The text of a spec sheet · part 10 of 27
Relay and Timer Specifications, Bulletin Number 700: General Purpose Electronic Timers and Counters, pages 89 to 98
Pages 89 to 98 of 250, from Relay and Timer Specifications, Bulletin Number 700
The original document is the PDF (17 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Allen-Bradley 700S-CFB620EJC
Page 89
Relay and Timer Specifications
General Purpose Electronic Timers and Counters Product Overview
Bulletin No.
700-FE
700-FS
700-HR52, -HRP, -HRS, -HRT, -HRV
700-HRM/-HRC
700-HRF
Type
DIN Rail Timer
DIN Rail Timer
Multifunction Timer
On-Delay Timer
Twin Timer
Features
• Only 17.5 mm wide • 5 A contact rating • Multifunction or single function • No additional socket required
• Only 22.5 mm wide • 8 A contact rating • Multifunction or single function • No additional socket required • Optional: • Star-delta timing function • True off-delay timing function • Hazardous location certification
• Dial timing relays • 5 A contact rating • Multiple programmable timing ranges • Tube base pin style terminals • Multi-voltage inputs • Timed contacts and instantaneous contacts • Transistor outputs • Single function and multifunction • 7 different operating modes
• Dial timing relays • 5 A contact rating • Multiple programmable timing ranges • Tube base pin-style terminals • Multi-voltage inputs • Timed contacts and instantaneous contacts • Transistor outputs • Single function and multifunction
• Independent ON and OFF settings • 14 time ranges • 8-pin models available • Dial timing relays • UL508
Control Outputs: Time Limit Instantaneous
1 N.O. or SPDT timed
SPDT or DPDT or 2 N.O. + 1 common
DPDT Timed, Transistor SPDT Timed/Instantaneous
DPDT Timed, Transistor SPDT Timed/Instantaneous
DPDT Timed
On-delay Off-delay One shot Operation Modes: Repeat cyclepulse Fleeting off-delay Pulse converter
11 timing modes
On-Delay Off-Delay One Shot Repeat Cycle Off Start Repeat Cycle On Start Signal On/Off-Delay On-Delay One Shot
On-Delay
Repeat Cycle Off Start Repeat Cycle On Start
Time Range
0.05 s…10 hr
0.05 s…60 hr
0.05 s…300 h
0.05 s…300 h
0.05 s…300 h
Supply Voltage
24V AC/DC 110…240V AC 24…48V AC/DC 24…240V AC
12V DC 24V…48V DC 24V…240V AC
12…48V DC 24…48V AC 100…240V AC 100…125V DC
12…48V DC 24…48V AC 100…240V AC 100…125V DC
12V DC 24V AC/DC 48…125V DC 100…240V AC
Contact Rating at 120V AC
5A
8A
5A
5A
5A
Certifications
CE, cULus
CE, cULus cURus, CE, C-Tick cURus, CE, C-Tick cURus, CE, C-Tick
Socket Cat. No(s).
DIN Rail or panel mount
DIN Rail or panel mount
700-HN100 OR 700-HN101 700-HN125 OR 700-HN126
700-HN100 700-HN125
700-HN100 700-HN125
Page
92
96
116
117
117
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
89
Page 90
Relay and Timer Specifications
Bulletin No.
700-HRY
700-HRQ
700-HNC
700-HNK
Type
Star-Delta Timer
True Off-Delay Timer
Miniature Timer
Ultra-Slim Timer
Features
• A wide star-time range (up to 120 s) • Star-delta transfer time range (up to 0.5 s) • UL Recognized
• Dial timing relays • Long power Off-delay times • 11-pin and 8-pin models are available • UL Recognized
• Four different operating modes • DIN Rail mount with socket • Pin configuration same as 700-HC relay
• Ultra-slim timing relay • Four different operating modes • Three operating voltages • DIN Rail mount with socket • Pin configuration same as 700-HK relay
Control Outputs: Time Limit Instantaneous
SPST (Star, Delta) Timed SPST - NO Instantaneous
DPDT Timed
4PDT
SPDT, DPST-NO
Operation Modes:
Star-Delta
True OFF-delay Timer True OFF-delay Timer w/reset
On-Delay One Shot Repeat Cycle Off Start Repeat Cycle On Start
On-Delay One Shot Repeat Cycle Off Start Repeat Cycle On Start
Time Range
0.5 s…120 s
0.05 s…12 min.
0.1 s…10 h
0.1 s…10 h
Supply Voltage
100…120V AC 200…240V AC
48V DC 24V AC/DC 100…240V AC 100…125V DC
12V DC 24V AC/DC 48…125V DC 100…240V AC
12V DC 24V DC 24V AC
Contact Rating at 120V AC
5A
5A
5A
5A
Certifications cURus, CE, C-Tick cURus, CE, C-Tick cURus, CSA, CE, C-Tick cURus, CE, ACA
Socket Cat. No(s).
700-HN100 700-HN125
700-HN100 OR 700-HN101 700-HN125 OR 700-HN126
700-HN103 700-HN128
700-HN121 700-HN122
Page
117
118
103
109
90
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 91
Relay and Timer Specifications
Bulletin No.
700-HT
700-HV
700-HX
Tube Base Timing Relay
Repeat-Cycle Timing Relay
Digital Timer
Pin-style terminals Single range or fixed timers Available as ON- or OFF-Delays
Pin-style terminals Single-range timer Repeat cycle
Digital timer 5 A contact rating Negative transmissive LCD display 10 functions or modes Environmentally friendly - flash memory, no battery NEMA B300 rated NEMA 4/IP66 DIN Rail or panel mount capable
DPDT
DPDT
SPDT
On-Delay Off-Delay
Repeat Cycle
Signal On-Delay 1 and 2 Signal Off-Delay One Shot Repeat Cycle Off Start Repeat Cycle On Start Signal On/Off-Delay Power On-Delay 1 and 2 Twin Timer Cumulative
Time Range
0.1 s…30 min.
0.1 s…30 min.
0.05 s…300 h
Supply Voltage
12V DC 24V DC 24V AC 120V AC 240V AC
24V DC 24V AC 120V AC 240V AC
12…24V DC 24V AC 100…240V AC
Contact Rating at 120V AC
10 A
10 A
5A
Certifications
UR, UL, CSA, CE
UR, UL, CSA, CE cURus, CE, C-Tick
Socket Cat. No(s).
700-HN100 OR 700-HN101 700-HN125 OR 700-HN126
700-HN100 700-HN125
700-HN100 700-HN125
128
133
138
Type
Features
Control Outputs: Time Limit Instantaneous
Timing Operation Modes:
Page
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
91
Page 92
Relay and Timer Specifications
700-FE Economy Timing Relay • Adjustable function and timing range timing relays • DIN Rail mounted without cost of socket • 17.5 mm wide, multi-function or single function • Available as 1 N.O. or SPDT contact output, 5 A • Timing ranges from 0.05 s…10.0 hr • Coil surge protection
Multi-Function This device offers you the flexibility of selecting one of 4 single timing functions. Operating Mode
Contact Output
Timing Range(1)
Input Voltage
Cat. No. 700-FEM1TU22
700-FEM3TU23
ON-delay, OFF-delay, One Shot, Flasher (repeat cycle starting with pulse)
1 N.O.
0.05 s…10 hr (6 settings)
24V AC/DC (2) 110…240V AC 50/60 Hz
ON-delay, OFF-delay, One Shot, Flasher (repeat cycle starting with pulse)
SPDT (1 C/O)
0.05 s…10 hr (6 settings)§
24V…48V AC/DC 24…240V AC 50/60 Hz
(1) Time ranges: 0.05 s…1 s, 0.5…10 s, 0.05…1 min, 0.5…10 min, 0.05…1 hr, 0.5…10 hr. (2) Voltage is either 24V AC/DC 50/60 Hz.
Single-Function This device offers you one specific timing function. Operating Mode
Contact Output
Timing Range(1)
Input Voltage
Cat. No.
1 N.O.
0.05 s…10 hr (6 settings)
24V AC/DC 110…240V AC 50/60 Hz(2)
700-FEA1TU22
SPDT (1 C/O)
0.05 s…10 hr (6 settings)
24V…48V AC/DC 24…240V AC 50/60 Hz
700-FEA3TU23
1 N.O.
0.05 s…10 hr (6 settings)
24V AC/DC 110…240V AC 50/60 Hz(2)
700-FEB1TU22
SPDT (1 C/O)
0.05 s…10 hr (6 settings)
24V…48V AC/DC 24…240V AC 50/60 Hz
700-FEB3TU23
1 N.O.
0.05 s…10 hr (6 settings)
24V AC/DC 110…240V AC 50/60 Hz(2)
700-FED1TU22
SPDT (1 C/O)
0.05 s…10 hr (6 settings)
24V…48V AC/DC 24…240V AC 50/60 Hz
700-FED3TU23
SPDT (1 C/O)
0.05 s…10 hr (6 settings)
24V…48V AC/DC 24…240V AC 50/60 Hz
700-FEE3TU23
1 N.O.
0.05 s…10 hr (6 settings)
24V AC/DC 110…240V AC 50/60 Hz(2)
700-FEF1TU22
SPDT (1 C/O)
0.05 s…10 hr (6 settings)
24V…48V AC/DC 24…240V AC 50/60 Hz
700-FEF3TU23
SPDT (1 C/O)
0.05 s…10 hr (6 settings)
24V…48V AC/DC 24…240V AC 50/60 Hz
700-FEL3TU23
ON-delay
OFF-delay
One Shot
Fleeting OFF-delay
Flasher (repeat cycle starting with pulse)
Pulse Converter
(1) Time ranges: 0.05 s…1 s, 0.5…10 s, 0.05…1 min, 0.5…10 min, 0.05…1 hr, 0.5…10 hr. (2) Voltage is either 24V AC 50/60 Hz or 24V DC.
Special Functions Operating Mode
Contact Output
Timing Range(1)
Input Voltage
Cat. No.
Star-Delta
2 N.O. with 1 Common
0.15 s…10 min (4 settings)
24V…48V AC/DC 24…240V AC 50/60 Hz
700-FEY2QU23
(1) Time ranges: 0.15…3 s, 0.5…10 s, 3 s…1 min, 30 s…10 min.
92
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 93
Relay and Timer Specifications
Accessories - 700-FE Relays Description
Pkg. Quantity
Cat. No.
Panel Mounting Adapter For surface mounting according to drilling plan EN 50 002
5
199-FSA
Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm
10
100-FMS
Function and Connection Diagrams - 700-FE Relays (A) On-Delay U Output
(B) Off-Delay A1/A2
15
A1/A3
A2
18
1 N.O. (SPST)
A1/A2 18 15 16 t
Output LED t
15
A1
18 16
15
A2
18
U
A1/A2
S
A1/B1 18 15 16
Output t
A1 B1 S
15
A2
18 16
LED
1 C/O (SPDT)
1 C/O (SPDT)
(D) One Shot
(F) Flasher (Repeat Cycle Starting with Pulse) A1/A2 18 15 t
15
A1
18
A2
U Output
A1/A2
A1/A2 18 15 16 t
A1
15
A2
18
A1
15
A2
18 16
18 t t t t t 15
LED
1 N.O. (SPST) U Output LED
A1 B1 S
1 N.O. (SPST)
A2
U Output LED
A1/B1 18 15
S
LED
U Output LED
A1/A2
U
18 15 t
1 N.O. (SPST) 15
A1
U Output
A2
18 16 t t t t
A1/A2 18 t 1516
LED
1 C/O (SPDT) 1 C/O (SPDT) (E) Fleeting Off-Delay
(L) Pulse Converter 1)
A1/A2 B1
1)
S A1
15
B1 t LED
A2
18 16
1 C/O (SPDT)
U S Output LED
A1/A2 t t
A1/B1 18 15 16
A1 B1
A2
S
15
18 16
(Y) Star-Delta Timing Relay A1/A2
U t
∆ LED
A1
17
A2
18
17/18 17/28 tu = 50...65 ms
28
∆
Bi-color light-emitting diode: 1 C/O (SPDT) or 1 N.O. Contact Timers LED U = green: Supply voltage available. LED Relay = red: Output is energized.
Single Color light-emitting diode: 2 N.O. with Common ON = green OFF = red
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
93
Page 94
Relay and Timer Specifications
Specifications - 700-FE Relays(1) Attribute
700-FE 1 N.O.
SPDT
Setting Accuracy
±5% of full scale
Repeatability
±1% of setting (typical) By voltage: ±0.01%/%ΔU By temperature: ±0.25%/°C
Tolerance
By voltage: ±0.001%/%ΔU By temperature: ±0.025%/°C
Supply (1) and 110…240V AC, 50/60 Hz
Supply Voltage
24…48V DC and 24…240V AC, 50/60 Hz
24V AC/DC AC
–15%/+10%
DC
–15%/+20%
Voltage Tolerance Power Consumption
0.5 W at 24V DC, 5VA at 240V AC
Time Energized
100%
Reset Time
100 ms
Cable Length (Supply Voltage Control)
Max. 250 m (750 feet) Pulse Control (B1) ≥ 250 ms
Impulse Duration
≥ 50 ms (AC), ≥ 30 ms (DC)
Input Voltage supply voltage range
Input Current
1 mA
Cable Length
Max. 250 m without parallel load between B1 and A2 Max. 50 m with load (< 3 kΩ between B1 and A2 Outputs
Contact Type Dielectric Withstand Voltage
Switching Capacity
1 N.O. contact
1 Form C – SPDT contact
Contact-to-coil
4000V
Power
1250VA
According to IEC 9475-1 According to UL 508
Short circuit Resistance
AC-1
5 A /250V AC (resistive load)
AC-14
1 A/250V AC (inductive load)
DC-13
1 A/24V DC (inductive load) NEMA D300 - 1 A/300V AC 6 A gL (Fast Blow Fuse)
Mechanical
20 million operations
Electrical
0.4 million at 1 A/250V AC, resistive 0.4 million at 0.5 A/250V AC, cos φ = 0.4 0.4 million at 1 A/24V DC, resistive
Life
State Indicator
1 bicolor light-emitting diode (Supply; Relay)
Certifications cULus Listed (File No. E14840, Guide NKCR/NKCR7), CE Marked
Standards
EN/IEC 60947-1, EN/IEC 60947-5-1, UL 508, CSA 22.2 No. 14
Insulation Characteristics
2 kV AC/50 Hz test voltage according to VDE 0435 and 4 kV 1.2/50 μs surge voltage according to IEC 60947-1 between all inputs and outputs
EMC/Interference Immunity
The following requirements are fulfilled: Surge capacity of the supply voltage according to IEC 61000-4-5: Level 3 Burst according to IEC 61000-4-4: Level 3 ESD discharge according to IEC 61000-4-2: Level 3
EMC / Emission electromagnetic fields according to EN 55 022: Class B
(1) Time Characteristics (according to VDE 0435, part 2021)
94
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
Page 95
Relay and Timer Specifications
Attribute
700-FE
Safe Isolation according to VDE 0106 T 101
Climatic Withstand
56 cycles (24 hr) at 25…40 °C and 95% relative humidity according to IEC 60068-2-30
Vibration Resistance
4 g in three axes at 10…500 Hz, test FC according to IEC 60068-2-6
Shock Resistance
50 g according to IEC 68-2-27 Enclosure: IP 40 Terminal: IP 20
Protection Class IEC 60947-1 Weight Certifications
60 g
60 g cULus, CE Certified cULus, Germanischer Lloyd, CE Certified Open: –25…+60 °C Enclosed: –25…+45 °C Storage: –40…+85 °C
Ambient Temperature
Connections
Screw terminal M3 for Pozidriv No.1, Philips, and slotted screws No.2. suitable for power screwdriver. Rated tightening torque 8.8 lb.-in. (max. 1.0 Nm) For terminal cross-sections of 1 x 0.5 mm2…2 x 1.5 mm2 (solid) or 2 x 1.5 mm2 (stranded with sleeve), #20…14 AWG. Finger protection according to EN 50274
Mounting
For surface mounting in any position; snap-on mounting on 35 mm DIN Rail or by adapter and two screws (M4 type)
Disposal
Synthetic materials without dioxin according to EC/EFTA-Notification No. 93/0141/D electrical contacts are AgCdO
(1) Voltage is either 24V DC or AC 50/60 Hz.
Dimensions - 700-FE Relays Approximate dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
80.0 (3-5/32)
13 (0.51)
22.5 (0.89)
43.0 (1-11/16)
45.0 (1-25/32)
75.0 (2.95)
4.3 (0.17)
35.0 (1.38)58.0 (2.28) 17 12 (0.67) (0.47)
66.0 (2-9/16) 70.0 (2-49/64)
17.5 (11/16)
2.0 (0.08)
4.3 (0.17) 9.0 (0.35)
Cat. No. 700-FE…
5.5 (0.22) Cat. No. 199-FSA…
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
95
Page 96
Relay and Timer Specifications
700-FS High Performance Timing Relay • Adjustable function and timing range timing relays • DIN Rail mounted without cost of socket • 22.5 mm wide multi-function or single functions • Available as SPDT or DPDT contact output, 8 A • Timing Ranges From 0.05 s…60 hr • Coil surge protection • Hazardous location version available
Catalog Number Explanation - 700-FS Relays 700
– a a Bulletin Number b -
FS
H
3
U b c d e c Operating Mode
Type of Relay
700
FS
A–On-delay B–Off-delay C–On- and off-delay D–One shot E–Fleeting off-delay F–Flasher (repeat cycle starts with pulse) G–Flasher (repeat cycle starts with pause) I–On-delay pulse generator J–On-delay (pulse controlled) K–One shot/watch dog (pulse controlled) L–Pulse converter
–
U23 f d Contact Output e Timing Range
3–One changeover contact (SPDT)1 C/O
A–0.05…1 s B–0.15…3 s C–0.5…10 s D–1.5…30 s E–0.05…1 min F–0.15…3 min G–0.5…10 min H–1.5…30 min I–0.05…1 hr J–0.15…3 hr K–0.5…10 hr L–3.0…60 hr U–0.05 s…60 hr (1)
f Input Voltage
Z12–12V DC U23–24…48V DC | 24…240V AC 50/60 Hz
(1) Valid for functions "A" and "B" only.
Single Function (With 2PDT 2 C/O contacts) Timing Range(1)
Input Voltage
Cat. No.
(DPDT) 2 C/O
12V DC
700-FSA4UZ12
(DPDT) 2 C/O
24…48V DC 24…240V AC, 50/60 Hz
700-FSA4UU23
12V DC
700-FSB4UZ12
24…48V DC 24…240V AC, 50/60 Hz
700-FSB4UU23
Operating Mode
Contact Output
On-delay On-delay Off-delay
(DPDT) 2 C/O
Off-delay
(DPDT) 2 C/O
0.05 s…60 hr
(1) The time range of "0.05 s…60 hr" is selectable in 12 smaller ranges plus an ON and OFF function for maintenance needs.
Single Function With Hazardous Location Certification(1) (With SPDT 1 C/O contacts) Operating Mode
Contact Output
One Shot / Watch Dog (Pulse Controlled)
(SPDT) 1 C/O
96
Timing Range
Input Voltage
Cat. No.
0.05 s…1 s
24…48V DC 24…240V AC 50/60 Hz
700-FSK3AU23-EX
0.5 s…10 s
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
700-FSK3CU23-EX
Page 97
Relay and Timer Specifications
Multi-Function This device allows the flexibility of selecting one of 8 single timing functions. Operating Mode
Contact Output
Multi-function timing relays 8 Single-functions: A, B, C, D, E, F, I, and L ON and OFF function additional (for installation and maintenance) note: See connection diagrams for further description.
Timing Range
Input Voltage
Cat. No.
(SPDT) 1 C/O
12V DC
700-FSM3UZ12
(SPDT) 1 C/O
24…48V DC 24…240V AC 50/60 Hz
700-FSM3UU23
12V DC
700-FSM4UZ12
24…48V DC 24…240V AC 50/60 Hz
700-FSM4UU23
0.05 s…60 hr
(DPDT) 2 C/O (DPDT) 2 C/O
Multi-Function With Hazardous Location Certification (1) This device allows the flexibility of selecting one of 8 single timing functions. Operating Mode
Contact Output
M Multi-function timing relays 8 Single-functions: A, B, C, D, E, F, I, and L ON and OFF function additional (for installation and maintenance) Note: See connection diagrams for further description.
(SPDT) 1 C/O
Timing Range(1)
Input Voltage
0.05 s…60 h
24…48V DC 24…240V AC 50/60 Hz
Cat. No. 700-FSM3UU23-EX
(DPDT) 2 C/O
700-FSM4UU23-EX
(1) The time range of "0.05 s…60 hr" is selectable in 12 smaller ranges plus an ON and OFF function for maintenance needs.
Special Function Operating Mode
Contact Output
Input Voltage
Cat. No.
12V DC
700-FSH3UZ12
24…48V DC 24…240V AC 50/60 Hz
700-FSH3UU23
12V DC
700-FSH3VZ12
24…48V DC 24…240V AC, 50/60 Hz
700-FSH3VU23
0.15 s…10 min(3)
24…240V DC 24…240V AC 50/60 Hz
700-FSQ3QU18
0.5 s…10 s
24…48V DC
700-FSY2CU23
Timing Range
0.05 s…60 hr Flasher (repeat cycle starting with pulse or pause)
(2)
(SPDT) 1 C/O 2 x 0.05 s…60 hr (2 ranges)
OFF-delay without supply voltages (True OFF-delay)(1)
(SPDT) 1 C/O (DPDT) 2 C/O
700-FSY2DU23
1.5…30 s Star-Delta
2 N.O. + 1 Common
0.05 s…1 min 0.15…3 min
700-FSQ4QU18
24…240V AC 50/60 Hz
0.5…10 min
700-FSY2EU23 700-FSY2FU23 700-FSY2GU23
(1) Due to shock during shipment, the state of the contacts should be verified before initial use. Minimum power on time is 800 msec (2) The time range of "0.05 s…60 hr" is selectable in 12 smaller ranges plus an ON and OFF function for maintenance needs. (3) This time range is selectable in four smaller ranges: 0.15 s…2.5 s, 0.5 s…10 s, 4 s…80 s, 30 s…10 min.
(1)Temp. Code T4A 2A 32VDC MAX.: II 3 G, EEx nL IIC T4 DEMKO 04 ATEX 0404974X 2A 32VDC MAX. Ta 70 °C Ind. Cont. Eq. for Hazardous Location Listed 87SL Class 1, Div. 2, Groups A,B,C,D Class 1, Zn 2, Group IIC Subject devices are to be installed in an ATEX Certified IP54 (as defined in IEC 60529) enclosure and accessible only by the use of a tool.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018
97
Page 98
Relay and Timer Specifications
Multi-Function Timing Relay Function and Time Range Settings - 700-FS Relays Description
SPDT Multi-function timing relays 700-FSM3U includes 10 setting functions:
DPDT
Multi-Time Setting Range 0.05 s…60 h
(A)On-Delay (B)Off-Delay (C)On- and Off-Delay (D)One shot (E)Fleeting Off-Delay (F)Flasher (repeat cycle starts with pulse) (I)On-Delay pulse generator (L)Pulse converter
(1 s) 0.05…1 s (3 s) 0.15…3 s (10 s) 0.5…10 s (1 min) 0.05…1 min (3 min) 0.15…3 min (10 min) 0.5…10 min (1 hr) 0.05…1 hr (3 hr) 0.15…3 hr (10 hr) 0.5…10 hr (60 hr) 3.…60 hr
(On)ON-Function (1) (Off)OFF-Function(1) Note: Switch ⊗ is on DPDT relays only. When switch is down, one contact is instantaneous and one is timed. When switch is up, both contacts are timed. (1) For installation and maintenance.
Accessories - 700-FS Relays Description
Pkg. Quantity
Cat. No.
Setting Knob with Scale (for time setting without tools)
10
700-FSK
Panel Mounting Adapter For surface mounting according to drilling plan EN 50 002
5
199-FSA
Label Sheet 105 self-adhesive paper labels each, 6 x 17 mm
10
100-FMS
Marking Tag Sheet 160 perforated paper labels each, 6 x 17 mm, to be used with a transparent cover
10
100-FMP
Transparent Cover To be used with marking tag sheets
100
100-FMC
Marking Tag Adapters To be used with marking tag: System 1492 W
100
(1)
100-FMA2
(1) Cat. No. 100-FMA2 is only a marking tag carrier. Please refer to the Terminal Block Accessories section, Marking Solutions of this publication for appropriate marker cards to be used with this carrier.
IMPORTANT
98
Versatile Mounting: The 700-FS timing relay can be panel or DIN rail mounted. For best long-term performance, allow at least 5 mm (0.2 in.) of space on each side of the relay for proper ventilation.
Rockwell Automation Publication 700-TD552C-EN-P - October 2018