Spec sheet · Allen-Bradley
Relay and Timer Specifications, Bulletin Number 700
Spec sheet250 pagesPDF 17 MB
Technical data for Allen-Bradley Bulletin 700 relays and timers, including the 700S-CF safety control relays such as the 700S-CFB620.
Names · 1 model
The models it names
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Rockwell Automation technical data for the whole Bulletin 700 relay and timer line. It gives contact data tables, NEMA ratings, timing relay selection and surge suppression, then specifications, accessories and dimensions for general purpose relays (700-HA through 700-HTA), electronic timers (700-FE through 700-HX), NEMA industrial relays, IEC control relays including the 700-CF and 700S-CF safety control relays, and solid-state relays. The 700S-CFB620 appears in the 700S-CF contact assignment tables.
Its parts
- Summary of Changes
- General Information
- General Purpose Relays
- General Purpose Electronic Timers and Counters
- NEMA Industrial Relays
- IEC Control Relays
- Solid-state Relays
From the sheet
Key facts from this sheet
Each line names its page in the PDF.
This technical data sheet covers the whole Allen-Bradley Bulletin 700 range of relays and timers; this summary draws on its pages for the 700-CF and 700S-CF IEC control relays. The 700S-CF section explains how to build a safety control relay number from its contact arrangement and coil voltage code, and gives life, terminal, accessory and dimension data. Its DC coil code table for the 700S-CF lists EJ (24V DC, electronic with diode) but not ZJ.
- Device
- 700S-CF IEC safety control relay with mechanically linked contacts (IEC 60947-5-1) p. 207
- Contacts
- 700S-CFB620: 6 N.O. and 2 N.C., gold-plated bifurcated on all contacts p. 208
- Coil
- Code EJ: 24V DC, electronic with diode p. 208
- Auxiliary block
- Permanently fixed front-mounted auxiliary contact block p. 207
- Life
- 700S-CF: 15 million operations mechanical; 1.5 million electrical at AC-15 (240V, 3 A) p. 209
- Main terminals
- 700S-CF: 1.5…6 mm2, 16…10 AWG; 1.5…2.5 N•m (13.3…22 lb•in) p. 209
- Auxiliary terminals
- 0.5…2.5 mm2, 18…14 AWG; 1…1.5 N•m (8.9…13.3 lb•in) p. 209
- Front marking
- Red cover and mechanically linked contact symbol on the front p. 207
- Accessories
- Side-mount auxiliary contact block (1- or 2-pole), electronic timing module, interface module, surge suppressor, labels and marking tags p. 210
- Standards
- UL 508, CSA C22.2 No. 14, EN/IEC 60947-1, -5-1 p. 209
- Certifications
- The sheet states cULus Listed (File No. E14840), CE Marked, CCC Certified, and third party certification SUVA p. 207, 209
What this sheet walks you through
- Choosing a 700S-CF relay by contact arrangement and AC coil voltage code p. 207
- Choosing a 700S-CF relay with a DC coil voltage code p. 208
- Terminal numbers of the 700S-CF contact arrangements p. 209
- Dimensions and accessories of the 700S-CF relays p. 210
- Building an E-stop safety circuit with five safety outputs from three 700S-CF relays p. 211
- Contact ratings of the 700-CF and 700S-CF relays p. 200
Good to know
- The listed relay numbers are incomplete until a coil voltage code is added. p. 208
- The AC-12 and AC-15 ratings in the selection tables are for the 700S-CF only; 700S-CFB ratings are in the specifications. p. 208
- Stranded wire with 16 or more strands needs an end ferrule. p. 209
- Dimensions are approximate and not meant for manufacturing. p. 210
Questions this sheet answers
What does EJ mean in 700S-CFB620EJC?
EJ is the DC coil voltage code for 24V DC, electronic with diode. p. 208
How many contacts does a 700S-CFB620 relay have?
Six normally open and two normally closed, all gold-plated bifurcated. p. 208
What is the difference between the 700S-CF and the 700S-CFB?
The 700S-CF has standard main contacts with gold-plated bifurcated front contacts; the 700S-CFB has gold-plated bifurcated contacts throughout. p. 207
What is the mechanical life of a 700S-CF safety relay?
15 million operations. p. 209
Can 700S-CF relays be used to build an E-stop circuit?
Yes. The sheet shows a circuit with five safety outputs built from three 700S-CF relays. p. 211
Contents
Chapters and sections
Each line opens the PDF at its page.
- Relay and Timer Specifications1
- Summary of Changes2
- General Information3
- General Purpose Relays9
- 700-HA General-purpose Relay12
- 700-HB Square Base Relay22
- 700-HD Flange Mount Square Base Relay28
- 700-HF Square Base Relay32
- 700-HC Miniature Ice Cube Relay39
- 700-HK Slim Line Relay44
- 700-HL Terminal Block Relay50
- 700-HL 2-pole Terminal Block Relay52
- 700-HLF Terminal Block Timing Relay60
- 700-HP Slim Line Relay64
- 700-HJ Magnetic Latching Relay71
- 700-HG Power Relay75
- 700-HHF Flange Mount Power Relay80
- 700-HTA Alternating Relay83
- Product Overview9
- General Purpose Electronic Timers and Counters89
- NEMA Industrial Relays149
18 more lines, from page 149 on
The whole text · 27 parts
Read the sheet here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
- Pages 1 to 81-8
- General Purpose Relays, pages 9 to 189-18
- General Purpose Relays, pages 19 to 2819-28
- General Purpose Relays, pages 29 to 3829-38
- General Purpose Relays, pages 39 to 4839-48
- General Purpose Relays, pages 49 to 5849-58
- General Purpose Relays, pages 59 to 6859-68
- General Purpose Relays, pages 69 to 7869-78
- General Purpose Relays, pages 79 to 8879-88
- General Purpose Electronic Timers and Counters, pages 89 to 9889-98
- General Purpose Electronic Timers and Counters, pages 99 to 10899-108
- General Purpose Electronic Timers and Counters, pages 109 to 118109-118
- General Purpose Electronic Timers and Counters, pages 119 to 128119-128
- General Purpose Electronic Timers and Counters, pages 129 to 138129-138
- General Purpose Electronic Timers and Counters, pages 139 to 148139-148
- NEMA Industrial Relays, pages 149 to 158149-158
- NEMA Industrial Relays, pages 159 to 168159-168
- NEMA Industrial Relays, pages 169 to 178169-178
- NEMA Industrial Relays, pages 179 to 186179-186
- IEC Control Relays, pages 187 to 195187-195
- IEC Control Relays, pages 196 to 204196-204
- IEC Control Relays, pages 205 to 213205-213
- IEC Control Relays, pages 214 to 219214-219
- Pages 220 to 227220-227
- Pages 228 to 235228-235
- Pages 236 to 243236-243
- Pages 244 to 250244-250
The file