safety function is not jeopardized. Typical applications: use with E-stops, light curtains, safety gates, safety interlocks.

Conformity to Standards

Approvals

NEMA ICS-5-2 cULus Listed EN/IEC 60947-5-1, including UL File #E14840, Guide NKCR Mechanically-linked Contacts CE Certified IEC 337-1 CENELEC BS 4794 VDE 0660 CSA C22.2 No. 14 ANSI B11.19, section 5.5.1, Control Reliability UL508

8

Your order must include: • Cat. No. of the relays required, complete with coil suffix.